Derek in part 2 of the installation and commissioning of the Glow-Worm micracom sees if the boiler can redeem itself and be easier to commission than install. • WORST GAS BOILER TO IN... Part one installation
When performing fga, Glowworm would do better to repeat the combustion tables in the maintenance section in the commissioning section. The O2 is an important indicator when analysing as are minimum rate figures. Sorry you didn't do more on system water quality analysis, bearing in mind MI'S and BS 7593.
I would be doing as per the MI's Why would you not? says ring then you have to ring least you can log you have rang them and put what they say in the notes on commissioning else its not been commissioned to MI's and you would have wrote your readings in the benchmark which are incorrect. If Glowworm say thats fine you have done what they have asked and note that down. With front case fitted = 9.2 ±1 %I f the value is outside of the permitted range: ▶ Measure the CO₂ content at the flue gas analysis point again and log the measured value. ▶ If the value is still outside of the permissible range, do not start up the product and, instead, report this to customer service.