@Total cooling Solution hello there. Mere paas Daikin 1.5 ton inverter AC h. Agar me temp 18 ya 19 me rakhta hu then only compressor on hota h and uske upar temperature krne se outdoor compressor trip ho jata h . Mene technician se kaam karvaya usne indoor and outdoor both pcb ko repair kiya , kich. Sensors ko v repair kiya plus kuch capacitor v change Kiya outdoor pcb me. Also indoor pcb me display sensor me v kuch repair kiya . Even pump down service v hua also vaccum v kiya but no luck. Any suggestions?
Sir, I have purchased Daikin 1.5 ton 5 star inverter split AC which is within warranty. After 10 days of installation, the outdoor unit including compressor and fan had gone off and on and speed of the outdoor fan was so slow resulted low temperature cooling and no water droplets. Besides, remote of the AC had also turned faulty as it's LED i.e. screen of the remote had gone filled with all buttons icons and the remote was not functioning. The matter was taken up with concerned through customer care, who changed the outdoor PCB and remote. On changing PCB, the fan speed increased but the outdoor unit again went off and on frequently and after delay also and remote had also developed same issues. The remote was changed again and at present four remotes have been replaced but developing sams issue. Now the outdoor fan has also been changed which resulted slow speed and outdoor unit again goes frequently off and on sometime after long delay and sometime frequently. Especially when I set the room temperature on 25 degree especially at 27 degrrr room temperature. The representatives of the company are saying the machine is working properly but I am not satisfied with them. What is the fault in the machine as per your opinion and what should I do further as the AC is within warranty period. With regards. Ashok from Distt. Kathua ward No. 10 mob. No. 6005877787 Jammu and Kashmir.
@@totalcoolingsolution Sir awaiting your valuable opinion. Kindly also check whether combination of both the Indoor and outdoor units is correct as Indoor unit showing model of the AC with prefix FTKG whereas the outdoor unit showing the model with prefix RKG.
Daikin ac 1.5 ton5 star hay sir mere pass Jab bhi rain hotihay jaise abhi pichle 3 din mein hui to us waqt outer unit ki noice bahoot badhjati hay... Baki normal to niche khade hy tab bhi pata nhi chalta onhay ya off itna quite hay Ladt year bhi yahi problem hui thi aur phir noise bahoot hi jyada badh gai to bahar ki motor change hui thi Rainy season meinhi noise badh jata hay bahoot jyada iska kya reason ho skta hay ?
Pahle to ap supply check krwao jub awaj krta h us time and ampaire agar theek h to sari gas niklwa do aur vaccum pump se 45 minutes vaccum krwa ke dobaara gas charge krwao hojayega theek
Hello sir, Mera Daikin ac (inverter split ) 24me sirf Kam Kar raha Hai. Jab Bahar ka weather Jada garam ho tab tab ac automatically band ho raha Hai. Apparently Dia Hua error code check kara sab sahi Hai. Please reply. Thanks 😊
I have Daikin 1.5 Ton 3 Star AC. Room size is 150 square feet. It takes 20 minutes to go from 34 degrees to 28 degrees at noon, but then it takes 2.5 hours to go from 25 degrees. I don't understand what the problem is. *Please help me and tell me how long it takes to change from 34 degrees to 24 degrees.*
1 Heat load of your room depending upon temperature change like roofheat, wall heat, windows etc. 2. I didn't know about ur ac it is inverter ac or fix speed ac and also about gas fully filed or not. 3 Cooling capacity of your ac.
Sir, Mere ghr 1.5 ton non inverter split ac laga hua hai. 8-9 min mein trip mar jata hai 20degree temperature par set kiya hua hai sir.. Koi error bhi nhi show hoon raha hai.... Plsssss suggest
Sir please help....mai 2 mnth s preshn hu mere pass daikin k inverter ac hai 1.5 tr jo 2 mnth s cooling nh kr ra....jb bhi baarish hoti h us din thnda krta h or raat ko daily thnda krta pr kbhi 2 bje to kbhi 3 bje k bad.....or din me thanda nh krta jis din baarish na ho......km s km 10 ac technician ki team aa kr dekh cuki hai kisi ko smjh nh aaya abhi tk kya problem hai or koi error v nh show kr ra......please help sir......please reply
I hav Daikin inverter ac 2yrs old ... Sir my Daikin inverter outdoor unit turns off after 10 sec and this process is repeating every 10 minutes ... What to do? ... No error code is shown . AC technician told to Change new PCB which is 5000rs. Should I change? Or any other mistake
Same issue for me too. No error code but outdoor stops in 10 sec. I called two different mechanics both are saying board issue. As there is lock down they are saying, board issue can be repaired after lock down only. Any one solved this issue?. Kindly guide
Sir, Mere Daikin 3 star split a me A5 me lambi beep aa rahi hai. Ac functions normal hai indoor k but cooling bilkul nahi ho rahi.... Jo beech beech me ek sound hoti hai normal Opreration me jiske baad ac thandi hawa deta hai wo feel nahi ho raha hai... Lag raha hai wo compressor On ki awaj hoti hai shayad compressor on nahi ho raha hai... Kya karu lockdown me koi mechanic bhi nahi mil raha
Sir ji daikin ka 1ton ka inverter ac h uska 1-2 minutes m outdoor unit triop ho jata h. Uske Baad 1-2 minutes m dobara chalu ho jata h. Kya problem ho sakti h ji. Please
Sir mera daikin ka Split AC he 1.5 ton ka uska outdoor 4-5 second chalne ke baad trip maar deta he mene usko daikin se bande ko bula kar check bhi karwaya tha to usne bola ke pcb kharab he fir mene pcb bhi change kar li he fir bhi vhi problem he aap bataiye kya kar sakta hu ..??
It's an Diakin 1.5 ton split AC and outdoor unit goes off immediately after its on and indoor stays on.. Error code is U2. And technician says change and get new stabilizer . Pls suggest
Error power supply failure ka h Problem Ya to koi connection loose h ya ya fluctuations jayada h first check al the connection if everything is fine then change as technician suggest you
@@totalcoolingsolution thank you sir for quick response. I have checked all connections and they are fine, technician says voltage issue, but there are 2 other ACs, one is very old model and one is 5 months old LG inverter AC on same connection and they are working fine. Also, this Diakin invertor ac, it works fine in the night but during day time, the outdoor unit is not kicking in.. its very strange issue. Can you suggest anything basis this?
I am facing same problem with my daikin 1ton all weather inverter ac, ac is tripping and no error code on remote i mean on all codes single beep. Dont know whats wrong
Brother i have daikin 1.5 ton non-inverter split ac...my ac gives very good cooling its been 2 weeks since we bought...it trips for every 5 mins...when it trips for the first time the cooling gets low and outdoor stops running and when it trips for the second time the outdoor unit start running and cooling comes....outdoor unit stops only for a few seconds...is there any problem
Sir meri bhi ac ka Out door 2 , 3 min bad band ho jata h or mene error bhi dekhe pr mere beep Sound nhi aata h beep speeker pehle bhut low huaa ab koi sound hi nhi krta h or jb se ye beep ana band huyi h tb se hi out door trip krne lga h Daikin se jo banda Aya tha us ne gas poori kr k kha ki PCB khrab h 7.5k ka khrcha diya h dekha kuch bhi nhi bs trip kr rha h pcb khrab h bol diya or pehle cooling drop krta tha to restart krne pr cooling aati thi jb jiyada kha to us ne khola out door or fir pta nhi kya kiya pechkas se ab inverter se non inverter ho gyi h cooling 5 min bad chali jati h 4 , 5 min bad aa jati h pata nhi kya kiya h aap btao kya krna h
@@totalcoolingsolution Sir, mera 1.5 ton Inverter AC 8yrs Old - Beep nahi karti ...... 1 hour mein OFF ho jatey hei Aur Green light blink hoteee rehtey - Daikin sey 2 bar bulaya technician ko - first guy 8000 - Outdoor PCB & 2 nd wala 7000 rs leeke Indoor PCB change kiya boley ...... Issue still not resolved??? I pity myself & curse Daikin & those technicians ...... Beep key liye Buzzer kaisa change kar sakta hun???
My AC does not turn OFF when the temperature is reached. And when the temp is set to 32C it keeps on running. Sometimes OFF and does not start automatically. Please help Model Daikin 1.5ton Split
Ok you mechanic direct your out door that's the reason.... There is some problem in pcb of ur ac plz repair it chandigarh and surrounded area I will cover
@@totalcoolingsolution Hi bro… Outdoor is not direct and Think pcb is problem should I change new pcb orelse is there any of repairing it.. checked temperature sensor too it’s working good.
Sir hmara lg ka inverter ac hai jab ham chalu karte hai 2-3 minutes ke bad trip marta hai uske bad 3-4 minutes ke apne aap chalu ho jata hai ye kya problem hai trip 1 bar hi karta hai
mera daikin inverter ac kafi time leta hai 1 hr 31 se 26 krne mai aur 26 pr pahuchne pr 50% load pr chl rha hai pr pehle 26 pr 20% pr chlta tha room ground floor hai aur ek side sun exposed hai pr dopahar mai 1 hr ke baad bhi full capacity pr chlta hai pr 29 degree pr he aa pata hai 31degree se
@@totalcoolingsolution waise toh pehle sahi chl rhi thi ek dam se aisa hua koi chance hai ke room temperature sensor mai koi issue ho agar hoga toh kya wo pcb warranty mai cover hoga ya nhi? Aur nhi toh sensor change mai kitne rs lgenge?
@@totalcoolingsolution ab toh room temperature 29 se niche nhi jaa rha aur load capacity bhi full pr he show kr rha hai pr cooling kr rha hai Kya yeh ek pcb fault hai
The resistance of the indoor unit suction air thermistor is abnormal - Either a disconnection of the cable, or a short circuit has occurred. CE - Abnormal radiation thermistor resistance - A faulty thermistor, disconnected cable or a short circuiting of the thermistor could be the source of the issue
@@totalcoolingsolution hello there. Mere paas Daikin 1.5 ton inverter AC h. Agar me temp 18 ya 19 me rakhta hu then only compressor on hota h and uske upar temperature krne se outdoor compressor trip ho jata h . Mene technician se kaam karvaya usne indoor and outdoor both pcb ko repair kiya , kich. Sensors ko v repair kiya plus kuch capacitor v change Kiya outdoor pcb me. Also indoor pcb me display sensor me v kuch repair kiya . Even pump down service v hua also vaccum v kiya but no luck. Any suggestions?