Hi i should do the same at work but i have a question Where do you set that the reference speed is gonna be by the digital terminals with the preset speed and not analogic terminal ?
Thank you for reaching out. Turning on one or more of the digital inputs assigned as a preset speed automatically tells the drive to ignore the analog input and to run at the selected preset speed. There is no programming or adjustment needed, other than to wire the controls so the preset speed input is turned on. Hope this helps.
Thank you for your message. We apologize for any inconvenience caused. Our customer care team would be happy to provide assistance. Please reach out to a customer care member in your location here: www.se.com/ww/en/work/support/country-selector/contact-us.jsp
Bonjour merci de me faire un retour J'ai un variateur similaire a celui sur la video ci dessus. J'ai changer le moteur 45 kw par un moteur 22 kw j'ai reconfigurer le variateur pour le nouveau moteur j'ai mis en marche le moteur sans remarque après un certain temps j'ai mis en arrêt le moteur ensuite j'ai activer dans la configuration filtre activer j'ai remis le moteur en marche le moteur n'arrive pas à ce démarrer j'ai désactivé la fonction filtre mais rien à changer le moteur n'arrive pas a ce démarrer apres le diagnostic j'ai trouvé que la tension au borne du moteur est 75 v au lieu de 400 v Je veux juste savoir est ce que le variateur maintenant est en panne ou juste une paramétrage non compatible merci de me faire un retour