Had a 3 story atrium where the AHJ called into question the location of our beam detectors in each atrium. To prove that the location would work we conducted a live smoke test using smoke candles and heat lamps (since the smoke is "cold" it typically rises slower, the lamps work to counter act that and simulate the heat of a real fire as close as we can).
The beam detector is located in the hole near the top of the atrium and is shooting across the center gap, look for the dark circle on the wall near the highest point of the building.
The beam detector activated in around 1 minute and 40 seconds. We had the notification devices disabled since we had already done that part of the testing on a previous visit.

Наука

Опубликовано:

 

4 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 3   
@deanrushin2006
@deanrushin2006 2 года назад
Interesting. What is the brand and model of beam smoke detector used here? Where is this building located?
@auliarahma4736
@auliarahma4736 Год назад
hey, can you defined the height of the building in this experiment?
@joaopnz
@joaopnz 3 года назад
Vesda, 10 seconds...
Далее
Smoke Detector Spacing Requirements Part 1
21:31
Просмотров 20 тыс.
Lighting metal fires (and putting them out??)
13:30
Просмотров 709 тыс.
10 Amazing Fire Tricks!
6:25
Просмотров 22 млн
New House Life Safety Inspection - Smoke Alarms
5:30
Beam -- Chapter 3: Beam Detector Alignment
5:08
Просмотров 38 тыс.
How Do Smoke Detectors Work? | Spec. Sense
1:19
Просмотров 279 тыс.
Fire vs Smoke Detector
1:34
Просмотров 11 тыс.
Samsung laughing on iPhone #techbyakram
0:12
Просмотров 6 млн