@@instrumentationknowledge1373 sir hotwell level ko mainten karne ke liye 2 control valve laga(1 recirculation and 1 export valve)hai sir mujhe yokogawa UT 35a controller ka use karna taki level setpoint ke according mainten ho
Sir I'm facing a problem in ut 35 where after giving 4ma signal I'm getting -300 as error even when I've set the low range as zero I want to do calibration of it can you please explain it ..please sir
Please set lower range and upper range and set input 4 to 20 ma And set output according Control valve . In case of Control valve and input Pressure transmitters Please off derivative. P = proportional I= integral D = off In case of Pressure transmitter input.