Комментарии
@harounemoussa2453
@harounemoussa2453 20 дней назад
did it thank you Mr jim
@jimdiggins101
@jimdiggins101 19 дней назад
You betcha
@darrelthompson
@darrelthompson Месяц назад
Greate information in this video. Is there a link somewhere that I can download your Resistance Check Spreadsheet?
@OdiagamerAb
@OdiagamerAb Месяц назад
Thank you sir....god bless you....keep posting knowledge.....i really appreciate your hardwork...
@hatemmoussa7467
@hatemmoussa7467 2 месяца назад
How much is this kit?
@raulmota1318
@raulmota1318 2 месяца назад
Hello buddy, can you provide this spreadsheet?
@sivasrinivas3716
@sivasrinivas3716 3 месяца назад
can i use 8 mm probe to measure radial vibration of a 27 mm nickel alloy shaft?
@Time4yes
@Time4yes 4 месяца назад
Say, I am using the same valve but I have been given values to start the valve travel at 11 and 13 psi as my full travel. Should I adjust the spring tension first according to these values or should I do on the positioner?
@jimdiggins101
@jimdiggins101 4 месяца назад
The actuator should have a rated benchset and travel distance. When the control valve assembly was engineered, the actuator specs were selected based on the force required to operate the valve. This test verifies the actuator performs according to the original design. The positioner reduces the error that is a result of mechanical friction.
@Time4yes
@Time4yes 4 месяца назад
Thanks
@sam.castaneda22
@sam.castaneda22 4 месяца назад
Need some videos of repairs out in the field
@sam.castaneda22
@sam.castaneda22 4 месяца назад
Im having issues with a valve currently for leaking by. Hard to find the right kits or someone is not getting the right info for them. Is there a website or something to find the right kits? Based in west texas.
@jimdiggins101
@jimdiggins101 4 месяца назад
Emerson owns Fisher Valves. From the Emerson website you can find the local business partner as well as drawings.
@cavourmartinelli9381
@cavourmartinelli9381 4 месяца назад
Simple explanation, but hard to find it. Do you know any supplier I can buy proximeters from? I am located in Brazil.
@jimdiggins101
@jimdiggins101 4 месяца назад
I don't know. Baker Hughes owns Bently Nevada and they have a global presence. I'm sure there is a local representative. I would check their website.
@Gregjm-v3t
@Gregjm-v3t 5 месяцев назад
Hi. Where could I get your excel table ? I would like to get it
@jimdiggins101
@jimdiggins101 5 месяцев назад
Build it in excel. I show all the necessary formulas in one of my videos.
@Gregjm-v3t
@Gregjm-v3t 5 месяцев назад
Thank you Sr. I'll do it
@dipakbhalodia7155
@dipakbhalodia7155 5 месяцев назад
Can you provide exell sheet formula
@dipakbhalodia7155
@dipakbhalodia7155 5 месяцев назад
Your email id please send
@liranhefetz5527
@liranhefetz5527 5 месяцев назад
PLEASE... Can you provide excel sheet? Thank you very much! +++
@sajidkamal8199
@sajidkamal8199 5 месяцев назад
What is tha input and output radial axial vibration plz answer
@jimdiggins101
@jimdiggins101 5 месяцев назад
I am not sure what you are asking. Can you provide some context?
@vinaysane5435
@vinaysane5435 6 месяцев назад
Like Video.
@omagbemigold2321
@omagbemigold2321 7 месяцев назад
NICE JOB 👍 WELL EXPLAIN
@s0nnyburnett
@s0nnyburnett 7 месяцев назад
Simple to the point explanations, thank you.
@karimkrimou1513
@karimkrimou1513 7 месяцев назад
Thanks sir, it is a very informative vidéo with a clear explanation
@abylabylabyl
@abylabylabyl 8 месяцев назад
where can I get the test sheets?
@wapeekung
@wapeekung 9 месяцев назад
Can you provide excel sheet? Thank you very much
@xrafter
@xrafter 9 месяцев назад
How does the eddy current generate in the metal? Does the varrying magnatic field has something with it?
@jimdiggins101
@jimdiggins101 9 месяцев назад
You are correct
@jeanoliveira8837
@jeanoliveira8837 9 месяцев назад
WOULD YOU LIKE TO SEND THE TALEBA FOR SENSOR CALIBRATION
@kithtube
@kithtube 10 месяцев назад
Good exlonation jim,thanks.
@husseinjavan-bg6sv
@husseinjavan-bg6sv 10 месяцев назад
Dear sir. I have two probes with different part number, PN: 86691-08065-0435-25 and PN:86691-09246-0435-25. I only know they are 2.5 m length but i am not sure they can be used interchangeably. Is it possible? What are their differences?
@jimdiggins101
@jimdiggins101 10 месяцев назад
I don't have that manual, so I cannot say for certain. From a performance standpoint it should work. Difference will be in the custom features. Such as mounting options, length of armored jacket, etc..
@siyabonga6156
@siyabonga6156 11 месяцев назад
Very good explanation, now I have a better understanding of Proximity probes.
@instrumentationbasicknowle2872
@instrumentationbasicknowle2872 11 месяцев назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-qd2-NfglGfw.htmlsi=pr6vKxgK2ZchdIKA
@josepatino7142
@josepatino7142 11 месяцев назад
Can you provide excel sheet? Thank you very much
@arturogonzalez2220
@arturogonzalez2220 Год назад
Jim, where do you get the values for Peak to Peak travel and Measured Value?
@jimdiggins101
@jimdiggins101 Год назад
I posted videos explaining how to perform the dynamic and static tests.
@hondat7435
@hondat7435 Год назад
hello, when i connect the power supply 24VDC positive to the com and negative to the Vt(-24 VDC) it creates an alarm on the power supply and shut down the power supply. Please advice on wiring?
@jimdiggins101
@jimdiggins101 Год назад
Power to com and -24. Output signal to out.
@crunchyrollo7474
@crunchyrollo7474 Год назад
Thank you very much for the information, although I have a question, at minute 2:24 you put the value of 1 in the voltage column. why 1? What shouldn't be 10mil*200mV= 2V?
@jimdiggins101
@jimdiggins101 Год назад
The response rate of 200mV / mil is only valid within the range of linearity. 0-10 mils is outside this range.
@nukeworker83
@nukeworker83 Год назад
Best video on youtube!
@michaelmorgan9536
@michaelmorgan9536 Год назад
How tight should the jams be tightened. What are the risks of not setting the jam nuts?
@jimdiggins101
@jimdiggins101 Год назад
The jams keep the connection block in place In most applications, the feedback arm connects to the block. In some cases, even a slight rotation can create feedback error or loss of position indication.
@user-hi7rf3bp8h
@user-hi7rf3bp8h Год назад
What do you supply proximity power with? What kind of lines?
@mohammedsaib3844
@mohammedsaib3844 Год назад
Excellent work 👍
@shanegovender6780
@shanegovender6780 Год назад
Hi thanks for the video ! We bought a couple of these fisher control valves and we noticed that they don't all have the same bench set values, what's the reason for this ? I also noticed that you did your bench set from 9 to 15 psi, so when will the valve start to move? Is it 9 psi or 3 psi?
@jimdiggins101
@jimdiggins101 Год назад
The bench set is engineered to operate the valve based on the process stream and will determine the pressure required to open the valve.
@shanegovender6780
@shanegovender6780 Год назад
@@jimdiggins101 thanks so much for the Response! Atleast now I know that I didn't buy the wrong things 😃
@JesusEmmanuelGoneCadena-pd2ug
Dear Jim thanks for video, I only have two questions, at the end we obtained values that were out of tolerance, right? And this was probably because we use other extension cable model, right? In advance thanks for your response! And good job!! 🤘
@jimdiggins101
@jimdiggins101 Год назад
Correct. Incorrect length is the most common cause of error
@andinstrumentcontrol4159
@andinstrumentcontrol4159 Год назад
Excellent!Can you provide excel sheet? Thank you very much
@InstrumentationTechnicianVP
Thank you for your video. I have a confused question " Can vibration monitoring module supply +24VDC and -24VDC ?"
@jimdiggins101
@jimdiggins101 Год назад
Are you referring to the proximitor card on the bently nevada monitoring rack?
@InstrumentationTechnicianVP
@@jimdiggins101 Yes, Sir
@uncle_joe
@uncle_joe Год назад
interesting...
@playaloc
@playaloc Год назад
I seen some valve bodies have a line on it instead of a flow arrow? Is the line an indication for flow?
@jimdiggins101
@jimdiggins101 Год назад
Some have a line on the body that has a downward angle, which represents the flow path through a globe valve. That may be what you are referring to. This alone does not indicate flow however, but for general service, you install with the angled downward part facing up stream so the flow enters below the plug and flows up through the port.
@playaloc
@playaloc Год назад
@@jimdiggins101 thanks for the info.
@lovesaudiaam3189
@lovesaudiaam3189 Год назад
Excellent
@jimdiggins101
@jimdiggins101 Год назад
Thanks
@nino4676
@nino4676 Год назад
Thanks
@Bwup
@Bwup Год назад
thank you
@jimdiggins101
@jimdiggins101 Год назад
You're welcome
@ShuhardRedd
@ShuhardRedd Год назад
Thank you!
@jimdiggins101
@jimdiggins101 Год назад
Welcome!
@ranjitkar2381
@ranjitkar2381 Год назад
Hi...Mr Jim... thanks for this informative video...kindly could you provide spreadsheet for me...
@hovanuc187
@hovanuc187 Год назад
Hi jim diggins. Why is the voltage value according to the datasheet approximately negative -1 to -17vdc. But you take the positive value 1 to 17 vdc
@jimdiggins101
@jimdiggins101 Год назад
Voltage is a potential difference and the polarity of the voltage has no bearing on the measurement. Use negative voltage if you like.
@agusgimbuk8365
@agusgimbuk8365 Год назад
Excuse me sir. My name is agus. I have some question related with vibration system. 1. Whats the function for minus DC power supply? 2. Whats correlation between DC power supply and AC power supply which generated by probe?
@jimdiggins101
@jimdiggins101 Год назад
Answer 1: The polarity doesn't matter unless you are a transistor, which in this case is why the polarity is reversed. For the purpose of understanding how it works, it makes little difference.
@jimdiggins101
@jimdiggins101 Год назад
Answer2: Think of the AC as DC with a wave. Normal AC changes polarity, this doesn't. You just have to switch a meter to AC to measure the dynamics of the sinewave that is created. It's AC with a voltage bias.
@devivara1162
@devivara1162 Год назад
How belt conveyor receive TPH from DCS??
@jimdiggins101
@jimdiggins101 Год назад
Depends on system.
@devivara1162
@devivara1162 Год назад
Sir what is solnide valve???
@jimdiggins101
@jimdiggins101 Год назад
A solenoid valve-discrete valve activated by a magnetic coil. In a control valve it is commonly used to interrupt air supply and force to a fail state.
@devivara1162
@devivara1162 Год назад
Sir why gearbox and coupling needed for alternator in powerplant???