Don't mistake it for a bad control board Carrier rooftop 

Michigan Heating Guy
Подписаться 20 тыс.
Просмотров 13 тыс.
50% 1

Learning experience for me I can't possibly know It all www.amazon.com/shop/miheatingguy
Milwaukee 2131-20 M18 ROCKET Dual Power Tower Light
amzn.to/3pe2hYH
Milwaukee M12 Surge Hydraulic Driver Kit 2551-22
amzn.to/3n5offb
Makita E-01563 Impact XPS 3 Pc. 6" Magnetic Nut setter Set
amzn.to/2JdAcku
Milwaukee 48-22-6330 Tongue and Groove Pliers Set
amzn.to/3kfch0R
GoPro Hero 8 Black Action Camera with Accessory Bundle
amzn.to/34AGamf
Veto Pro Pac Tech XL Tool Bag
amzn.to/2U1QqPF
OLIGHT Bundle H2R LED Headlamp, 2300 Lumens Rechargeable Flashlight
amzn.to/370rGiq
Amprobe AMP-320 Clamp Meter
amzn.to/2GNxUHe
Fluke 117 Electricians True RMS Multimeter
amzn.to/3iFZP9t
Milwaukee 2364-20 M12 Rover
amzn.to/2HNvitK
Milwaukee Rocket light 2132-20
amzn.to/341OTPm
#MIHeatingGuy

Опубликовано:

 

6 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 38   
@Tom-l9z
@Tom-l9z 2 месяца назад
I know this is 4 years old, but they made an auto reset replacement for that limit.
@makeithotornothvac6347
@makeithotornothvac6347 4 года назад
I work for a factory authorized dealer for carrier, they are rolling out replacement motors for certain models, call your local branch tech support for tips, wire nut the two red leads together, replace the blower limit with a auto reset, then wire the new limit and the heat exchanger limit in series so if the blower does fail to communicate it will reset on it’s own. Temporary fix
@MiHeatingGuy
@MiHeatingGuy 4 года назад
Thanks
@CarlosMendoza-yo8ul
@CarlosMendoza-yo8ul 3 года назад
Just got off the phone with tech support and that is exactly what he told me to do. Told me to replace limit with #hh18a160 Thanks for the help
@allanford1582
@allanford1582 2 года назад
I can tell you in the course of my 50+ years around this trade, we are in the era of rapid change to be gentle, there is no doubt the limit tripped in heating mode, due to the nature of the fan I always suggest maximum fan off delay and minimum fan on delays where possible, good luck to all service techs, the speed of change will require it.
@Jremi95
@Jremi95 2 года назад
Appreciate this. Just saved me a load of time scratching my ass on a roof trying to figure out what was going on. Not super familiar with carrier equipment, especially the new stuff.
@jonnymac31
@jonnymac31 4 года назад
Nice. So now instead of just the heat exchangers dying every third year the fan will too. Fantastic.
@MiHeatingGuy
@MiHeatingGuy 4 года назад
The only good thing is its going to be easy to change
@gregmercil3968
@gregmercil3968 Год назад
I had a Carrier RTU do similar to me a few days ago, expect this unit was a little older (2015) and had the traditional belt driven blower wheel. The board got 24v but no 24v at the Tstat connections or anywhere else. I went through the whole system and when insane trying to figure it out, I ended up condemning the board. None of those limit switches felt like they were tripped either. Except I think this may have actually been the board, because nothing reset.
@andym7513
@andym7513 Год назад
Wish I had watched this before I ordered a board. Thanks
@maheradous9257
@maheradous9257 Месяц назад
Good job 👍
@stevenbennett9785
@stevenbennett9785 4 года назад
I had one doing the same thing. Ended up being fan not moving enough air. Had to adjust blower on the board based on static, and dc voltage.
@HVACGUY
@HVACGUY Год назад
Thanks for the video. You just taught me something.
@mattcummings8402
@mattcummings8402 Год назад
Thanks so much for this! Saved me a huge headache.
@trinito97
@trinito97 Год назад
Now you have to find out why is tripping
@MiHeatingGuy
@MiHeatingGuy Год назад
Filters
@steverosswog4926
@steverosswog4926 4 года назад
I had this same exact problem last week, had the same thought, bad board. Another guy went back to change the board and found that limit tripped.
@renj6531
@renj6531 4 года назад
0:15 that fan reminds me of the one on the old porshce air cooled engines
@RJMaker
@RJMaker 4 года назад
That reverse vane (or whatever it's called) blower is great. Hopefully those units were commissioned correctly, if not you'll be back.. :-(
@antoniosantiago2770
@antoniosantiago2770 4 года назад
Question why did it trip. Maybe in heating. That's what I want to follow up if it happens again. Great video
@MiHeatingGuy
@MiHeatingGuy 4 года назад
I think it happened in heating with not enough delay for the fan on off cycle
@capitolrefrigerationheatin7501
@capitolrefrigerationheatin7501 4 года назад
@@MiHeatingGuy there is a service bulletin for that issue
@sharky5570
@sharky5570 4 года назад
Limit trips cuz the fan stops running and found sometimes it’s the plug not making good connection to the controls
@jwchicano
@jwchicano 4 года назад
Blower off delay isn't adjustable to my knowledge (please correct me if I'm wrong) and not sufficient to cool the heat exchanger. Been replacing those limits with automatic reset limit switches.
@MiHeatingGuy
@MiHeatingGuy 4 года назад
I think your right
@AmericanFarmerHVAC2024
@AmericanFarmerHVAC2024 2 года назад
Rooftop with an icp sticker? Must be a recent decision.. never seen any icp rooftops before.
@dwight.bennett
@dwight.bennett 4 года назад
Interesting ... Guessing the idea behind the new fan design to eliminate belt/pulley maintenance ... Seems like that got swapped for controls maintenance.
@MiHeatingGuy
@MiHeatingGuy 4 года назад
The new fan is because of government regulations
@guyguyguy2020
@guyguyguy2020 2 месяца назад
Would there be a manual reset limit in a Carrier HVAC? No power to our Controller or boards. We swapped everything from boards to transformer and Controller. Everything works perfectly fine with an ac that is running. Any ideas? Thanks
@MiHeatingGuy
@MiHeatingGuy 2 месяца назад
Believe it or not, some of the older carriers when they switch to the little blue fan have manual reset high limits in that compartment and there is a service bulletin on them. I've done the same thing, changed every board out and still no power because of a limit
@jsfkdkjslfdslfkdj
@jsfkdkjslfdslfkdj 4 года назад
Cool tip thanks
@Jason-wc3fh
@Jason-wc3fh Год назад
What a POS. a heat related limit switch prevents the whole board from working and not even allowing you to have air conditioning. Does it not display the fault anywhere?
@MarkCarpenterHVAC-me2jg
@MarkCarpenterHVAC-me2jg Год назад
In newer commercial units, most things including smoke detectors are now home run to the board. Trane uses Modbus, similar to the way cars use CANbus. It's nearly impossible to meet efficacy standards like California's Title 24, using electro mechanical controls anymore. Newer Carrier units are going to Near Field Communications (NFC). You hold your phone up to the board similar to the way you tap to pay for things at the store. Haven't worked on one yet but it seems interesting. Not to worry much of this is on It's its way to residential units. The normal progression is from Chillers > Commercial > lite commercial and finally on to residential. There are some advantages to using DC reference signal to ground, it sure makes for some easy troubleshooting.
@dennisduffy5678
@dennisduffy5678 2 года назад
What caused the trip ? you just reset it ?
@MiHeatingGuy
@MiHeatingGuy 2 года назад
Brown out
@jamesg9936
@jamesg9936 4 года назад
Where in the world have you been
@fastzombie1
@fastzombie1 4 года назад
That is a really odd looking fan.
@throttlebottle5906
@throttlebottle5906 4 года назад
more great engineering by people whom can hardly wipe their rears and have zero field experience... yet a piece of paper says they're qualified, for what? :))
Далее
No Colling On A Friday Night At Taco Bell
17:01
Просмотров 2,6 тыс.
Первый день школы Катя vs Макс
19:37
Butch REACT to Creative way to fix damaged tile!
00:46
Просмотров 858 тыс.
Аруси Точики ❤️❤️❤️
00:13
Просмотров 253 тыс.
New Carrier RTU No Cooling
8:52
Просмотров 11 тыс.
MULTIPLE CARRIER VFD FAILURES
12:42
Просмотров 46 тыс.
What Is an Economizer for a Packaged RTU?
8:25
Просмотров 14 тыс.
Breaker Tripping On Kitchen RTU or Is It?
16:43
Просмотров 9 тыс.
Short Pro tool AC Diagnostic troubleshooting
18:59
Просмотров 23 тыс.
Furnace/AC How to Troubleshoot The Control Board
9:11
Просмотров 861 тыс.
Finding The Problem In The Sea Of Condensers
10:23
Просмотров 2,2 тыс.
Первый день школы Катя vs Макс
19:37