Hi, I would like to ask a question. How to save our parameter setting at ms300? because I when I was turn off the inverter and tried to running again, the inverter need seeting again
Hi, can you do a video on how to configure the ms300 to a lathe machine(Grizzly / Powermatic) using external switches/buttons to run the run/forwar/stop/reverse
Hi pds4927. I'm Steve. I am trying to do just that..get an MS300 inverter to work on a PM 3520B. Did you ever have any luck configuring it with your lathe? I'm desperate. There are many more options than the original S inverter.
Hi, for 4-20mA use the ACI terminal as signal and ACM terminal as common. For speed reference, 03.00 = 0, 03.01 = 1, 00.20 = 2. For PID feedback, 03.01 = 5.
Using an external 24VDC input, see the control terminal wiring fig 6-5 in the manual. Pulse input - the frequency of the pulses determines the speed. Check the description in parameter 10.16 External Up / Down - 00.20, 02.01 ~ 02.07 set to 19 and 20
I am wanting to run a vacuum pump for my cnc table. I was to told split the wire from the vacuum on switch and put it on m1 and vcm. Is this a safe method to run the drive?
It can be other resistances but you will lose range on the pot. For example, at 50% rotation on a 10k pot you'll be 5k ->10V -> 100% reference on the drive.