Dc control supply earthing system |110v dc system how we getting 55v positive or negative to earth. 

Barani Tech
Подписаться 26 тыс.
Просмотров 13 тыс.
50% 1

Dc control supply earthing system
110v dc system how we getting 55v positive to earth or negative to earth.
normally we get 110v between + to- .then how getting 55v respect to earth
Why we use DC supply in Substation or Switch gear?
What Earthing system are mostly using in Substation or Switch Gear?
What is the application of Mid-Point Earthing ?

Опубликовано:

 

23 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 34   
@Biginjapan85
@Biginjapan85 4 года назад
Many thanks for the video. It cleared many things up! all the best
@erfan_muhammad
@erfan_muhammad 2 года назад
Hi sir, thanks for the video. this is midpoints/center point earthing. 1.what is the another earthing type? positive connection to earth or negative connect to earth. 2. i notice that the most substation using this type of connection. while for the power plant with alot of instrumentation using negative connection to earth. im wondering why. 3. i think this is the best connection to protect instrumentation/plc/ vfd thanks in advance for your reply.
@varadharajanelectricalengi5954
@varadharajanelectricalengi5954 3 года назад
🙏😳🌍🌏🌎😲🙄 6:53 AWESOME EXPLANATION ☢️THALA🙏 9:51 SUPER THALA
@baranitech1026
@baranitech1026 3 года назад
thank you and welcome
@amolmane5586
@amolmane5586 8 месяцев назад
In case postive to ground showing +70v and negative to ground - 40 v . What that means , i observed such type of volatge in many of the substations
@baranitech1026
@baranitech1026 6 месяцев назад
it look like negative earth fault is there or there should be problem in mid point earthing system thank you.
@yousefalotaibi8343
@yousefalotaibi8343 5 лет назад
Could you explain the effect of DC positive or negative eath fault on the trip circuit ? And how can that cause malfunction for protection relays ?
@Biginjapan85
@Biginjapan85 4 года назад
@@baranitech1026 Did you ever make the earth video?
@AnandKumar-ym9yw
@AnandKumar-ym9yw 3 года назад
Thanks you cleared my doubt.
@baranitech1026
@baranitech1026 3 года назад
Your most welcome 🙏
@Mhdmnr68
@Mhdmnr68 5 лет назад
Thanks dear ,very useful explanation,also one doubt this mid point normally taken from battery or in charger in substation?(because both are conected in Parallel)
@rajeshtk1246
@rajeshtk1246 5 лет назад
The shown diagram shows solid earthing of the mid point of the battery bank. If the mid point is earthed solidly, there is still path for half the fault current that would have been present if the battery set's -ve was earthed. The correct way to earth the battery system is: Earth the mid point of the battery bank via a high resistance in the charger. This way, the voltage will be halved. Also, the return fault current if any, will have to overcome the high resistance in the return path to the mid point of the battery bank which earthed as a reference point.
@petarsimic2303
@petarsimic2303 5 лет назад
Thank you for good videos
@SunnySingh-ei3rp
@SunnySingh-ei3rp 4 года назад
Dear sir In our substation DC grounding is not done, what is the advantage and disadvantage of this.
@SunnySingh-ei3rp
@SunnySingh-ei3rp 4 года назад
@@baranitech1026 yes sir we have battery charger
@a.k3771
@a.k3771 3 года назад
Thanks Sir
@baranitech1026
@baranitech1026 3 года назад
Welcome
@gurpreetsinghee
@gurpreetsinghee Год назад
Any method to find out dc leakage in grid sub station sir?
@baranitech1026
@baranitech1026 Год назад
your asking about DC battery leakage sir.
@nilamanijena6904
@nilamanijena6904 5 лет назад
Plz give a lecture on battery maintenance.
@naveenchaddha2802
@naveenchaddha2802 Год назад
Sir please explain Why 11kv incoming panel Y phase PT Ground in Becomake panel
@baranitech1026
@baranitech1026 Год назад
i am not able to understand . if you have schematic please share to my email id i will check for you.
@narayananbiju3224
@narayananbiju3224 2 года назад
For a full battery bank earth system of 30v DC system the phase to earth voltage is 30v,but the phase to earth voltage will be zero volts.
@baranitech1026
@baranitech1026 2 года назад
Positive to earth or negative to earth
@erfan_muhammad
@erfan_muhammad 2 года назад
i dont understand the question.. do you mean +ve to earth = 30vdc -ve to earth = 0vdc. interested to understand
@yousefalotaibi8343
@yousefalotaibi8343 5 лет назад
Thank you
@arifmehmud5677
@arifmehmud5677 4 года назад
thanx
@vigneshwarselva9276
@vigneshwarselva9276 3 года назад
the metal scale is not connected to ground.. then how it is acting like earthing, someone pls explain..?????
@baranitech1026
@baranitech1026 3 года назад
Very good question. This metal scale is just explanation for potential dividend( just like in actual cases). Thank you for your question
@pankajrastogi6834
@pankajrastogi6834 Год назад
Negative to earth will be -55 bhai
@baranitech1026
@baranitech1026 Год назад
negative to earth 55 is done on batter charger Unit thank you for comments bro.
@Biginjapan85
@Biginjapan85 4 года назад
Many thanks for the video. It cleared many things up! all the best
Далее
Understanding DC Ground Faults
1:12:51
Просмотров 10 тыс.
Китайка и Пчелке Холодно😂😆
00:21
Как не носить с собой вещи
00:31
I tricked MrBeast into giving me his channel
00:58
Просмотров 10 млн
Substation Battery Chargers
27:07
Просмотров 27 тыс.
Common Ground - Demonstration - Simply Put
6:28
Просмотров 13 тыс.
DC Grounding: Grounding Series (Part 5)
4:36
Просмотров 24 тыс.
FIXING 24 VOLTS LOW INSULATION | Marine Electrician
9:40
Китайка и Пчелке Холодно😂😆
00:21