Тёмный

How to calculate cable size || Cable calculation formula with example 

Be An Engineer
Подписаться 10 тыс.
Просмотров 198 тыс.
50% 1

How to calculate cable size:
First we must know these three values:
Load - ?
Voltage - ?
% efficiency - ?
Example:
Load (P)=1 kW
Voltage=230 V
% Efficiency=80%
Answer:
Formula-
P = V x I x CosØ x efficiency %
1000 = 230 x I x 0.8 x 0.8
I = 6.79 A
Every Motor have Voltage drop avg.=2%
Voltage drop=6.79 x 2%
=0.1358 A
Total Current=6.79+.135
= 7 A
For Al Cable:
1 sqmm =1.5 A
So
7 A = 1/1.5 x 7
7 A = 4.66 sqmm.
For Cu Cable:
1 sqmm = 2.5 A
So
7 A = 1/2.5 x 7
7 A = 2.8 sqmm.
Facebook Page Link:
Be-A-Enginee...

Опубликовано:

 

4 июл 2019

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 54   
@abdulghafoor8186
@abdulghafoor8186 3 года назад
Thanks a lot ,very helpfull vedio
@nelson.s718
@nelson.s718 4 года назад
Great bro....tnx
@prasadsad4196
@prasadsad4196 Год назад
Great Teaching.
@abhishekmishra5936
@abhishekmishra5936 3 года назад
Thank you so much 🙏
@sadsad220
@sadsad220 4 года назад
efficiency relates output to input power, you can not add it to the power equation, then your assumption is correct only if you put the source near the load only if not you have to take cable length into consideration
@electrictech7996
@electrictech7996 4 года назад
Thank you so much
@chetanchavan4567
@chetanchavan4567 3 года назад
Thank you ....friend .....power factor ke liye video bana de na ...details me
@tahirajmeri7073
@tahirajmeri7073 Год назад
What about short circuit capacity?, It's play important role in cable sizing selection.
@athilaldurry5880
@athilaldurry5880 3 года назад
Many thanks
@gandaraysabellemontecarlo1011
@gandaraysabellemontecarlo1011 11 месяцев назад
Good day to you Sir, may I know the voltage drop you have used for single phase and for 3 phase of 2 and 5 percent respectively. Is there calculation table for that voltage drop ?. Supposing the distance of the motor is 30 meters what might be the VD assuming the motor is operating at 440v three phase, with the same Eff.
@arun4846
@arun4846 2 года назад
Thanks ❤️❤️❤️
@GreenLandFamily
@GreenLandFamily 4 года назад
dear sir my load 1200 amp, laying root is inside the mud,total length is around 50 mtr which type cable using ? please help me
@ELShahbaazHussain
@ELShahbaazHussain 2 года назад
Sir how can we find no of stranded wires without using standard table of conductors?
@Mokamafoods
@Mokamafoods Месяц назад
Where did you get cos fi value?
@moocow8204
@moocow8204 Год назад
why 2% voltage drop for single phase versus 5% drop for three phase? can it change?
@nabeelshahulhameed2451
@nabeelshahulhameed2451 4 года назад
1 sq mm cu cable have 6 amps capacity
@Nideesh777
@Nideesh777 3 года назад
Hi, if 1sqmm = 6 amps, for 100amps motor is it sufficient 20sqmm?
@AbdulHakim-zz6mb
@AbdulHakim-zz6mb 4 года назад
Sir why we multiply efficiency in formula please explain....
@kdaksh1996
@kdaksh1996 Год назад
Eff.= P/VI cos fi
@manabendragiri1138
@manabendragiri1138 2 года назад
Please tell me what is cable size of breaker
@mahfuzalam939
@mahfuzalam939 2 года назад
And cable selection plz reply
@ranjan1436
@ranjan1436 4 года назад
Voltage drop depends on the length of the cable??
@NawtieBoy96
@NawtieBoy96 3 года назад
yes , R= p*L/A , V=IR so more length means more resistance , more voltage drop
@pkelectrical3813
@pkelectrical3813 4 года назад
Bhai your vedio is very helpful for me....and ..bhai..apka...samzana..ka ..tarika..or .bi. Good..ha ..bhai... ..bahi ek or vedio ACB ..ki. rating par ..chaya.. bhai
@thegoldenmomentsinformativ4138
Good
@ParthaPratimMahapatra
@ParthaPratimMahapatra 3 года назад
3hp submirsible motor single phase. I need cable size for aluminum. Distance from electric meter is 1000 to 1200 meter.
@kishorsalunke5434
@kishorsalunke5434 9 месяцев назад
👌
@user-ge1mh1dg8q
@user-ge1mh1dg8q 6 месяцев назад
P/v×cos°×effiency 1Phase formula how to possible 6 A
@ngtech118
@ngtech118 9 месяцев назад
Sir cable cross section calculation ka video banao
@pateldivyesh9030
@pateldivyesh9030 Год назад
Sir 22kw motor he kitne ka cables lage ga plz sir thoda calculation shamjaye
@Tech_Gaurav
@Tech_Gaurav 4 года назад
Amp mai 2 % kab se drop hone laga
@khajaanwer745
@khajaanwer745 9 месяцев назад
regarding this cable size ans is not understand how you got ans i=20.5 A explain clearly
@balajiengineers
@balajiengineers Год назад
Nice information #balajiengineers
@patelkaushik2996
@patelkaushik2996 3 года назад
1kw to 500 kw taki motor me voltage drop kitna lena parega
@basantaswain2219
@basantaswain2219 Год назад
Sir building ka load calculation kese kare
@sanjayson1
@sanjayson1 4 года назад
For Fire pump
@mubasshiryunus2241
@mubasshiryunus2241 11 месяцев назад
@giriyappaanapur4861
@giriyappaanapur4861 Год назад
Your thumb rule of current carrying capacity of cable is wrong you can check
@AbdulHakim-zz6mb
@AbdulHakim-zz6mb 4 года назад
and one thing more. .....why we take 0.8 always for cos@
@mohammedsaifullah6437
@mohammedsaifullah6437 4 года назад
Hello friends chai pelo 🤭🤭
@narottamdwivedi8148
@narottamdwivedi8148 3 года назад
How to convert hp into kw
@BeAEngineer
@BeAEngineer 3 года назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-70ebZpasdPI.html
@danieldyer9177
@danieldyer9177 3 года назад
Got 0.9 for cos@
@user-fq1ij3sn8t
@user-fq1ij3sn8t Год назад
Where is cable sq mm calculation?
@electricalworld4692
@electricalworld4692 4 года назад
230x0.8x0.8 = 147.2????
@electricalworld4692
@electricalworld4692 4 года назад
Kindly clarify please
@TheRenijoy
@TheRenijoy 4 года назад
@@electricalworld4692 1000/147.2=6.79 1000=1kw
@atulthanawala6397
@atulthanawala6397 3 года назад
योर गाइड लाइन में बहुत गलत रेटिंग दिया है
@ankushpatil3451
@ankushpatil3451 2 года назад
Wrong explanation for cable size
Далее
Cable Selection Method | Cable size calculation
13:08
Просмотров 3,3 тыс.
BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.
11:39
Просмотров 170 тыс.
How to choose sq mm of Electric Cables? _Tamil
13:02
Просмотров 292 тыс.