EARTH LEAKAGE - REAL LIFE EXAMPLE 

Bristolsparky
Подписаться 10 тыс.
Просмотров 18 тыс.
50% 1

No need for fancy intros….
No need for fancy graphics….
No need for clickbait….
No sponsorship….
Everything you see i have purchased myself, this gives me complete control to voice my honest opinion about any product
Just day to day sparky videos
If you like it, that’s cool, if you don’t, that’s cool as well.
Remember, context is important, I can’t show/film every part of every test otherwise I’d still be there now😂just assume I’ve carried it out correctly

Опубликовано:

 

29 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 65   
@OptiJack
@OptiJack Год назад
Did you ramp test just the rcd with no load on it? If load still on then existing leakage could effect ramp test reading?
@bristolsparky
@bristolsparky 10 дней назад
Can't remember
@davidpatterson1574
@davidpatterson1574 10 месяцев назад
Very informative video-thankyou
@bristolsparky
@bristolsparky 10 месяцев назад
Glad it was helpful!
@sergiofernandez3725
@sergiofernandez3725 Год назад
Good video
@bristolsparky
@bristolsparky Год назад
Thanks
@leevium
@leevium 8 месяцев назад
comprate una pinza de fugas con coneccion bluetooth te ayudaria mucho
@bristolsparky
@bristolsparky 8 месяцев назад
Nah, that’s OTT, this’ll do just fine
@DominicBoyle-o8x
@DominicBoyle-o8x Год назад
Everyone's favourite game 😀
@JimWhitaker
@JimWhitaker Год назад
Not
@bristolsparky
@bristolsparky 13 дней назад
😂
@g0fvt
@g0fvt Год назад
Even as a non electrician earth leakage faults have driven me insane more than once, when you have isolated every appliance in the kitchen, unplugged everything only to find a pet has pissed on an extension lead behind a settee.
@bristolsparky
@bristolsparky Год назад
😩😩😩
@Davidhughes9467
@Davidhughes9467 8 месяцев назад
could you not smell it 😂😂😂
@g0fvt
@g0fvt 8 месяцев назад
@@Davidhughes9467 sadly not, or more accurately they do it somewhere else as a distraction...
@icarossavvides2641
@icarossavvides2641 Год назад
I like the way that we are required to use metal CU's but its OK to stick them in a lovely flammable cabinet!
@bristolsparky
@bristolsparky 14 дней назад
They aren't flammable
@HenryOCarmichaelSmith
@HenryOCarmichaelSmith Год назад
Isolate the board and check again. Could be diverted neutral current from another property?
@bristolsparky
@bristolsparky Год назад
Already checked, It’s not diverted neutral current
@louissmith5203
@louissmith5203 Год назад
Good video to see mate. Informative for someone like myself still learning 👍🏻 always good to see somone break things down while having a little laugh 👍🏻😅
@bristolsparky
@bristolsparky Год назад
Thanks 👍
@philipoakley5498
@philipoakley5498 Год назад
RFI filters in all the electronics take up to 1.6mA each, eg Computer + 2 display units, set top box + TV, that's 5 straight off.
@bristolsparky
@bristolsparky 10 дней назад
Exactly 👍🏻
@JBE
@JBE Год назад
New RCBO board on its way and definitely worth taking a bag of crisps for your trouble 😊.
@bristolsparky
@bristolsparky Год назад
Sounds good!🤌🏻🤌🏻
@JohnnyMotel99
@JohnnyMotel99 Год назад
best turn phone sideways
@bristolsparky
@bristolsparky Год назад
Nah, it’ll be fine
@dmlelectrics8990
@dmlelectrics8990 Год назад
Good video As your aware in the regs a 30mA RCD is only allowed 30% which is 9mA so wouldn’t comply. Bad practice putting Solar on a AC RCD shared with other circuits. Would be interested in what the DC leakage was? Obviously not above 6mA as it didn’t blind the AC RCD when testing. I’m looking at getting the TIS 570 AC/DC earth leakage tester to replace my Megger 305E.
@dmlelectrics8990
@dmlelectrics8990 Год назад
@@Mainly_Electrical Thanks corrected it. My bloody podgy fingers using my phone 😂
@bristolsparky
@bristolsparky Год назад
I’m very aware of the current requirements mate👍🏻 it is not my installation, called out to intermittent tripping & have given my professional advice to the client
@dmlelectrics8990
@dmlelectrics8990 Год назад
@@bristolsparky I realised it wasn’t your installation mate, I wasn’t being negative? I was just backing you up & adding some facts/figures for others who might be trainees etc.
@bristolsparky
@bristolsparky Год назад
@@dmlelectrics8990 👍🏻👍🏻👍🏻
@grahamek86
@grahamek86 Год назад
Probably find the immersion heater will dump a few mA into earth when heating the water. Quite common for the elements to get a bit leaky.
@bristolsparky
@bristolsparky Год назад
The immersion is currently a backup & not used so in this instance it was not part of the issue
@joejames8146
@joejames8146 6 месяцев назад
I went to a job today with 1.5amps between Line and neutral tails any ideas? split load board intermittently tripping a single RCD
@bristolsparky
@bristolsparky 5 месяцев назад
Issue somewhere!
@lansdorf
@lansdorf 6 месяцев назад
Went to a property were the down stairs lights worked with the neutral meter tail sisconected and all earth conductors disconected.
@bristolsparky
@bristolsparky 5 месяцев назад
Ok
@gregcressey1791
@gregcressey1791 3 месяца назад
The radius bend isnt rignt surely also exposed metal glanding
@bristolsparky
@bristolsparky 2 месяца назад
The bending radius isn't great
@gd-bq7em
@gd-bq7em 9 месяцев назад
Did you change the c.u did it solve the issue
@bristolsparky
@bristolsparky 9 месяцев назад
Yes, watch a later video where I change it.
@rjkelectrical6086
@rjkelectrical6086 Год назад
Good video 👌
@bristolsparky
@bristolsparky Год назад
Thank you 👍
@Rossisearle
@Rossisearle Год назад
😅😅
@bristolsparky
@bristolsparky 10 дней назад
👍🏻
@Rossisearle
@Rossisearle Год назад
Great.. so easy Ill happy help you
@bristolsparky
@bristolsparky 9 дней назад
🤙🏻
@bongyb9407
@bongyb9407 Год назад
next time ya ramp test, turn the circuits off so there is no load through the rcd giving you a more accurate result pal 👍
@bristolsparky
@bristolsparky Год назад
Prefer real scenario results but I understand what you’re saying.
@garrygriffithselectricalse843
Split boards 🤦🏼‍♂️
@bristolsparky
@bristolsparky 10 дней назад
Terrible
@stevebowley
@stevebowley Год назад
I have the same tester. Do you ever have any issues with it. Sometimes certain applications show massive currents reading which must be wrong be rcd not tripped 🤷‍♂️
@bristolsparky
@bristolsparky Год назад
Never had an issue with mine
@adoughertycontracting7243
@adoughertycontracting7243 Год назад
I had a issue with mine so i ended up getting the megger one.
@andrewwhite3793
@andrewwhite3793 4 месяца назад
Why did you ramp test the RCD with the circuits on ?
@bristolsparky
@bristolsparky 4 месяца назад
To prove if it’s weakened under load
@dennisfowler-dg5vf
@dennisfowler-dg5vf Год назад
those tester are shit...not reliable....good vid thou
@bristolsparky
@bristolsparky Год назад
I’ve had this one for 4 years and it’s always been reliable
@dennisfowler-dg5vf
@dennisfowler-dg5vf Год назад
mines been giving me reading all along...until i compare it with a more expensive one ...then begin to wonder .... which one is right or wrong @@bristolsparky
@johnlee701
@johnlee701 4 месяца назад
​@@bristolsparky do you still use them? I'm after a set and the megger ones are about 4 times the price 🤦‍♂️
@bristolsparky
@bristolsparky 4 месяца назад
@@johnlee701 yes, still use it after 4 years
@mossmm73
@mossmm73 Год назад
For full information as well as your videos to give us more benefit Please make videos This video would be more beneficial if made properly
@bristolsparky
@bristolsparky Год назад
Yaaaawwwwwnnnn
Далее
Fault Finding - You Will Never Guess What It Was...
13:46
DAXSHAT!!! Avaz Oxun sahnada yeg'lab yubordi
10:46
Просмотров 329 тыс.
Inside a smart meter, and the REAL problem with them.
16:45
FAULT FINDING - RING CIRCUITS
15:38
Просмотров 42 тыс.
EARTH LEAKAGE MEASUREMENTS
15:38
Просмотров 79 тыс.
RCDs: Neutral - Earth Faults
11:32
Просмотров 446 тыс.
How a AC/DC Clamp-Meter works
20:48
Просмотров 53 тыс.
DAXSHAT!!! Avaz Oxun sahnada yeg'lab yubordi
10:46
Просмотров 329 тыс.