#63 - Why use a LoZ Meter? 

The Tech Circuit
Подписаться 2,3 тыс.
Просмотров 2,5 тыс.
50% 1

Using a LoZ meter, such as the Klein CL800, you can easily detect ghost voltages and compromised voltage sources. What are ghost voltages and compromised voltage sources? Link to multimeter: amzn.to/45mtBJs . To donate to The Tech Circuit, click here: techcircuit.org/donate
Link to LoZ article: techcircuit.org/how-lowz-work...
#kleincl800, #loz, #lozmeter, #whatisloz, #appliancerepair, #hvacrepair, #electrician
To help support the Tech Circuit, please go to www.TechCircuit.org/support
We are a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for us to earn fees by linking to Amazon.com and affiliated sites.

Опубликовано:

 

26 авг 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 6   
@turdsferbreakfast
@turdsferbreakfast 11 месяцев назад
Great content! Clear and consise.
@alejandrogalarza3147
@alejandrogalarza3147 10 месяцев назад
It would be interesting to see this function to measure phase to ground in an isolation transformer
@PigsOnBook
@PigsOnBook 2 месяца назад
thanks, the sentence is confusing, "sometimes....even have leakage current through a high resistance..." Length of wire make more resistance to electrical flow, right? How can something that "Resists" electricity flow "higher" than other things, allow leakage? Leakage occurs when something has Low resistance? V=ir. Should the sentence say, "sometimes...even have leakage current through a something that has very low resistance..."?
@PitchnYaw
@PitchnYaw 4 месяца назад
Another use is testing earth leakage breaker function by measuring voltage across live and earth. A LoZ meter should trip the earth leakage breaker.
@TheTechCircuit
@TheTechCircuit 4 месяца назад
True that it will trip a GFCI, but cannot be said to test it. On a 120v circuit, the 3200k ohm LoZ mode will cause 38mA to pass from line to ground - which is way above the trip threshold of the GFCI. Properly testing a GFCI would be ensuring it trips at the threshold current which is around 6mA.
@PitchnYaw
@PitchnYaw 4 месяца назад
@@TheTechCircuit agree. It’s useful only to see if there is some type of protection there, not to fully test that it is operating to spec.
Далее
Ghost Voltages - Interesting and Confounding!
14:14
Просмотров 3,7 тыс.
What is Ghost Voltage?
19:45
Просмотров 30 тыс.
How to use a multimeter like a pro, the ultimate guide
12:55
DIY SOLAR ESSENTIAL TOOL-Klein CL800 meter
8:58
Просмотров 6 тыс.
#84 - Open Neutral Testing in 120v Circuits
8:57
Просмотров 2,9 тыс.
LED Resistor Calculation
11:23
Просмотров 158 тыс.