Тёмный

#347 

Andreas Spiess
Подписаться 475 тыс.
Просмотров 147 тыс.
50% 1

In video #321, we looked at DC current sensors. Today we will look at how to measure AC mains currents, which is much more difficult. And more dangerous because it can kill you if you do not pay attention. And, because measuring AC power is useful in home automation, we will also look at how to measure voltage and calculate power. To measure correctly, we have to learn about phase shifts and power factor. And I will tell you the essential rule to live long around high voltages.
I am a proud Patreon of GreatScott!, Electroboom, Electronoobs, EEVblog, and others
Links:
Mains checker: s.click.aliexpress.com/e/_dZf...
HCPL3700: s.click.aliexpress.com/e/_dZx...
ZMPT101B: s.click.aliexpress.com/e/_dX7...
Dimmer: s.click.aliexpress.com/e/_dWs...
Current Transformer: s.click.aliexpress.com/e/_dZi...
UT204A: s.click.aliexpress.com/e/_dVA... or amzn.to/2Pb3eRb
PZEM-004T: s.click.aliexpress.com/e/_dZ2... or amzn.to/2P76TiS
Sonoff POWR2: s.click.aliexpress.com/e/_dW0... or amzn.to/3hQUHzj
Shelly EM and 3EM: shelly.cloud/products/shelly-...
Power Monitor: s.click.aliexpress.com/e/_dTS...
Lots of interesting stuff: innovatorsguru.com/zmct103c/
Dimmer Library: github.com/RobotDynOfficial/R...
Library for ZMPT101B: github.com/MartinStokroos/Tru...
DSO213 Oscilloscope (update from my 203): s.click.aliexpress.com/e/_ADoGHF
The links above usually are affiliate links which support the channel (no additional cost for you).
Supporting Material and Blog Page: www.sensorsiot.org
Github: www.github.com/sensorsiot
My Patreon Page: / andreasspiess
Discord: / discord
If you want to support the channel, please use the links below to start your shopping. No additional charges for you, but I get a commission (of your purchases the next 24 hours) to buy new stuff for the channel
My Amazon.com shop: www.amazon.com/shop/andreassp...
For Banggood bit.ly/2jAQEf4
For AliExpress: bit.ly/2B0yTLL
For Amazon.de: amzn.to/2r0ZCYI
For Amazon UK: amzn.to/2mxBaJf
For ebay.com: ebay.to/2DuYXBp
profile.php?...
/ spiessa
www.instructables.com/member/...
Please do not try to Email me or invite me on LinkedIn. These communication channels are reserved for my primary job
As an Amazon Associate, I earn from qualifying purchases

Наука

Опубликовано:

 

9 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 474   
@johnnyhu
@johnnyhu 3 года назад
Mr. Spiess: Beautiful but... your Power Factor formula at 17:57 is wrong. It is not P/Q but, instead, P/S. Power Factor is the cos(theta) and the closer to 1, the better.
@AndreasSpiess
@AndreasSpiess 3 года назад
True! It would be very high if Q is zero!
@johnnyhu
@johnnyhu 3 года назад
Indeed, Mr. Spiess. As you know, we, the machines, must obey the Law Zero of Robotics/AI, "Thou shalt not divide by zero". I must say yours is a great channel with great and very well done material, which by the way made me to be your subscriber. Thank you for all the videos you've published so far. They've really helped me to upgrade several of my systems.
@mawamatakama5150
@mawamatakama5150 3 года назад
The "One hand rule" was the first thing we learned at school. Seeing it in this video, also as first point, show how well educated and well versed Mr Spiess is in Electricity and Electronics.
@StringerNews1
@StringerNews1 3 года назад
We learned to keep our left hand in our pocket whenever possible, as that's the side that the heart's ventricles lean towards. So there's a slightly lower chance of damaging the heart.
@AndreasSpiess
@AndreasSpiess 3 года назад
As I said: I am no specialist. And I am left-handed. So I seem to have a problem with your rule @StringerNews ;-)
@StringerNews1
@StringerNews1 3 года назад
@@AndreasSpiess Blame my high school electronics teacher, it was his rule. IIRC he made an exception for lefties.
@successmiracles
@successmiracles 3 года назад
@@StringerNews1 I second that 👍
@keithroberts5946
@keithroberts5946 3 года назад
Was told to brush the back of your hand against metal cases - if it was energised your arm would retract away from the danger If you grip an energised circuit you cant let go
@AndrewDanne
@AndrewDanne 3 года назад
An excellent review of the topic. I had forgotten allot of this. Power factors, RMS and needed a refresher. Very educational and you are a great teacher. Thank you.
@EpsRae
@EpsRae 3 года назад
best content to see before bed time in NA, thank you Andreas! Very informative, simple and Swiss accenty. Happy to be in the front row.
@mawamatakama5150
@mawamatakama5150 3 года назад
* Swiss accent intensifies *
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you enjoyed it! So you are a "night owl" ;-)
@BubonicPestilence
@BubonicPestilence 3 года назад
Thank you very much for making such videos, which helps not someone who learning electricty from 0, but jump-starters and diy-ers who started w/o advanced/deep-basic knowledge in electricity!
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome.This channel is made for ambitious people ;-)
@LordGeva
@LordGeva 3 года назад
I'm gonna need to watch this video again and again to apprehend the concepts, but its clearly explained as always. Thanks Andreas!
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad it was helpful!
@GeorgeWMays
@GeorgeWMays 3 года назад
Excellent, as always. Thank you for an instructive and entertaining video. Much appreciated.
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you enjoyed it!
@pamdemonia
@pamdemonia 3 года назад
As an electrician mainly working in commercial settings (3 phase here) I am extremely jealous of your 3 phase residential power! Sometimes the single phase (one 220v phase split to 2 110v legs) we have for residential power is very annoying! Very interesting video, btw. Thanks for all you do for us out here in RU-vid land!
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome! Here, distances are short. Maybe this is the reason we use this method.
@Glenn.Cooper
@Glenn.Cooper 3 года назад
Excellent job covering the top. I very much appreciate it!
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad it was helpful!
@isabido
@isabido Год назад
I loved the video and how it is presented. Very practical and of great didactic contribution, a pity not to have seen it until this 2022! I just found your channel, you already have one more subscriber.😉
@AndreasSpiess
@AndreasSpiess Год назад
Welcome aboard the channel!
@tatavox1408
@tatavox1408 3 года назад
Good Job ! it's a real pleasure to watch you ! Please continue , .. Success !
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you, I will!
@RickB3n
@RickB3n 3 года назад
Grest work, as always👍
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you! 👍
@SmithyScotland
@SmithyScotland 3 года назад
Thank you for putting the links in the description.
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome!
@mkm_is_here
@mkm_is_here 3 года назад
Thanks sir, very informative and useful for my projects, and the information delivery is very good. Subbed!
@AndreasSpiess
@AndreasSpiess 3 года назад
Welcome aboard the channel!
@avejst
@avejst 3 года назад
Great video as always 👍 Thanks for sharing 👍😀
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome!
@jpjude68
@jpjude68 3 года назад
from what i remember from my tuitions, power factor can be corrected by using capacitors of the right size on the mains wires. However there's another neat trick : if the mains are 3-phased, and the power factor is similar between all 3 live wires, the power factor can be corrected using a synchronous AC motor (yes, synchronous, not asynchronous) that runs without load. It'll probably heat up, but the motor ends up consuming the bad power factor just as capacitors would.
@AndreasSpiess
@AndreasSpiess 3 года назад
You are right. As I said I am no specialist. But sure, you can (and have to) correct the power factor in large installations.
@matthewmaxwell-burton4549
@matthewmaxwell-burton4549 3 года назад
It is called a synchronous condenser. On a synchronous AC motor you can vary the amout of reactive power consumed or produced by changing the DC voltaged applied to the rotor.
@jpjude68
@jpjude68 3 года назад
@@matthewmaxwell-burton4549 Ah, good to know. cheers!
@TheEmbeddedHobbyist
@TheEmbeddedHobbyist 3 года назад
When looking at RMS to DC converters, it good to look at how well they respond to the signal "Crest Factor" which is an indicator of how close the signal being measured is to a sine wave. e.g. Crest factor is a parameter of a waveform showing the ratio of peak values to the effective value.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for the addition. If I remember right, GreatScott did once a test with such converters. So far I never worked with such converters.
@vk3fbab
@vk3fbab 3 года назад
If only I'd seen your video 18 months ago. Caught out by measuring voltage and current across different phases. Data looked correct but power consumption was too low compared to the bill. Turns out the electrician that did the install of 3P meter had an off by 1 error with the voltage feed on the 3P bus bar. Took me a while to figure that one out. This was using Schneider Electric measuring gear. Quite accurate but expensive. Great work as always.
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad to read that my theory worked ;-) I assume this not only happened to you. This was one reason for that video.
@bmacdoug
@bmacdoug 3 года назад
Thank-you Herr Eng. Spiess for all of your great videos. Your information is always accurate and very professionally presented. In North America, houses do indeed have a 120/240 V split phase system that work well. Large apartment buildings often have three phase systems with 120/208 V, using the phase voltage to create 208V rather than 240V. This is annoying as kitchen ranges and clothes dryers meant to work on 240V are now operating at 208, which delivers only 75% of the expected power.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for the additional information!
@TishSerg
@TishSerg Год назад
Does that mean you in America can use European appliances that need 220-240V by connecting them not to Live and Neutral wires but to Live1 and Live2?
@TishSerg
@TishSerg Год назад
Oops, I missed that you in America have 60 Hz, but we in Europe have 50 Hz. So attention is needed regarding freq range the device can work on.
@GordieGii
@GordieGii Год назад
You missed one important detail. 208V, 3 phase, 4 wire power (3 phases plus Neutral, what you call 120/208) is used here in Canada and the USA in apartment building and factories because you can run 3 phase motors for booster pumps, HVAC units, and industrial equipment AND 120V outlets (from any phase to neutral) from the same transformer and breaker panel. Industrial motors here are usually rated for 220V because 208 and 240 both fall within the +/- 10% voltage tolerance. So, while it is inconvenient for your 240V appliances it holds major cost and complexity savings for the electrical systems of the building.
@pablom695
@pablom695 2 года назад
never heard that advice about the hand on the pocket. great way to not forget !
@AndreasSpiess
@AndreasSpiess 2 года назад
Simple rules are a good thing ;-)
@jmaguilarr
@jmaguilarr 3 года назад
great teacher as always
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you! 😃
@Taran72
@Taran72 3 года назад
This video was extremely useful!! I am in the process of making a datalogger with Arduino and also exploring different methods to connect to mains and DC powered devices. Thanks.
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad it was helpful!
@bobpaydar
@bobpaydar 3 года назад
thanks for this video and also for your wonderful youtube channel ❤️🌹
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you enjoy it!
@libervolucion
@libervolucion 3 года назад
This is a really great video, thank you
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you liked it!
@rigfix
@rigfix 4 года назад
It's a pleasure to sit in the first row :)
@AndreasSpiess
@AndreasSpiess 4 года назад
Thank you!
@PhG1961
@PhG1961 3 года назад
Indeed ! We're over 241K at this moment. Rather crowded here on the first row. But where else would you like to be then ?
@rigfix
@rigfix 3 года назад
@@PhG1961 By first row, I meant early access as a Patreon :)
@LarryKapp1
@LarryKapp1 3 года назад
Thanks for the explanation of the meter at the very end. I have one of these and wondered about the watts reading when the power factor was low. I have a solar system and inverter so the power coming out of my inverter is not accurate just from the watts reading unless power factor is 1. When you explained that it should be labeled VA that makes more sense to me.
@AndreasSpiess
@AndreasSpiess 3 года назад
Both are needed. On motors you sometimes find both numbers.
@judo-rob5197
@judo-rob5197 3 года назад
Excellent explanations.
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you liked it
@FrankZosso
@FrankZosso 4 года назад
Very well explained!!!
@AndreasSpiess
@AndreasSpiess 4 года назад
Thank you!
@TheUnofficialMaker
@TheUnofficialMaker 3 года назад
the chips graphic was Hilarious! well done
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you!
@TitomnJeswen
@TitomnJeswen 3 года назад
Great videos! 🥨🥚🍟
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you like them!
@efimovv
@efimovv 3 года назад
Very useful, thank you!
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome!
@roguethinker6284
@roguethinker6284 3 года назад
Superb video!
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you very much!
@DragonsTaco
@DragonsTaco 3 года назад
Excellent video.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you very much!
@JohnnieHougaardNielsen
@JohnnieHougaardNielsen 3 года назад
In addition to better measurement, another advantage of the Sonoff Pow R2 over the older version is improved fire safety of the design.
@AndreasSpiess
@AndreasSpiess 3 года назад
Good to know. Thanks!
@moeburn
@moeburn 2 месяца назад
I built one of these home energy monitors for my split phase system using two CT clamps, an AC/AC transformer, an Arduino Uno, and Robert Wall's EmonlibCM. The latter is essential for this project because he takes all the complex calculations from an electrical engineering PHd background and does them for you, to the precise timing known on the Uno's chipset. It's also surprisingly dangerous - even though the CT clamps aren't actually touching the mains wire, if they do not have a load resistor or a TVS diode, they will explode in a big puff of smoke if you clamp them around a wire carrying 100 amps+ of current. Because with no load resistor, they will generate theoretically millions of volts. As i nearly discovered.
@AndreasSpiess
@AndreasSpiess 2 месяца назад
Your clamps are simple transformers with one primary and many secundary turns. So indeed, they are made to create high voltages...
@zolatanaffa87
@zolatanaffa87 3 года назад
Hi Andreas. Excellent and accurate explanation. In Italy only those who request a three-phase contract receive all three phases: the energy meters are simpler and less expensive (from corridor whispers they should cost less than 40 euros each to the energy distributor, considering that in Italy only for E-distribution we talk about 33 million meters, three-phase and single-phase together ... with a hundredth of difference each we make a good figure. I have seen that in Germany, the only country where I have been able to see a home meter, instead they carry three-phase electricity also in homes, I don't know in the rest of Europe. Here in Italy, at least years ago, before the liberalization of the market, (Enel was a non-profit national body, but in fact it was a monopoly) the customer who wanted a three-phase contract in a civil home had to sign an indemnity on the dangerousness of the voltage at 400V. In all cases, the distribution lines are all three-phase at 400V, with the same cross-section of cables it transports twice the power compared to a single-phase system, but the derivations for the individual supplies (we could improperly call it the last mile) are all single-phase to exception of those who specifically request a three-phase supply
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for the update. Here in Switzerland we also have three phases to all homes.
@stuartajc8141
@stuartajc8141 3 года назад
@@AndreasSpiess In the UK we have a single phase to most homes. We can request three, but at a cost. Factories etc. have three phases.
@robertclark8351
@robertclark8351 3 года назад
The Kill a Watt type meters are convenient and have become reasonably inexpensive.Two uses I find they're handy for are for checking the output of my old school generator, and for establishing an idea of how much power small appliances use.
@AndreasSpiess
@AndreasSpiess 3 года назад
I agree.
@DrHarryT
@DrHarryT 3 года назад
In the US we do have 3 phases but that is typically industrial although a residence can have it if it is available at the local distribution point, is needed and requested. Residential customer might have to pay for that in fracture to be installed up to a point and the voltage on each phase is 208 with respect to earth/neutral/common. The two phases you talk about is simply single phase coming down the local transmission lines [2 wires/14KV] to a transformer that puts out 240V with a center tap that is used as neutral to reference 120V off of each line. This way it is single phase 240V and when referenced to neutral 120V using only half of the phase but still 60Hz.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for your explanation. I think I showed the "split phase" concept in the video. I named the two wires "phases" because it has a shift of 180 degrees if measured against neural which can be relevant for measuring power (if I understood right)
@mlab3051
@mlab3051 3 года назад
Great content.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you!
@manu808
@manu808 3 года назад
What a nice topic!
@AndreasSpiess
@AndreasSpiess 3 года назад
Glad you think so!
@smoothjamie4046
@smoothjamie4046 3 года назад
Nice video, and a complicated topic. One thing not covered here though, don't always expect the Current waveform to be sinusoidal. Switch mode power supplies, CFL bulbs, LED lamps are all non-sinusoidal and measuring power factor, and true power is very difficult. These modules make this possible because they have delta-sigma converters and an 'algorhythm' to determine the true power. You can use the LTC1966 AC to true RMS converter to do the RMS calculation for Voltage and Current. Then regardless of the wave shape the power factor can be calculated (V_avg * I_avg) / (V_rms * I_rms). Have a look at those modules, they work really well with Arduino.
@AndreasSpiess
@AndreasSpiess 3 года назад
You are right. I think I showed also some other chips which do these RMS calculations. Fortunately they are no more rare...
@gacherumburu9958
@gacherumburu9958 3 года назад
Thanks for the info..👍
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome!
@xboxgamer9216
@xboxgamer9216 3 года назад
Ur vids are good
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you!
@pacovictoria5091
@pacovictoria5091 3 года назад
Excellent !
@AndreasSpiess
@AndreasSpiess 3 года назад
Many thanks!
@typxxilps
@typxxilps 3 года назад
I have a SonOff V2 and it measured for over a year on the same walll plug the more reliable energymaster was used for. After 1 year and 500 kWh consumption the difference is below 0,4% or less than 2 kWh. Did not change anything. Since then I purchased a different model that is housed in a plug in plug design switch for 16 A max. Results are 0,5% different so not that bad to get behind consumption of a dryer over a year to see that seasonal curve if that exists or that of a washing machine or even a night light outside and its movement sensor. It is a 32 Watt fluter and used 1 kWh per month so just 12 kWh a year. Who knows what a light does during the deep night so we measured to be sure that this is not a silent or hidden energy burner. If you check each single pluged in device and also the directly grid connected pieces like window jalousies you get a good feeling about your home energy consumption and efficiency especially if you make an inventory list of all devices and its standby watt and usage and an estimated use time per day ... If you then enjoy your holiday you get behind if your standby estimation and device inventory is right or not. That makes things easier to change habits or devices ... for example a smaller oven to heat up for just a fresh bread or piece of pizza instead of the usual oven which takes kWh to heat it up before starting to cook. When do you turn of a water cooker ... if it is already cooking or earlier and what is the difference? So we measured the water cattle for a quarter and guess what: it is used far often or with more water than assumed. It uses 5% of household energy consumption ... for tea mostly.
@AndreasSpiess
@AndreasSpiess 3 года назад
Very interesting info. So it seems that these chips are quite precise.
@romanhar4151
@romanhar4151 3 года назад
Thank you very much for the very informative video. What is the Type of the Battery powered oscilloscope, and where can it be bought?
@flipthecoin.
@flipthecoin. 3 года назад
P = V*A ill have to digest that on a monday morning :) Awesome video.
@AndreasSpiess
@AndreasSpiess 3 года назад
This video is for the layman and I thought, it is more understandable because I as current was not formally introduced before...
@chimeranzl9147
@chimeranzl9147 3 года назад
*boom* - that was the sound of my brain after getting to the end of your video
@AndreasSpiess
@AndreasSpiess 3 года назад
Is this good or bad?
@michaelyoutube5149
@michaelyoutube5149 3 года назад
Three phase power is used in the United States in places like almost all of New York City. The Two phase system allows for larger appliances to run on 240v compared to most other household appliances which run on 120v. This way most normal homes have 120v wiring with occasional outlets at 240v for high powered AC units, clothes dryers, and ovens. With a standard wall socket voltage of 120v, the three phase wiring would only provide 208v and not 240v. This is actually convenient in places like NY City where they don't want the consumer to be running high powered devices like electric ovens or electric clothes dryers which are, as far as the electrical grid is concerned, better powered by gas.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for the additional information!
@BitesandGo
@BitesandGo 2 года назад
How could I measure real time power on a 3 phase system. I saw I could use a 6 channel ESP energy meter. Because I wanna do it with ESPHome and homeassistant. But I dont find that board here in germany (Shipping is very expensive ) What would you recommend me ? Thank you !
@AndreasSpiess
@AndreasSpiess 2 года назад
I use the Shelly 3M for that purpose because I do not want to build a mains device myself. It is not cheap, but it works.
@matneu27
@matneu27 3 года назад
The yellow Metrrixx multimeter has the state of an old Nokia cellphone. Always reliable, tough and still working after dropping from the ladder. Only changing the mA fuse from time to time and a battery every year (if you did not forget to switch it off) 😉
@AndreasSpiess
@AndreasSpiess 3 года назад
True. Mine is already very old :-)
@rogerzink9090
@rogerzink9090 3 года назад
Hello Andreas, thank you for another brilliant video and all the work you do on this channel - to start with. Concerning the measuring device shown at 23:22 - I absolutely do not understand the wiring diagram on the website. Could you please explain where to connect L, N and the leads to the load to these four connectors on the device? Must be a mental hickup... Thank you!
@AndreasSpiess
@AndreasSpiess 3 года назад
#2 is not used. #1 is neutral IN, #3 is neutral out, and #4 is Line IN and OUT,
@boblewis5558
@boblewis5558 3 года назад
In the UK we normally ONLY are supplied with a SINGLE phase supply. The three phases of a local final transformer are shared as equally as possible between multiple houses. e.g. the first pair or first two pairs of houses will be fed from one phase, then the next group of houses, then the third group from the other two phases Some households MAY receive a three phase supply if it has been requested (and approved) from the distribution company. This may or may not be the same company who bills the premises (more commonly not). If a business is being run from home premises that requires three phase, quite often, depending on the area, the local council will be told and business rates applied to the premises! That is AFTER they may take you to court for unlawfully setting up a business without gaining planning approval first!! Smart meters in future will almost certainly start charging (and more costly charges!) for reactive power since it causes current loading problems for the localised grid area - the reactive (but REAL) current can exceed the local capacity of the grid cables, hence requiring more expensive infrastructure. This is "partly" due to the massive increase in non PFC compensated switch mode power supplies in homes driving SELV (low voltage) LEDS. It is also complicated by the increase in solar PV usage WITHOUT the relevant storage of the excess which instead goes straight back to the local grid.
@AndreasSpiess
@AndreasSpiess 3 года назад
We will see what happens. Here often the energy is not much more expensive than a fixed price for the network. And I assume pricing will change if people more and more start to produce their own (peak) energy...
@michaelyoutube5149
@michaelyoutube5149 3 года назад
There are 2 reasons to measure AC mains. 1) Because there is a need to know how much power is being used. 2) To know *IF* power is being used. This video had great information for case 1. But, what about case 2 ? True, if the answer is available for case 1, then case 2 is known. But, case 1 is often more complicated and more expensive. What about a simple cheap solution to case 2. But, you may ask, why be interested in only case 2? For example, a microcontroller can be used to mimic the IR input to a lot of IR controlled devices, like Air Conditioners, TVs, and a lot of others. Unfortunately such a device does not give good feedback to the microcontroller, so the microcontroller can't know if sending the "cycle power" command worked and actually turned the device ON or OFF. One way the microcontroller can know if the device is turned ON or OFF is *if* the device is using power. Exactly how much power is of much less concern, maybe only that the ON state is a lot more than the OFF (or standby) state. Here is a simple solution that i used which is protected from mains: In a video #321, "the guy with the Swiss accent" mentioned some current sensors usually built off of the Allegro ACS712 hall sensor (or something similar), which he rightly discouraged for use with mains - at least as-is. Only with luck will that chip work with mains. And relying on luck when working with mains is a quick way to posthumously earn a Darwin Award. Since that chip is only rated for a working voltage of 100v - sending 120v of mains AC through it might work, but it's not a good idea; And if your mains are 240V... that's almost 700v peak-to-peak and not to even be thought of. However, that little chip (or any similar chip) can be coerced into working with mains very safely - although it comes with a loss of accuracy. Again, if the real question is *IF* power is flowing, then accuracy is not very important. Here is what i did: I took a large eye-hook screw (4cm or 1.5inch diameter) that a magnet would stick to (stainless steel is not good) and sawed of the screw part, this left an iron loop with a small gap where the loop comes together. Then i wrapped some heavy gauge insulated power wire around the metal of this loop. Starting from near the gap i wrapped a spiral around the metal until it got to the other side of that small gap - i got 25 tight turns. Then i used hot glue to place one of those the hall-effect sensor chips into the center area of the gap... you want the gap just big enough to fit the chip without damaging it. Power from one line of the mains goes through the heavy duty wire in the loop. If the wire used is designed for use with mains power then this is as safe as any extension cord since the mains power is completely isolated (as long as the insulation does not melt). And now the microcontroller can read the hall sensor to see if there is current - and if is current flowing then power is being used. The reading is not exactly accurate - as particularly at very low current flow there is a fair amount of noise. But since the difference between stand-by and someone actually using the microwave oven is really huge, my microcontroller can easily tell if the microwave was turned on. On the software side, the program must be aware that this signal is AC and switches from positive to negative flow 50-60 times per second. I have mine probe as fast as possible for 200ms and average the absolute value of the results. But that is a whole other discussion.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you for sharing your design. It is an interesting concpt!
@martinkorinek5489
@martinkorinek5489 3 года назад
Great video, thanks. I would like to ask about the model of battery powerrd oscilloscope and where Can I buy he same?
@forteleaerieneromane
@forteleaerieneromane 3 года назад
It's an older model of this one I think: www.banggood.com/MINI-DS213-Digital-Storage-Oscilloscope-Portable-15MHz-Bandwidth-100MSa-or-s-Sampling-Rate-2-Analog-Channels+2-Digital-Channels-3-Inch-Screen-With-Logic-Trigger-p-1412378.html?rmmds=myorder&cur_warehouse=CZ
@amisadaipc691
@amisadaipc691 3 года назад
Nice video
@AndreasSpiess
@AndreasSpiess 3 года назад
Thanks!
@PhG1961
@PhG1961 3 года назад
Excellent ! Usefull, indeed. A nice wrap up and prep for evening classes starting in September. Well, that of course depends on the Corona issues, but let's think positive. Great entertainment too and as usual every time I see your oscilloscope up close, I start drooling...
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you! I had a good deal with the oscilloscope...
@PhG1961
@PhG1961 3 года назад
@@AndreasSpiess I'm looking out for a good deal too... ;-)
@EPYCMX
@EPYCMX 3 года назад
Great videos! This one and 321... Working on a project that will turn on and off a load of less than 5amps at 110v... Want to include power monitoring and I am using acs 712 for now... For this application what would be the advantage of a more complex solution as the ones you presented here?
@AndreasSpiess
@AndreasSpiess 3 года назад
You need to measure very fast to get the sine wave correctly. The specialized chips do that for you.
@FinneyDale
@FinneyDale Год назад
Great video as usuaI. I also share your concern about connecting to mains. It's great that we now have smart plugs with built in monitoring but I wonder about the accuracy. For constant loads directly connected to the panel, it might be easiest to read the nameplate or use a Current probe with your multimeter. Then monitor when the load is switched on. For variable loads (like my heat pump) I thought about the AD8210 Current sense amplifier and a current transformer and burden resistor. Current transformers are evidently an accepted practice. My solar panel installer put one in my panel.
@AndreasSpiess
@AndreasSpiess Год назад
I recently made a video about commercially available power meters...
@SteveWrightNZ
@SteveWrightNZ 3 года назад
How interesting to see the PF of that dimmer
@AndreasSpiess
@AndreasSpiess 3 года назад
I also was surprised. But I checked other sources and it seems to be "real".
@PFBruno3
@PFBruno3 3 года назад
Good stuff! Any recommendations on AC current meters which output a DC proportional voltage? This would allow the ucon to do other stuff and just read at any time.
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not know how to do the RMS calculations with analog means. But I did not search for long.
@vivekchauhan7468
@vivekchauhan7468 3 года назад
Hi Mr.andreas you show device at 9:10 . I want to detect AC mains (healthy voltage) does it do the job? I am building a device which can see whether mains voltage is ok or not. It is ok if voltage above 200v ac if it is below 200v it is not healthy phase. What do you recommend to use in this scenario?
@AndreasSpiess
@AndreasSpiess 3 года назад
If you want to have a signal for a precise voltage you have to use something like the ZMPT101B. The "mains checker" has no precise threshold. Maybe you can experiment with different resistors if you get it precise enough for your needs.
@vivekchauhan7468
@vivekchauhan7468 3 года назад
Thanks i will try some resistor divider. I hope it will works..
@FilipeNeto616
@FilipeNeto616 3 года назад
Do you, by chance, know if the Shelly EM can be "tasmotized"? Once again, thank you for sharing your knowledge
@AndreasSpiess
@AndreasSpiess 3 года назад
github.com/arendst/Tasmota/issues/8055
@yusufsuleymane6100
@yusufsuleymane6100 2 года назад
Sir for measure voltage and current on single phase transformers for test automation! Could you please provide me some hints thank you
@AndreasSpiess
@AndreasSpiess 2 года назад
Inputs and outputs of transformers have to be measured like all other AC systems.
@spyrostsimpinos2985
@spyrostsimpinos2985 2 года назад
Hello, thanku very much for the informations, very helpfull, i would like to ask how much is the phase angle error for current transformer?
@AndreasSpiess
@AndreasSpiess 2 года назад
I do not know.
@doylemaleche9937
@doylemaleche9937 3 года назад
I always look forward to your videos. so professional and informative! do you have a recommendation to measure mains power before the mains breaker? There are occasions when city power is down and i open the mains breaker to back-feed a generator power to the mains panel. i would like to monitor when city power is restored. My intention is to find a suitable sensor to monitor one or both 240 mains cable in the power panel. I understand the a cable clamp is used to measure current, however, since the mains breaker is open and voltage is present from city power, no (home) load is connected so i assume zero current. can a current clamp be used to sense when the city power is restored? I would like to measure any voltage activity on city power and have an Arduino trigger a relay to provide an audio indication, then silence the alert. what contactless/clamp sensor would you recommend? I release you of ALL liability when answering (thought i would add this for your protection). Keep up the OUTSTANDING work, Sir!
@AndreasSpiess
@AndreasSpiess 3 года назад
I have no knowledge in wiring such distribution box. You have to ask somebody who knows much more. You can use the clamps whenever you have current flowing through a wire.
@khrisravelo8196
@khrisravelo8196 3 года назад
14:45 About CT by clamp to Neutral wire, but if your wire (line) of my house is Live (Hot) 1/Live (Hot) 2 wire from DU (220V 50/60Hz). How can i use this CT?
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not know the situation in your country. So you have to ask an electrician.
@chiliphil64
@chiliphil64 3 года назад
Could you please assist in testing current of PCB tracks. I have a problem where I have a short on a pcb and need to track it down. I have been told there is a probe that will show the magnetic fields on pcb.
@AndreasSpiess
@AndreasSpiess 3 года назад
PCB tracks usually are tested with an ohm meter.
@boblewis5558
@boblewis5558 3 года назад
The other thing to note for left-handers: It's very difficult, but try to keep your left hand in your pocket rather than your right. Current will always flow through the easiest path to ground and that means (unless your heart is on the right - a VERY small minority are) then slightly more current will flow THROUGH your heart to ground from your arm down your left side. Current will still flow down your right side too but your heart is not in the way. If you receive a shock through your right arm, current will still flow through your heart, but mainly NOT and in any case will be much smaller, hence marginally safer.I learnt this over 50 years ago from an OLD TV engineer who used to have to work with 10kV to 35kV or more in CRT TVs. The bigger the screen, the higher the voltage (usually) and colour screens more than mono.
@AndreasSpiess
@AndreasSpiess 3 года назад
Here all honest people have the.heart at the „right“ side. So fortunately not too uncommon;-) But you are right, of course.
@boblewis5558
@boblewis5558 3 года назад
@@AndreasSpiess :)) LOL
@OldCurmudgeon3DP
@OldCurmudgeon3DP 3 года назад
5:00 was the scope saturating at the peaks or was there another component/source issue?
@AndreasSpiess
@AndreasSpiess 3 года назад
Hopefully not from the scope if you look at its price tag ;-) I assume it comes from the open transformer but did not do any investigations.
@romchiko
@romchiko 3 года назад
Thanks 2 U, guy with swiss accent!
@AndreasSpiess
@AndreasSpiess 3 года назад
You are welcome!
@GhostsOfSparta
@GhostsOfSparta 3 года назад
Learnt two new tricks. thanks! How can I measure 20kHz 70% dutyCycle pulsed DC current?
@AndreasSpiess
@AndreasSpiess 3 года назад
I assume with a small resistor and an oscilloscope. Maybe you can replace a resistor with a hall sensor shown in this video. But you have to check their max. frequency.
@vivekchauhan7468
@vivekchauhan7468 2 года назад
Hi andreas any everybody, 12:37 can you suggest how can i measure current with bare zmct103c. Any article or links please..
@AndreasSpiess
@AndreasSpiess 2 года назад
I would search for "zmct103c Arduino".
@vivekchauhan7468
@vivekchauhan7468 2 года назад
@@AndreasSpiess i did it but i cant find satisfied results.
@jamesgoacher1606
@jamesgoacher1606 3 года назад
I am a retired Electrical Engineer and I found this extremely interesting and there are a few places where I need to watch again because you said something which surprised me. Power Factor correction is extremely important in industry and the supplier will shout at you very loudly (as well as charging you) if it drops low. The domestic user pays for power factor indirectly because VAR does not do any work but you pay for it. During my Apprenticeship Elec Tech called this Wattless Power. I need to look at your Oscillospcope traces again mainly. At 75 yrs old I do not need to, just curious. Thank you.
@solidfuel0
@solidfuel0 3 года назад
What is VAR
@kiowablue2862
@kiowablue2862 3 года назад
@@solidfuel0 VAR = Volt Amperes Reactive
@kiowablue2862
@kiowablue2862 3 года назад
@James Goacher If by domestic user you mean residential - as opposed to commercial/industrial - then they may not be paying for reactive power. The Ferraris type meter and its electronic equivalent used in North America tally only real power.
@jamesgoacher1606
@jamesgoacher1606 3 года назад
@@kiowablue2862 I have never done domestic electricity apart from the necessary repairs of appliances. The last Electricity Meter I saw was the Eddy Current disc type. My present meter is in a cupbord outside and is a block of something with a couple of digital displays which I read remotely cos it supposed to be a Smart Meter, never understood that term. I am way out of date with equipment now because I have been retired for fifteen years from a fast moving field. I keep up to some extent but I do not need to design anything because I have no problems to solve (mostly). I am watching this RU-vid channel because of Mr Spiesss' (that is grammatically correct s appostrophe not apostrophe s) other output because I am inventing problems to solve with Arduino type things.
@AndreasSpiess
@AndreasSpiess 3 года назад
@James: To be still curious at 75 is a very good thing. Without that you probably would get old fast. I am 12 years younger but already see colleagues which stopped to be curious...
@Gastell0
@Gastell0 3 года назад
13:16 - Also as I recall if the voltage across both wires is not 0, you have a leak somewhere if you haven't noticed yet (usually it's sparkly and hot)
@AndreasSpiess
@AndreasSpiess 3 года назад
You are right. In this case our fuse would trip immediately. Because it monitors leak currents.
@SQ8MXT
@SQ8MXT 3 года назад
@9:20 What should be the distance between AC and DC? Arent optocouplers made to withstand 2kV'ish+ volatages? Or the typical pcb not suitable for such clearance?
@AndreasSpiess
@AndreasSpiess 3 года назад
I am not a specialist. But often they create a slot in the PCB to separate 240V from DC
@SQ8MXT
@SQ8MXT 3 года назад
@@AndreasSpiess Thanks for the reply. I guess a slot can never hurt and is overall a good practice. But if it was only about the distance then manufacturers would've surely used a bigger case for the optocoupler I guess.
@RalfVogler
@RalfVogler 3 года назад
Can you also access the data from the power monitor with the display (called P06S apparently)? I didn't find any information about a serial interface like the PZEM-004T has. Would be nice to have a display and broadcast the data.
@RalfVogler
@RalfVogler 3 года назад
This seems similar: hackaday.com/2016/07/11/put-a-reverse-engineered-power-meter-in-your-toolkit/ So not that easy to do safely. Also, some versions are not STM32-based.
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not like to work with mains. This is why I prefer wireless and ready-made devices...
@bartdepauw1156
@bartdepauw1156 2 года назад
Any one any idea how to measure L1 AC mains current AND current DIRECTION with a split clamp current transfo and arduino ? Like to know if I'm injecting or using from the net and how much (not taking into account the PF)
@AndreasSpiess
@AndreasSpiess 2 года назад
I am no specialist, but I think that the phase between voltage and current is different in both directions. I am not sure if the Arduino is fast enough for precise measurements because you have to measure a lot of points on the "sine" wave.
@ClosestNearUtopia
@ClosestNearUtopia 3 года назад
Thank you. I get really crazy of al thos people saying volts, amperage or wattage..those people probably also say they ran 200distance..
@AndreasSpiess
@AndreasSpiess 3 года назад
What is then the correct word for volts?
@bnproduction9298
@bnproduction9298 3 года назад
@Andreas Spiess I want my esp8266 to log power consumption of my air conditioner. Which module to use ? I am clueless. Please Help.
@AndreasSpiess
@AndreasSpiess 3 года назад
I share my knowledge in my videos and unfortunately do not have time for individual research :-(
@bnproduction9298
@bnproduction9298 3 года назад
@@AndreasSpiess please don't misinterpret. To your knowledge, is there any AC energy meter that can be programmed with arduino IDE?
@AndreasSpiess
@AndreasSpiess 3 года назад
Did you watch the video till the end? There I showed them.
@skd5432
@skd5432 2 года назад
Hi Andreas Is it possible to use PZEM044T for three phase(ac) power measuring hooked with an arduino? Am Working on a diy project for measuring 3phase current & voltage for a 240AC motor. Any other better ideas too is a welcome.
@AndreasSpiess
@AndreasSpiess 2 года назад
I use a Shelly 3M. It should be possible to do it with single Phase systems. But the voltage sensors have to be at the same phase as the current sensors
@skd5432
@skd5432 2 года назад
thanks​@@AndreasSpiess , let me try it.
@wp0049830
@wp0049830 3 года назад
Both AC/DC voltages and Currents can be measured safely (isolated) using chips like ACPL7900 or equivalent. They produce a differential voltage in proportion to input voltage or current.
@AndreasSpiess
@AndreasSpiess 3 года назад
True. I omitted them because of time. The video is already quite long...
@largepimping
@largepimping 3 года назад
Would love to see some testing of how accurate (or not) the Sonoff devices actually are.
@AndreasSpiess
@AndreasSpiess 3 года назад
If I remember right I did some testing in the old video. But this is not my specialty :-(
@JohnnieHougaardNielsen
@JohnnieHougaardNielsen 3 года назад
I'm getting good values with the Sonoff Pow R2 (after calibration), while the older Sonoff Pow should be less accurate.
@darianleduc
@darianleduc 3 года назад
Hilarious - the arm thing. Good presentation. Especially for lay person...
@AndreasSpiess
@AndreasSpiess 3 года назад
Thank you!
@chrispletcher6535
@chrispletcher6535 3 года назад
I, for one, love the Swiss accent. But i must know: are you saying "pretty youtubers", "greeting youtubers", or something else at the beginning? 😂 Great comprehensive AC video. I loved it.
@AndreasSpiess
@AndreasSpiess 3 года назад
It is "Grüezi RU-vidrs". This is Swiss German and means "hello RU-vidrs"
@chrispletcher6535
@chrispletcher6535 3 года назад
@@AndreasSpiess Thanks! My German is fairly sparse, i was only familiar with Gruß. I will sleep better now 🤭
@raeesmuqthar7991
@raeesmuqthar7991 3 года назад
This is something i was looking for. But how can i send that 21:21 data to a server to monitor the readings online
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not thing this device offers a machine readable interface. So you have to chose a different one.
@raeesmuqthar7991
@raeesmuqthar7991 3 года назад
@@AndreasSpiess do you have any suggestions of such a device / board
@BenMitro
@BenMitro 3 года назад
I'd like to know if there is a device that will tell me if I am feeding power to the grid or drawing power from the grid. This is to use excess solar power in water heating and battery charging. Is there a device that will tell me this? (Or do I have to build something to detect phase of current/voltage and then work it out from that assuming I don't have a motor running that will skew those results)
@kiowablue2862
@kiowablue2862 3 года назад
@Benny Indeed there is. Robin at mk2pvrouter.co.uk sells a kit that does exactly what you're asking about.
@BenMitro
@BenMitro 3 года назад
@@kiowablue2862 Thanks Bill. Excellent.
@rohithp8868
@rohithp8868 3 года назад
Is there any dc voltage and current measurement video for 16cell 100amp lifep04 cells. Want to make bms with esp32 is it possible.
@AndreasSpiess
@AndreasSpiess 3 года назад
I never covered high power applications on this channel.
@rohithp8868
@rohithp8868 3 года назад
@@AndreasSpiess ok can you do something similar with smaller 13s 48v. Hope thats fine its under 60v dc
@KnaufL
@KnaufL 3 года назад
Andreas, when will the second row seats start to get occupied?
@AndreasSpiess
@AndreasSpiess 3 года назад
60% of the views come from the second row (non-subscribers)...
@KnaufL
@KnaufL 3 года назад
@@AndreasSpiess I was thinking more in the direction of when will the first row overflow, but the information you provided really surprised me
@RalfVogler
@RalfVogler 3 года назад
I want to put a power monitor for the apartment in my fuse box and publish via mqtt. The FI seems to be only 25A. What's the best choice for accuracy+speed (want to try to detect different devices by their power profile like sense.com)? I have a PZEM-004T with a 100A CT but haven't put it in yet. How much more accurate would a 30CT coil be? Are the CT versions just safer or also less precise? What about a Sonoff Pow R2? It seems to be only 20A, but I guess that'd be enough. What happens if it went over 20A? Many questions :)
@svdhallen
@svdhallen 3 года назад
If you want to have a more accurate measurement with your PZEM-004T 100CT, and your max current is less than 50A (in most of the cases true for residential houses), then you can make 2 rounds with your source cable in the CT coil. I you do this, then you will use the PZEM in full scale (0-100A) but then you need to divide the result again by 2 off course to get the correct value.
@RalfVogler
@RalfVogler 3 года назад
​@@svdhallen Thanks. That would be easiest, but the wire is too thick and also too short (and hard to access - since I'm renting I don't want to rip the box out of the wall). The PZEM-004T claims 0.5% accuracy - does that mean 0.125% accuracy for a 25A CT? I'm confused by the use of percentage instead of some constant like for the resolution.
@DEADB33F
@DEADB33F 3 года назад
Here's an interesting question... How would you go about monitoring actual high voltages? ...ie electric fence voltages (~10kV, ~150mA, 1Hz ...but with short duration soliton pulse) I made a few Lora fence monitors and am using basic voltage dividers. Looking for a more robust solution measuring voltage using opto isolators though.
@TheUnofficialMaker
@TheUnofficialMaker 3 года назад
neon lamp and LDR?
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not know. Maybe with a parallel wire and a resistor? You should get some energy "transmitted". Or a simple radio receiver with an antenna. There you should easily hear the sound of the voltage spike. I would not connect resistors to the wire itself because it can reduce the maximum voltage considerably.
@K9-33
@K9-33 3 года назад
Get an inductive pick-up off an old automotive timing light. The pickup clamps around the spark plug wire and fires the strobe. A simple interface to the pick-up will detect the short duration high voltage pulse.
@AndrewGillard
@AndrewGillard 3 года назад
Power factor is a big problem for those current transformer devices that are sold to be clamped around the main tails to/from your electric meter in order to report the consumption of the whole house, even when the installation only has one phase delivered to it, as is the case for almost all UK houses¹. The ones I've used don't measure the mains voltage - *at all*, let alone in tandem with the current - and yet they report power rather than current, so presumably they're just assuming a mains voltage of 240V RMS and an arbitrary power factor?! I've used three such devices - the Energenie Mi|Home MIHO006, the Loop electricity monitor, and the Owl CM160 - and they all reported power consumption figures that were *significantly* wrong: in the region of 30% out! They each reported different figures, too, so it seems they're using different assumed values. If the difference was only 5% or even 10% I wouldn't care nearly as much, but 30% is unacceptable, IMO. The mains voltage here (as measured by a couple of TP-Link HS110 devices and imported to InfluxDB+Grafana) has ranged from 230V to 245V over the past month, so even assuming that to be constant introduces some amount of error... These days I'm using an ESP32 and a phototransistor to measure the duration between the flashes of the red LED ("1000 imp/kWh") on my electricity meter, very similar to the system described here: esphome.io/cookbook/power_meter.html (though I'm using ESPHome's "pulse width" sensor, because ESPHome's specific pulse counter implementation means that the more frequently you want it to report a value, the less accurate its readings get, to the point that, with a report every ~10 seconds, I had a *resolution* of around 400W!) This method is very accurate - it matches what's displayed by my utility-provided smart meter's in-home display - and since it uses the meter's own measurement hardware, it doesn't have to worry about the power factor - it would even automatically switch to reporting VA if my supplier decided to start charging me for apparent power, as Big Clive suggests they will! ;) ¹ Which will itself become more of a problem in the coming years: 60-100A at 240V [14-24kW] has been plenty for most households so far, even with a 8-12kW electric shower, but having e.g. an electric shower *and* an EV charger can create problems - both practical and regulatory - and 3-phase makes faster EV charging more practical as well (not that it's needed for most people)... But I don't think even houses being built in 2020 have 3-phase supplies, sadly... ² Energenie: energenie4u.co.uk/catalogue/product/MIHO006 | Loop: www.amazon.co.uk/dp/B00YNCJB3S | Owl: www.amazon.co.uk/dp/B004BDNR84
@AndreasSpiess
@AndreasSpiess 3 года назад
I do not know the power meters you used. But it could be that they cannot measure "true" RMS. It would also be interesting if it is only a calibration issue or a random error.
@PHamster
@PHamster 3 года назад
**ElectroBoom walks in** Owwww!
@AndreasSpiess
@AndreasSpiess 3 года назад
:-))
@boblewis5558
@boblewis5558 3 года назад
Ah yes! Mehdi the Maddie! LOL
@ahmadmuhaimin2852
@ahmadmuhaimin2852 Год назад
any option for measuring up to 200a current? can i use different transformer on pzem004t?
@AndreasSpiess
@AndreasSpiess Год назад
I think so. The pzem004t does not care about the winding ratio, just the voltage.
@ahmadmuhaimin2852
@ahmadmuhaimin2852 Год назад
have you ever used SCT-019 CT?
@AndreasSpiess
@AndreasSpiess Год назад
@@ahmadmuhaimin2852 no
@user-od3rl5mc
@user-od3rl5mc 3 года назад
I have 7 24v thermal actuator heads. If I had 24v transformer at 1amp, would that be sufficient to power 7 thermal actuators at once, or any combination of the 1-7 powered? Low energy input approx. 3W - 3.5W. • Breakaway current: 0.35A (24V) • 24V can be supplied from either an AC or DC source. • Coil resistance: 24V: 115 Ohms +/-29
@K2teknik.
@K2teknik. 3 года назад
Max power consumption looks like: 7*3.5W = 24.5W. Your transformer is 24W (24 volt * 1 Ampere). So you are a fraction below, but I would give it a try, or to be safe go one step up in transformer power.
@AndreasSpiess
@AndreasSpiess 3 года назад
You have to do your calculations. 24 volts is ok. But you also have to take into account the max. current all actuators will draw. Of course the transformer must be capable of sourcing also this current. 1 A is sufficient for max. 3 actuators (3x350mA).
@user-od3rl5mc
@user-od3rl5mc 3 года назад
@@AndreasSpiess Thank you! Yes I was confused by the documentation for their official wiring centre. It said that "With its 50 VA transformer, the 24V version allows up to 16 x 3W electrothermic heads to be controlled" which is 2 amperes, so with only half I calculated at 1 ampere for own setup. It does say later in the docs that their is 4A, transformer protection. Ref EWC-1: emmeti.co.uk/wp-content/uploads/EWC-Wiring-boxes-technical-Product-guide-April-2016-V2.pdf
@0124akash
@0124akash Год назад
Sir, am making homeautomation project based on ESP32 and relay module, project is properly worked. But i don't understand which protocol used. As per my knowledge HTTP protocol for WiFi networking. Am i right sir ? And second question is relay module connect to ESP32 through 10 wire so what is the protocol for this type communication ?
@AndreasSpiess
@AndreasSpiess Год назад
1. You can use different protocols over WiFi. I use MQTT. I would Google "Tasmota." 2. Each relay is usually controlled by an ESP32 pin (and a transistor). No protocol is needed other than on-off.
@0124akash
@0124akash Год назад
@@AndreasSpiess thankyou sir
@mfx1
@mfx1 3 года назад
Ironically most modern power supplies are switch mode and have to convert the incoming AC to DC first , DC transmission is more efficient but the technology to convert between voltages at DC wasn't available back in the Edisson/Tesla years so AC was the better choice but now DC would be better.
@AndreasSpiess
@AndreasSpiess 3 года назад
You are right. And today DC has a comeback for power distribution (e.g. underground cables). Silikon is cheap...
@typxxilps
@typxxilps 3 года назад
sounds like a war or battlefield: to avoid any casualties
@AndreasSpiess
@AndreasSpiess 3 года назад
Dead is dead, I think...
@user-xw9pf9ov6m
@user-xw9pf9ov6m 8 месяцев назад
Please make a video with ATM90E26 and esp32
@AndreasSpiess
@AndreasSpiess 7 месяцев назад
You get already a ready made board (google "IPEM-1 ESP32UE ATM90E32 IoT Power Energy Monitor Board"). And an ESPhome integration.
@ches74
@ches74 3 года назад
UK homes only have single phase as standard. Neighbours either side will have the other two phases.
@AndreasSpiess
@AndreasSpiess 3 года назад
Thanks for the information. Maybe a compromise between the US and Europe...
@ches74
@ches74 3 года назад
@@AndreasSpiess UK has 100Amp main fuse so probably just different ways to share the power out. US definitely needs more than one phase for running cookers and heating, 120V would need a lot of copper for the current. UK is Europe, just not mainland ;)
@matteopascoli
@matteopascoli 3 года назад
So two neighbours can conspire to connect their phases across the garden and milk 400V ?
@ches74
@ches74 3 года назад
@@matteopascoli It's being metered in each house. Anyone can get the phase installed in their house if they want but unless your running heavy machinery it's not really required.
@ches74
@ches74 3 года назад
@@Sal--- Wrong, Brexit took the UK out of the EU. The UK remains as firmly on the European continent as Switzerland does.
Далее
The Most Confusing Part of the Power Grid
22:07
Просмотров 1,3 млн
Current Transformers (CT)
14:31
Просмотров 473 тыс.
Measure DC Voltage and Current with Arduino
37:29
Просмотров 196 тыс.
Measuring AC Current with Arduino
19:29
Просмотров 72 тыс.
Сложная распаковка iPhone 15
1:01
Просмотров 15 тыс.
ОБСЛУЖИЛИ САМЫЙ ГРЯЗНЫЙ ПК
1:00