@sergus2 hi there, hope you are doing good. someone changed in/output voltage values at adjust menu, if you share that values it will be highly appreciated. i have the password of adjust menu, dont mind about that.
@@TarinSalehTradinglogisticServiI can't see now in which menu item of the UPS the parameters for calibrating the input/output voltage values are, but in the service program there are menu items: AC input\Vinp L1 RMS calib., AC Bypass\Vbyp L1 calib., AC Output\Vinv L1 calib.
@@sergus2 if u have the UPS available with u now, then it will be ur honest if share the adjust menu settings with me... and if u dont have it currently then dont mind about it
Sir, I want to ask about the UPS S 8 problem. If the power source is off, why is the UPS also off? Why can't automatically back up? Even though the battery status is normal, it's full.
Прикольно: у вас нагрузка отображается 1:40 в 200 Вт. Скажите: а возможно ли значение ниже, чем 200 Вт??? То есть будет ли он показывать на экране и в софте менее 200 Вт и на какой мощности находится "мертвая зона", а то ориентироваться на индикатор 25% такое себе занятие. Правда, у вас и модель послабее, может и может. У меня, к примеру, KU9103S-RT 125 Вт не видит. Хотя по инструкции, внешнему виду похоже, что у них общий папа. В Китае.
The password is dynamic and is generated in the service program. In addition, you need to know the eeprom number with this battery service requirement setting. I don't have a service program, so I can't help.
@@oleja3196 если ибп полностью разрядил свои батареи и выключился, то когда придёт питание от сети, тогда ибп сам включиться и через некоторое время сам подаст питание на подключенную нагрузку, эта функция ибп автоматически включена, с ИБП делать ничего не нужно.
Hi, I am facing the alarm code 4684, and I would like to reset the alarm. Would you mind sharing me how to do it? And I believe it requires also password. It would be great if you could share me. Thanks in advance.
@@ocheadoga303 Max. battery charging current (programmable) the beginning of battery recharge at nominal load. For this UPS 60kVA at PF=0.8 lag. - 33A, at PF=0.9 lag. - 17A
Check DS3-PSU Power supply board 24 volt DC. DS3-INV board power supply 1 out of tolerant check main power supply board. DS-PIM1 microcontroller board connectors contactless. After checks and troubleshooting, you will need to reset the error using the service software or code.
В обоих ИБП один и тот же тип силовых модулей (с зеленой полосой, то есть) ? Возможно, в данном случае неравномерное деление обусловлено отсутствием нагрузки либо недостаточно качественной калибровкой выходного напряжения.