Earthing & Bonding Lecture 7 : Earth Resistance of Vertical Rod 

Railway Engineering Insights
Подписаться 6 тыс.
Просмотров 2,4 тыс.
50% 1

Опубликовано:

 

23 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 26   
@aliuyar6365
@aliuyar6365 2 года назад
Great teacher
@railwayengineeringinsights6463
@railwayengineeringinsights6463 2 года назад
Many thanks
@mwangimurikwa3630
@mwangimurikwa3630 3 года назад
Thanks very much Engineer, I have watched your 7 lectures on earthing and I am truly grateful. I now have a much better understanding of earthing. Thanks for your generosity and may God bless your life.
@railwayengineeringinsights6463
@railwayengineeringinsights6463 3 года назад
Many thanks for your words.
@arjunmurmu2427
@arjunmurmu2427 Год назад
Mind blowing 👌👌👌
@railwayengineeringinsights6463
Many thanks
@shrutishetty7058
@shrutishetty7058 4 года назад
Back to engineering school... Superb explanation .. Keep doing the grt work... 👏👍📑📚
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Many thanks...
@Priyanka-bh6cj
@Priyanka-bh6cj 4 года назад
This has clear my old doubts..Thanks..
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Many thanks...
@mwangimurikwa3630
@mwangimurikwa3630 3 года назад
Hi Engineer, looking forward to your lecture on earthing of surge diverters
@railwayengineeringinsights6463
@railwayengineeringinsights6463 3 года назад
Will upload soon
@이승훈-g4c4d
@이승훈-g4c4d 4 месяца назад
Hello. Your video is so helpful. By the way, at 9:36 the third formula named EN50522 is different from the drived formula. Could you explain why the third one is different from the first?
@railwayengineeringinsights6463
@railwayengineeringinsights6463 3 месяца назад
Actually, all these standards not only follow the derived expression, but make suitable adjustments to it based on test reports and results from software to match accuracy. Therefore, you might some changes. However, the approach remains same.
@sexualhealin87
@sexualhealin87 4 года назад
Thanks for your videos. What would you do if the earth rod was not a "rod" and instead a pipe? Would you include the material contained within the pipe as the overall "rod" diameter?
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Many thanks... What you stated is correct.... The resistance that we derived here is the dissipation resistance of rod. So, whether you take into consideration rod or pipe in both the cases it remains same. We will consider pipe radius as initial value and infinity as final. It would be great if you also refer to Lec 2 of this series, where I explained about dissipation resistance.
@muralikrishnapaluri2007
@muralikrishnapaluri2007 Год назад
how to calculate the Resistance of earth rod when provided with chemical earthing
@avitimushi1541
@avitimushi1541 4 года назад
After equating A1 to A2, how did you arrive at A that you used in the derivations?
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Here A is the cross section area, which is considered to be equal to A1 at x distance from the rod (A=A1). Then at x+dx, it will be A2. As dx is tending to 0, A2 will be nearly equal to A1 as we can equate dx to 0. So, A1=A2=A.... This is true only for dx change, i.e. very very small change...
@SM-de2it
@SM-de2it 4 года назад
Could you please provide the same video for the horizontal rod and more importantly plates?
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Sure will do that... For horizontal rod with half inside the surface and plate, I will prepare one lecture... However, for the case where rod is embedded at certain depth like the case of BEC, we need to use Maxwell equations which I will deal in EMC series...
@SM-de2it
@SM-de2it 4 года назад
@@railwayengineeringinsights6463 Thanks a lot. I will wait for your update. By the way, how do you apply the soil material, humidity, temperature, etc. to the problem when designing the grounding system? Because for example, if you are using the vertical rod, still, you have to consider that because of the geographical position of the well, maybe you cannot obtain a good value for the resistance. Please correct me if I am wrong.
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Yes you are absolutely correct... We need to measure the soil resistivity (using Wenner 4-pole method)... Which is dependent on the type of soil (geographical location, temperature, moisture content, etc). If we find that the resistivity to too high like in dry regions, then we apply resistivity enhancement material like bentonite... This helps to lower the resistivity... Also sometimes we used concrete cased electrode, this help also in reducing corrosion if you use MS as the rod material...
@SM-de2it
@SM-de2it 4 года назад
@@railwayengineeringinsights6463 I would be grateful if you can explain about the methodologies of the items that I have written in my two comments in your next video.
@railwayengineeringinsights6463
@railwayengineeringinsights6463 4 года назад
Sure I will do a video... However, it will be done at the end of this series where I will explain about resistivity test... Upcoming lectures will be related to fault calculation....
Далее
Fastest Build⚡ | Doge Gaming
00:27
Просмотров 792 тыс.
Lecture 11: Earth Resistance Test - Part 1
26:39
Просмотров 10 тыс.
Installing an earth Rod - New TT Supply
30:36
Просмотров 50 тыс.
Earth Electrodes Part 1
11:48
Просмотров 100 тыс.
How 3 Phase Power works: why 3 phases?
14:41
Просмотров 1,4 млн
Rail Human Library - Introduction to OLE
1:17:47
Просмотров 3,6 тыс.