I find this material very helpful.. think you guys.. personally I can tell Dettronics are the best detection device I ever see thinks again. Greetings from Algeria 🇩🇿
Great short video to the point. You’re awesome. I’ve been trying to understand these at my work for years. This video made it all come together. Thank You 👍
Hi Jose, You will need to confirm you are using a mA generating device. Some PIRECL units are for the Det-Tronics EQP and will not generate a mA signal. Once you confirm it’s a mA device, you will have to ensure you have a jumper in at terminals 5 and 6 with the signal wire on 7. Power is important as well. Terminal 2 is +24 and terminal 1 is the negative. If you are doing a 4 wire configuration, then the mA loop will need to be powered. Terminals 6 and 7 are the mA loop. The wiring diagrams can be found on page 10 of the manual. If you like, I can email this to you (lets connect via info@spartancontrols.com). - Leon Jackson, Field Service Specialist