How to remove and replace an air conditioning compressor on a Carrier, central ac system. High-rise apartment maintenance.
Vacuum Hoses - amzn.to/3ytDi97
Vacuum Pump - amzn.to/3vgYay7
Evacuation Manifold - amzn.to/34oo2fX
SSX34 Fieldpiece Subcool/Superheat Meter - amzn.to/3xCQRSM
Vacuum rated Valve Core Removal Tools - amzn.to/3yAHSCg
Compressor Tote - hdsupplysolutions.com/p/diver...
00:00 - refrigerant recovery
01:15 - removing compressor
04:16 - installing new compressor
05:55 - brazing in new compressor
07:16 - leak test with nitrogen
08:31 - evacuation set-up
10:01 - evacuating system
10:46 - breaking vacuum
11:49 - installing valve cores
13:03 - charging ac system by subcooling
*As an amazon affiliate I may receive commissions from qualifying purchases. *

Опубликовано:

 

13 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 38   
@jrh86
@jrh86 9 месяцев назад
Great job and insightfull and a big thank you from al of the respectfull viewer's 💯👍👍👍
@Khn83
@Khn83 Год назад
Great video!! Not sure if you do this often on compressor change outs but sometimes it’s a good idea to flush out the system to avoid cross contamination from a burnout. Love the content you are putting out… keep up the good work👍👍
@ApartmentMaintenancePro
@ApartmentMaintenancePro Год назад
Yes thanks! I always requests properties to have acid away on hand as well as acid test kits but that doesn't always happen - I just do the best I can with what I got :)
@KenMagee
@KenMagee 3 года назад
Great video my guy! Everything was done the same way I do it personally.
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
Thanks Ken!
@techfive7202
@techfive7202 3 года назад
Bro! Compressor tote!? Say what? Where has this been all my life
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
They are a game changer for sure 👍
@techfive7202
@techfive7202 3 года назад
@@ApartmentMaintenancePro I just got mine in the mail. Thanks. It dubs as a tank holder
@LexVance
@LexVance 3 года назад
Great video! Go Noles! I live in Tallahassee. 😆
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
Right on bro ! Go Noles!!
@slowupspeeddown1242
@slowupspeeddown1242 3 года назад
Great stuff! Keep it up man 🤙🏽
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
Thanks Jared :)
@joeyysossa4144
@joeyysossa4144 2 года назад
How Important is it to use the valve stem removing tools???...I never used one of those I screw the blue line from the manifolds straight to the low side of the minisplits when I perform a vacume.
@ApartmentMaintenancePro
@ApartmentMaintenancePro 2 года назад
Lots of debate about this - cuts down on my evacuation time
@666miguel99
@666miguel99 Год назад
Thanks for the video. Question, do you know if there's a valve core removal tool for the fatter valve stems on commercial HVAC?
@joeyysossa4144
@joeyysossa4144 2 года назад
Hi great video I just suscribed to yr channel my question is whats the name or the shreader valvule removal tool??? I need to buy 2 of them...I like their function. Thnks n be safe.
@ApartmentMaintenancePro
@ApartmentMaintenancePro 2 года назад
Valve core removal tools - links in the video description as well 👍
@JP-zz5rm
@JP-zz5rm 3 года назад
Nice! Did a heat pump compressor changeout today as well. What’s the link for that shut off valve that you used on the vacuum pump to not let any air into the system?
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
Nice man! It's a Evacuation Manifold - amzn.to/34oo2fX :)
@JP-zz5rm
@JP-zz5rm 3 года назад
@@ApartmentMaintenancePro thanks brotha! Will definitely be checking out your other videos!
@RoaringRecip
@RoaringRecip 2 года назад
What year was this unit installed?
@ApartmentMaintenancePro
@ApartmentMaintenancePro 2 года назад
Not sure. 2021?
@zc3658
@zc3658 2 года назад
So, Copeland specifically says to charge liquid into the high side only for their scroll compressors. I guess it really doesn't matter?
@ApartmentMaintenancePro
@ApartmentMaintenancePro 2 года назад
Reference link??
@bretjohnson9981
@bretjohnson9981 3 года назад
What superheat/subcool meter are you using and where did you get it?
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
SSX34 I bought it about 10 years ago at a supply shop. Just looked it up on amazon doesn't seem anythings changed on it amzn.to/3xCQRSM
@techfive7202
@techfive7202 3 года назад
What size brazing tip are you using
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
It’s bigger than what I usually use but all I had one me. I don’t know the size off the top of my head
@abdullah_q8171
@abdullah_q8171 3 года назад
Whats Pressure for gas 410r ?
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
go by superheat for pistons and subcool for txv's :)
@younasafzal7307
@younasafzal7307 2 года назад
Why he didn't change the expansion valve???even if we change the compressor we should must change it... Can anyone explain
@rafaeldiegonavarro
@rafaeldiegonavarro 3 года назад
i bet the compressor was just fine you just needed to change the electrical connection . could of saved the client a ton of money
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
Your probably right I’ve only been doing this crap for about 15 years. I obviously have no clue
@rafaeldiegonavarro
@rafaeldiegonavarro 3 года назад
@@ApartmentMaintenancePro lol 15 years doing it wrong your right
@ApartmentMaintenancePro
@ApartmentMaintenancePro 3 года назад
@@rafaeldiegonavarro Did you steal that comment from tik tok or come up with it all by yourself?
@artlovemusicpeace
@artlovemusicpeace Год назад
@@ApartmentMaintenancePro you’re just mad because you know he’s right 🤣 shady @ss hvac guys are at it again!
@emailfilters
@emailfilters Год назад
1:48 - Wow. Could have inspected that first and saved time and materials. Maybe the compressor is still OK. If there are no opens, and no shorts to ground, a loose peckerhead connection was the reason the compressor wouldn't start. Replace the wring harness clean the terminals and put back into service.
@ApartmentMaintenancePro
@ApartmentMaintenancePro Год назад
Not on this one. The compressor would run, but would not pump, meaning the pressures were equalized when running, meaning the valves were shot.
Далее
Rate my Scroll Compressor Install (1-10)
9:25
Просмотров 4,3 тыс.
TXV Valve Installation
10:24
Просмотров 48 тыс.
COPELAND SCROLL COMPRESSOR TEAR DOWN
19:38
Просмотров 36 тыс.
Copeland Scroll Compressor Teardown
7:03
Просмотров 63 тыс.
HVAC 074 B Scroll compressor cut open
8:26
Просмотров 27 тыс.
Locked Compressors
20:13
Просмотров 111 тыс.
Repairing a Refrigerant Leak on a Condenser Coil
6:20
How to Leak Test an AC With Nitrogen Pressure
8:00
Просмотров 224 тыс.