HIPOT TEST FOR HV BUS BAR
FOR HV 6.6KV Switchboard
Before going into Test we have to check the following things
1. Open earth switch.
2. Rack out VT
3. Check The barricade around Testing AREAR.
4. IR test has to conducted before hipot testing.
5. Check the humidity of the place.
For switchboard bus bar peak withstand voltage is 20 KV so we are going for 80% on it. Ie is 16KV
DOWNLOAD HIPOT TEST REPORT
drive.google.c...

Опубликовано:

 

29 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 29   
@zeeshanahmad5997
@zeeshanahmad5997 3 года назад
Where we use AC hipot and DC hipot. In RMU bushingh which test carried out AC or DC?
@baranitech1026
@baranitech1026 3 года назад
For bus bar we use AC hipot test , for cable we use DC hipot test.
@zeeshanahmad5997
@zeeshanahmad5997 3 года назад
@@baranitech1026 reason?
@baranitech1026
@baranitech1026 3 года назад
@@zeeshanahmad5997 ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-eWha0JtvH5o.html
@velusamypothiraj2300
@velusamypothiraj2300 3 месяца назад
@@baranitech1026any reason
@ranjitsahoo7627
@ranjitsahoo7627 3 года назад
Sir, What about Circuit Breakers i.e. Racked in/out and Close/Open Condition
@baranitech1026
@baranitech1026 3 года назад
outgoing or incoming cable has to remove and we can keep cb in service with close
@velusamypothiraj2300
@velusamypothiraj2300 3 месяца назад
@@baranitech1026control circuit hipot test how to perform?
@DesiMusafir1
@DesiMusafir1 5 лет назад
Dear Sir,Your video is very helpful . I follow but kindly explain test kit name ,connection and acceptance criteria
@pardeepsharma8657
@pardeepsharma8657 11 месяцев назад
How much value of mA is allowble?
@baranitech1026
@baranitech1026 9 месяцев назад
it is not fixed its depends on number of feeder for best check is to ref with FAT reports thank you.
@muhamedmuneer4540
@muhamedmuneer4540 3 года назад
Why hipot not doing in distribution transformer and VT at site ?
@baranitech1026
@baranitech1026 3 года назад
i don't know but i try to get answer for your question
@harekrushnadixit400
@harekrushnadixit400 3 года назад
Hi sir can you tell your kit make
@baranitech1026
@baranitech1026 3 года назад
kephv.com/en-en/hipot-tester/hvts-70-50 for your ref.
@kedarnathswain2540
@kedarnathswain2540 4 года назад
Video not clearly and talking not clearly
@baranitech1026
@baranitech1026 4 года назад
in future i will try to make more clear video
@dinkartiwari1883
@dinkartiwari1883 2 года назад
Sir please show connection
@velusamypothiraj2300
@velusamypothiraj2300 4 года назад
Is AC dc hipot option in same kit or another one
@dhanabalanify
@dhanabalanify Год назад
Good information
@baranitech1026
@baranitech1026 Год назад
thanks and welcome
@dickiirnanda700
@dickiirnanda700 3 года назад
How much time need to DC High Voltage for busbar ?
@baranitech1026
@baranitech1026 3 года назад
60 sec
@dickiirnanda700
@dickiirnanda700 3 года назад
What reference for this time ? 60 s
@dickiirnanda700
@dickiirnanda700 3 года назад
Standard or anything else ?
@baranitech1026
@baranitech1026 3 года назад
@@dickiirnanda700 standard .
@dickiirnanda700
@dickiirnanda700 3 года назад
I know this from standard but what stnadard ? Iec ?
Далее
How to Hipot Test
11:15
Просмотров 124 тыс.
BB Diff high impedance Stability test
7:43
Просмотров 1 тыс.
CAN Bus Properties and Troubleshooting
18:09
Просмотров 1,4 млн
GIS BUS BAR HIPOT TEST
6:50
Просмотров 12 тыс.
AC vs. DC Hipot Testing
8:49
Просмотров 38 тыс.
How to do HT breaker hipot ?
8:29
Просмотров 5 тыс.
High Voltage Test | With Practical | TheElectricalGuy
12:34