Contactors and relays are used in almost all heating, cooling, and refrigeration equipment for the operation of loads in the system.
They are both similar in operation since both contain a coil that opens or closes the contacts.
A Contactor is larger and capable of carrying more amperage than a relay.
When testing same procedures can be used to check both Contactors and relays.
There are three areas of problems encountered with Contactors and relays the contacts, the coil, and the mechanical linkage.
Any one of these three areas can cause a Contactor or relay to malfunction.
A Contactor controls high voltage with a low voltage input.
For example, a thermostat uses low voltage, usually 24 VAC, to control the high voltage 240 Volts input into many HVAC systems such as an air conditioner.
The thermostat 24 VAC will enable an electromagnetic coil that pulls down on the contacts and allows 240 volts AC to flow into the system.
A relay is very similar to a Contactor and operates the same, with an electromagnetic coil.
The main difference is the voltages used with relays are usually much smaller while Contactors manage higher voltages such as 240 volts AC.
The Contacts must make a good direct connection when the coil is energized for the device to function properly.
One of the problems with Contactors and relays is the Contacts inability to make a good connection.
They can be burned, pitted, or stuck together. A set of contacts that are burned or pitted can cause a voltage drop across the contacts.
There are several methods of checking a set to determine they are burned or pitted enough to warrant changing the device.
The easiest method is to make a visual inspection.
Most Contactors have a movable center that allows easy visual inspection. Most relays are sealed, and visual inspection is impossible.
A resistance check can also determine the condition of a set of contacts. The device must be energized to check normally open contacts. Normally closed contacts must be checked with the device de-energized.
If the resistance is greater than 2 or 3 ohms, the contacts should be considered faulty.
A voltage check can determine the condition of a set of contacts. When a voltage check is made, the Contactor or relay should be energized.
To make a voltage check on a set of contacts, take a voltage reading from one side of the contacts to the other. The reading will show how much voltage is being lost.
The load must be energized when a voltage test is being performed. If the voltage loss across the contacts exceeds 5% of the line voltage, the contacts are faulty, and the Contactor or relay should be replaced. The contact alignment can also cause a contactor or relay to malfunction.
Contacts should close directly in line with each other and sit directly in line with good firm contact. The major cause of contact misalignment is a faulty mechanical linkage. If the contacts are out of alignment, the Contactor or relay must be rebuilt and any faulty components replaced.
The coil of a relay or Contactor is used to close the contacts by creating a magnetic field that will pull the plunger into the magnetic field.
If the coil of a relay or Contactor is faulty, the device will not close the contacts.
A coil of a contactor or relay should be checked for opens, shorts, or measurable resistance. If a coil is shorted, the resistance will be 0 ohms, and the coil should be replaced. An open coil will give a resistance reading of infinity, and this coil should also be replaced.
A measurable resistance indicates that the coil is good. Almost any measurable resistance indicates a good coil because of the variance in coil voltages. A shorted contactor coil will cause a transformer to burn out, and the service mechanic should take caution not to allow this to happen.
The mechanical linkage of a Contactor or relay can cause malfunctions in many different forms, such as sticking contacts, contacts that will not close due to excess friction, Contacts that do not make good direct contact, and misalignment of contacts. The best method for detecting a faulty mechanical linkage is by visual inspection.
On Contactors and some relays, this can be done by removing the device and merely looking it over. However, most re-lays are sealed, and inspection is impossible. A sealed relay must be checked by determining if the contacts open and close when the relay coil is energized or de-energized.
A mechanical linkage problem can cause a contactor or relay to stick open or closed or cause misalignment of the contact. If a Contactor or serviceable relay has a mechanical linkage problem, it should be replaced.
Jabirwaqas.com

Наука

Опубликовано:

 

31 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 79   
@shkarbhatiya5895
@shkarbhatiya5895 3 года назад
بھت زبردست سمجھایا آپ نے،خدا آپ کو خوش رکھے اور تندرستی عطا فرمائے
@boozoogamerzya1363
@boozoogamerzya1363 2 года назад
ماشالہ جی 100
@syedwaseeulla2179
@syedwaseeulla2179 2 года назад
Mashallha nice👍👏👏👏😊
@maazawan4223
@maazawan4223 2 года назад
Good job
@sumonislam710
@sumonislam710 3 года назад
Nice Video Sar👍👍🇧🇩
@narenderkumar-oj4lk
@narenderkumar-oj4lk 3 года назад
Very nice thanks sir
@fitnessaddict473
@fitnessaddict473 2 года назад
Your Express good ,
@syedfarhanaliqadri2027
@syedfarhanaliqadri2027 2 года назад
Wa alaikumussalam sir
@hamadahamad8456
@hamadahamad8456 Год назад
Mashaallah aap bahut achchi video banate h
@pradeeppal8509
@pradeeppal8509 3 года назад
uncle g ap video achi banate ho
@Jabirwaqas
@Jabirwaqas 3 года назад
Pradeep, bht bht shukrya ap ka....
@riyazansari2058
@riyazansari2058 3 года назад
Nic sar
@samiullahscotish8111
@samiullahscotish8111 3 года назад
Asslam o alaikum Sir really you are brilliant. Sir i am not a electrician but mujhy buhat شوق hai is tarha k knowledge ka . ماشاءاللہ buhat khushi hwi app ki diffrent videos daikhian ajj mai ne .
@Jabirwaqas
@Jabirwaqas 3 года назад
Sami ullah, bht bht shukrya. Itna pyara comment krnay k lya...
@trrz8628
@trrz8628 21 день назад
Sir ap great ho ❤
@sudeshputran69
@sudeshputran69 3 года назад
Super
@mohdnafees2167
@mohdnafees2167 3 года назад
Masha Allah Allah Aapko salahmat rakhe
@samhaazratechnicalsupport
@samhaazratechnicalsupport Год назад
Very niece bhai jaan ❤
@shallushaikh1833
@shallushaikh1833 3 года назад
Walekumsalam
@mudasirabbasiabbasi1067
@mudasirabbasiabbasi1067 3 года назад
Sar ji thnk you
@user-gq4pz7gd7o
@user-gq4pz7gd7o 3 года назад
Thanks sir
@arifnaveedsipra4234
@arifnaveedsipra4234 3 года назад
Jazak Allah khaira
@pradipray8710
@pradipray8710 3 года назад
Sir please single n double poll contractor ka wearing ka video banaiye bohut meher bani hoga
@Jabirwaqas
@Jabirwaqas 3 года назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-rswJ5M57q6s.html
@tacnicallknowlage2634
@tacnicallknowlage2634 4 года назад
Good knowledge
@avtarworld1033
@avtarworld1033 4 года назад
Good informative video sir ji
@Jabirwaqas
@Jabirwaqas 4 года назад
Thankyou krishan mohan
@nexttimetry1431
@nexttimetry1431 3 года назад
Mashaallah keep going
@Jabirwaqas
@Jabirwaqas 3 года назад
thankyou...
@shahnawazwarsi8635
@shahnawazwarsi8635 3 года назад
Masha allah
@khalidjaved8193
@khalidjaved8193 4 года назад
Thank you sir
@deepakubade3795
@deepakubade3795 3 года назад
Hi sir plz contactor wiring video banaye. Single pole and double pole
@Jabirwaqas
@Jabirwaqas 3 года назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-rswJ5M57q6s.html
@Jawadparesis
@Jawadparesis 4 года назад
Thanks
@mwaseem932
@mwaseem932 4 года назад
Sir plz make a video on lock out relay and SPPR with diagram and practical
@climaxstory8082
@climaxstory8082 2 года назад
Assalamu alaiku R22 wala ac me us ac ka Gas R22 k bajaye R410 ya R32 Gas filling karsakte hen ?
@Jabirwaqas
@Jabirwaqas 2 года назад
Safiullah.. Nhe kr sktay....
@UmaShankar-xl3bv
@UmaShankar-xl3bv 3 года назад
मैग्नेटिक कॉन्टैक्टर का वायरिंग कैसे किया जाता है सर इसका प्लीज वीडियो बनाइए
@deepakpanwer
@deepakpanwer Год назад
Bhai ji ac ki wiring be bata dejye
@sumailmehandi146
@sumailmehandi146 4 года назад
Asalam alykum sir compressor ground hone ke kya kya wajahat hoti h plz sir answer
@samhaazratechnicalsupport
@samhaazratechnicalsupport Год назад
Bhai jaan pichhein ka vusal aap ne kaise used kiya please bayein .kaun sa app hai❤
@shariquejaved2934
@shariquejaved2934 11 месяцев назад
Jabir bhai aap aur tafseel se bataye ki Contactor aur relay hota kya hai aur oska kaha kaha usage hai
@Jabirwaqas
@Jabirwaqas 11 месяцев назад
Inshaallah... ❣️
@sadabakram7368
@sadabakram7368 4 года назад
Sir tisra sabse bada wala contacter kahan kaha kis Kam ke liye use Kiya jata Hai please message me
@tacnicallknowlage2634
@tacnicallknowlage2634 4 года назад
Hello sir Ek inverter ac hai usme indoor nahi chal raha hai lite bilk kar raha hai Outdoor unit chal raha hai only kiya problem ho Sakti hai please batai
@Jabirwaqas
@Jabirwaqas 4 года назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-AdyweHTV5wY.html is link man video ha, jis s maloom ho ga k motor m problem ha ya pcb man.
@kamalnasim2935
@kamalnasim2935 4 года назад
Hi sir
@Jabirwaqas
@Jabirwaqas 4 года назад
Hello. Kamal nasim, How r you?
@syedsuleman6665
@syedsuleman6665 3 года назад
Sir jb ac me gas charg krty hain to us k upr laikha hota hay t1 7.3amp or t3 9.3 hoty hain to gas k kitny amp krny cha ay
@Jabirwaqas
@Jabirwaqas 3 года назад
Suleman freon hmasha wzn kr k dalny chaheay......ac k oper likha hota ha k kitny dalny ha.
@samhaazratechnicalsupport
@samhaazratechnicalsupport Год назад
Bhai jaan ye jo ac ke image lagatein hai kaha se download kartein hai . Copyright to mahi aata hai please batayein ❤
@salmangujjarpk2193
@salmangujjarpk2193 4 года назад
Sir 24v contacter ke connection pr 1 video bnayn
@sumailmehandi7774
@sumailmehandi7774 3 года назад
Assalam alykum sir Mera ye sawal h LP or HP kitne kitne volts pe kaam karta h example ke liye 24 volt 110 volt 220 volt kya LP or HP ye tino voltage pe kaam karte h
@Jabirwaqas
@Jabirwaqas 3 года назад
Sumail,,, lp, hp ksi bi volt k ho sktay han, ap k unit ki specification p depend krta ha..... Ap ko lp, hp ka kam krnay ka treeka pta hona chaheay,,,
@sumailmehandi7774
@sumailmehandi7774 3 года назад
Assalam alykum sir jaise LP or HP 220 volts ki h to kya ham uspe 24 volts se supply de skte h
@sumailmehandi7774
@sumailmehandi7774 3 года назад
Ab jaise bht sare unit ko Maine dekha uska wiring 24 volts ki h but usme jo LP or HP lga h wo 220 volts ki h fir bhi unit working Kar rha h
@KhalidKhan-le4ud
@KhalidKhan-le4ud 2 года назад
Assalamualikum Sir aap Kaha se ho
@Jabirwaqas
@Jabirwaqas 2 года назад
Khalid, man pakistan say hon. Lakin saudia man hota hon.
@imransaleem9137
@imransaleem9137 3 года назад
Kia Howa ap Kahn gain ho gaye Hain kia masla Hy
@Jabirwaqas
@Jabirwaqas 3 года назад
Imran. Aj ak video upload ke ha, ab jldi jldi video bnaya kron ga, inshaallah.
@imransaleem9137
@imransaleem9137 3 года назад
@@Jabirwaqas jee ap ka bht shukria may ap ki video ko bht pasend krta hon ap say dafa baat bhi hoi Hy ! Raat kay waqt humray "Ac" say Pani drain say tapap raha tha or ap nay us Raat humra problem Haal kia tha AJ do saal ho gayen Hain lakin drain say Pani nahi tta hay is ka Liya ap ka bht shukria good bless you
@guddukryadav7507
@guddukryadav7507 4 года назад
Aslam lekum sir mere paas ek Question hai jo bahut din se parsan kiya hai hai. 1. Ek old contactor hai jispe koyi data nahi likha hai to usko kaise find kare ki ye contactor kitani volt ki hai bina power diye huwe plazzz jarur bataye aapke video dekh kar bahut hi kuchh sikhane ko milta hai plazzz tell me answer I am waiting sir
@Jabirwaqas
@Jabirwaqas 4 года назад
guddu kryadav bht bht zabardast question ha. kya ap ka question ya ha k contactor ki coil 220 ya 110 ha... ya ya kasay maloom kya jay k contactor ki coil dc ya ac ha?
@guddukryadav7507
@guddukryadav7507 4 года назад
Ji sir Kaiser malum kare ki ye 1.220v ac 2.24v ac 3.110v ac 4.ac or dc coil hai
@Jabirwaqas
@Jabirwaqas 4 года назад
ac ar dc coil ka to dakh k bi andaza ho jata ha. dc coil k coil k ring zada honay ki wjha say us ki resistance zada hoty ha , ac coil say....... lakin 110, 220,,, 24v ... ko kasay dafferent kran gay ak dosray say. maray lya b nya topic ha, soon i will try to answere in detail,.
@guddukryadav7507
@guddukryadav7507 4 года назад
Ok sir thank you.. I am waiting
@akhtarali2145
@akhtarali2145 4 года назад
Sir send me your whatsaap number please
@asgharhameed4233
@asgharhameed4233 4 года назад
No body understand without dayagram only speech
@shallushaikh1833
@shallushaikh1833 3 года назад
Allha ap ko Lambi umar de mai ap ko dil se salam karta hu ap hame apna whataapp number de
@Jabirwaqas
@Jabirwaqas 3 года назад
Shallu bht bht shukrya ap ka...
@abbaskanju494
@abbaskanju494 2 года назад
Sir apna numbr send kr den plz
@adilmamtaz7466
@adilmamtaz7466 4 года назад
Nmbr chayea
@adilmamtaz7466
@adilmamtaz7466 3 года назад
جابر صاحب واٹس اپ پر آپ سے معلومات کیلئے میسج بھیجتے ہیں آپ جواب نہیں دیتے
@TechnicianGroups
@TechnicianGroups 3 года назад
Not good speech 😜 theory and practical need more esperance
@aftabahmed4142
@aftabahmed4142 2 года назад
YOU ARE WASTING OF TIME
@Jabirwaqas
@Jabirwaqas 2 года назад
Wasting of time theek nhe.... Waste of time hota ha brother......
@malikshahrukhmalikmuhammad2175
Super
Далее
I Built a EXTREME School Bus!
21:37
Просмотров 8 млн
БИМ БАМ БУМ💥
00:14
Просмотров 1,7 млн
IQ Level: 10000
00:10
Просмотров 4,4 млн
Rule Of Law No Longer Exists In Pakistan | Eon Clips
18:41
АЙФОН Г0ВН0
0:54
Просмотров 1,5 млн
Лучший браузер!
0:27
Просмотров 536 тыс.