How to check a 3 phase motor system 

Electronic Control Services
Подписаться 8 тыс.
Просмотров 1,2 млн
50% 1

How to check a 3 phase motor system. This addresses the 3 phase motor in the system. Working through the system Motor to disconnect,overloads, contactor and fusses. Check us out at www.improvemaintenance.com
I have a written version with simple print at www.improvemaintenance.com/3-p...
Troubleshooting a 3 phase motor system. I teach these methods and more on site on your equipment. George@improvemaintenance.com

Опубликовано:

 

25 окт 2014

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 106   
@mrdkoser
@mrdkoser 7 лет назад
Professional and impressive use of theory. Great job!
@chandanshanaz3340
@chandanshanaz3340 8 лет назад
very good testing, explaining in a simple way...
@mikekuknyo3329
@mikekuknyo3329 2 года назад
Great video man. 10 yrs maintenamce...excellent suggestions...thank u
@kalelopaka
@kalelopaka 5 лет назад
Done hundreds, this is the cleanest place I've ever seen, where's the water and hazardous chemicals, thats where I learned.
@electricalcontractor6944
@electricalcontractor6944 3 года назад
If water and hazardous chemicals were part of an electrical system what you said you matter, but clearly that not the case, so what you stated is out of place. Electricity works the same way regardless, of where it is.
@fasteddie4107
@fasteddie4107 3 года назад
Motor. Disconnect. Overload. Contactor. Fuses. Power. Check. Great video. Thanks for sharing this great information.
@theotrotchie
@theotrotchie 7 месяцев назад
Very well explained. I have slow it down and rewatch because a lot is covered in this vid.
@wilecoyote2650
@wilecoyote2650 8 лет назад
very good, correct PPE, this is the way it should be taught, very good
@MD-cd7em
@MD-cd7em 6 лет назад
GREAT VIDEO!..YOU COVER BASICS AND GET TO THE POINT!!
@javierferrer4634
@javierferrer4634 5 лет назад
Excellent video thank you!
@edgardoalfaro2307
@edgardoalfaro2307 6 месяцев назад
Great information like the way you explain the topic
@firemusic82
@firemusic82 9 лет назад
Very helpful. Thanks for this.
@Improvemaintenance
@Improvemaintenance 9 лет назад
Thank You for the feedback. If you have any video requests go ahead and post in comments and we will try and get one together.
@firemusic82
@firemusic82 9 лет назад
I do actually...a turn to turn short. Walk us through how to diagnose a turn to turn short in a 3 phase motor.
@user-wb3yp4bm1k
@user-wb3yp4bm1k 7 лет назад
Edward James م
@dougjones4987
@dougjones4987 5 лет назад
Good explanation thanks
@wmhvac-r2826
@wmhvac-r2826 6 лет назад
Great video
@surendrakverma555
@surendrakverma555 2 года назад
Very good. Thanks
@nickledimez4012
@nickledimez4012 2 года назад
Good video!
@simpliciocamirino2271
@simpliciocamirino2271 2 года назад
thank you for that sharing sir.
@Improvemaintenance
@Improvemaintenance 9 лет назад
Our first how to
@user-tf2yy8ck6z
@user-tf2yy8ck6z 7 лет назад
IMPROVEMAINTENANCE
@theslenderman4427
@theslenderman4427 4 года назад
Hey bro if i i only have 3 cables and are ground red and black so my question is i want to install a little switch fuse box can i connected only using ground red and black
@theslenderman4427
@theslenderman4427 4 года назад
Please let me know if you can
@tomascolz6375
@tomascolz6375 5 лет назад
to check the motor it's better to use isolation tester. more than 0,5 MegaOhm between ground and phases. You check the cable also.
@nithyanandavenkatappa5416
@nithyanandavenkatappa5416 2 года назад
Please *confirm and clarify* the following; Is it possible to connect 3-Phase twin motor control panel in series (*two Numbers*) - for the same/ only one pump set- motor ??
@michealplater9007
@michealplater9007 2 года назад
I start at the other end, most faults are not at the motor, most of the time there is a protection trip, phase supply fault, overload or over temp.
@mauriciolopez9652
@mauriciolopez9652 9 лет назад
Thank you, really helpull info. xD
@mdmannankhan8358
@mdmannankhan8358 7 лет назад
thanks
@upakotv6457
@upakotv6457 8 лет назад
i prove exellent circuit
@scrappydogfinance8434
@scrappydogfinance8434 2 года назад
First test should be for voltage to ensure the circuit is actually de-energized. You should test your meter first on a known live circuit, then test on the de-energized circuit, then check on the known live circuit again to ensure your meter is actually working and not falsely indicating 0 voltage. Make sure your meter is properly rated for the Hazard category. usually 480vac 3phase motor circuits are considered CAT III. Minimum your meter should be rated for CAT IV 600V or CAT III 1000V even better. It should be certified by at least 2 independent labs like UL CSA TUV DVE for this CAT rating. Your test leads should have been inspected for any damage before use and your probe tips should have the least amount of metal exposed as possible. Ideally you clamp the COM lead to a ground away from the terminals to be tested first. and then use 1 hand to probe each terminal for voltage 1 at a time. This creates a greater distance between the two leads and lowers risk of accidental arc flash forming between the probe tips. After you are sure the circuit is de-energized then you can check phase to phase ohms on the motor windings and T leads.
@russelsprout2155
@russelsprout2155 Год назад
If you don't know this you shouldn't be touching this equipment
@kevinb.3656
@kevinb.3656 11 месяцев назад
Dude, no shit.
@adamkarsky473
@adamkarsky473 7 месяцев назад
No shir huh, you copy paste that from Google 😂
@StealingLightLtd
@StealingLightLtd 6 лет назад
Your written list is 404 error for the url.
@shanemcdaniel1509
@shanemcdaniel1509 5 лет назад
Watch this video more than once a grasp what he is saying also watch other videos on motor Controls and how to use a meter along with the danger of 3 phase 480/ 600 volts potential ...period
@jasondangelo7064
@jasondangelo7064 8 лет назад
why not check amperage???
@FaZeno5cope
@FaZeno5cope 4 года назад
If you motor starts with the N.O start button and stops correctly, the control circuit is working properly and you can eliminate most of the steps shown in 30 seconds or less, then just check the power circuit and go from there. If your motor isn’t wanting to start, try manually picking it up with the seal in contact, If it starts, check start and stop button.
@tsikboiteevee6387
@tsikboiteevee6387 4 года назад
interesting content keep it up! #HuertsGamz Channel
@marktonydavis
@marktonydavis 7 лет назад
Did I see a AB power flex 40 along with AB C09 DJ01?
@dougjones4987
@dougjones4987 5 лет назад
Ughh..
@soviethammer
@soviethammer 8 лет назад
Is the incoming control voltage 24VDC?
@youmah25
@youmah25 7 лет назад
yes
@edcrowe6977
@edcrowe6977 6 лет назад
sometimes the control voltage is 120 VAC if a step down transformer is used from the main power. This would all depend on the type of coil voltage used in the main contactor
@tommygurule3496
@tommygurule3496 7 лет назад
I have a question,how do you get a 3phase motor out of Lock Rotar Amp
@edcrowe6977
@edcrowe6977 6 лет назад
if you remove the input voltage to the motor and make sure the motor shaft is free from any other mechanical sources , then the motor rotor should turn free within the motor housing. However, if the motor shaft fails to turn with no voltage applied , then the motor needs to be taken apart and inspected for bad end bell bearings and remove the motor rotor from the field and check for any damages there as well.
@edcrowe6977
@edcrowe6977 6 лет назад
the locked rotor motor test is basically when the shaft of the motor is locked so that it cant move and then the rotor winding's are short circuited and checked that the lower frequency applied and reduced supply voltage matches the full load rated current of the motor
@vincentsanchez9195
@vincentsanchez9195 4 года назад
I understand the incomeing control voltage but what is the incomeing line voltage?
@vincentsanchez9195
@vincentsanchez9195 4 года назад
I ment to ask what is the difference of income line voltage and income control voltage
@josephdupre770
@josephdupre770 4 года назад
@@vincentsanchez9195 Line voltage is coming from the motor control center or substation. Control voltage is on the secondary side of the control transformer and has been stepped down to run the control circuit.
@caroldj.jenkins1843
@caroldj.jenkins1843 4 года назад
Can some one explain what he means by incoming control voltage? Where is the incoming control voltage on the Contactor?
@jasonryan2175
@jasonryan2175 4 года назад
A1 and A2
@garethmurphy8235
@garethmurphy8235 5 лет назад
What are you meaning by "control voltage"? Are u meaning 24VDC from the power supply?
@johnstamper3974
@johnstamper3974 5 лет назад
yep going to a1 and a2
@elevatormechanic
@elevatormechanic 7 лет назад
Why are you checking the motor at the disconnect? According to your print the normally open motor starter will be open. Kinda dumb
@quantumfoam140
@quantumfoam140 6 лет назад
Rubberneck He mentioned in the video that sometimes a disconnect is installed near the motor to provide a convenient point to lock out for safety. In the schematic, this disconnect would appear after the overloads and before the motor.
@mahamoodahammed3169
@mahamoodahammed3169 7 лет назад
تمام صلى علي حبيبك محمد
@juanleonardourena2883
@juanleonardourena2883 3 года назад
Debiste seguir el tema que estaba hablando el dr nieves
@rebelkhot3620
@rebelkhot3620 6 лет назад
Make submarcible motor
@hbknhry
@hbknhry 5 лет назад
Very informative.
@Biginjapan85
@Biginjapan85 9 лет назад
Hey, will checking the resistance between each phase of the motor not give the same resistance, as all of the windings are connected together in the motors terminal box?
@charliec8936
@charliec8936 8 лет назад
+rory johnstone if you check resistance between each phase then yes the resistance should be the same as they are balanced. if they were different then they would be imbalanced and cause the motor to have a problem
@Biginjapan85
@Biginjapan85 8 лет назад
+Charlotte Cottam As i understand the links for star/delta in the terminal box on the motor would have to be disconnected to properly test between phase to phase. As checking phase to phase with the links in will not show the fault due to the three phases being tied together in the terminal box.
@edcrowe6977
@edcrowe6977 6 лет назад
In order to properly checking the motor winding resistance a megometer would be required as well. If any motor winding shows any resistance to ground. the motor field windings would have to be repaired then
@keyworksales6241
@keyworksales6241 5 лет назад
Your meter may pick up small differences, however you should disconnect the motor from the circuit and test the insulation of the windings with a megger or meg-ohm-meter
@jeffgreen7897
@jeffgreen7897 Год назад
You said “never throw a disconnect under load”. Sometimes you have to throw a disconnect under load if there’s an emergency.
@jenmagbojos624
@jenmagbojos624 7 лет назад
i feel like inside the airplane
@pbrown4
@pbrown4 6 лет назад
do 3 phase motors not need an earth? what about neutral?
@quantumfoam140
@quantumfoam140 6 лет назад
Peter Brown They do require an earth ground. In the United States it is usually the green wire as shown in the video when he shows the inside of the disconnect box. There is no neutral wire in a 3 phase motor. Each of the 3 phases is a hot wire.
@edcrowe6977
@edcrowe6977 6 лет назад
no neutral wire is required only a green ground wire
@oscar27ization
@oscar27ization 4 года назад
That disconnect didn’t need a supply side bonding jumper, since the enclosure didn’t seem to have eccentric knock outs
@robertosteen6621
@robertosteen6621 5 лет назад
To check the motor shouldn't you determinate the motor or at least check the termination? I've had instances where the motor shoots good from the cabinet but you open the peckerhead and the phases are melted together. Obviously it would cause the breaker to trip but still from the disconnect you would see the same reading if the phases were not shorted.
@robertosteen6621
@robertosteen6621 5 лет назад
Still an awesome video though!
@lanthonyperdum6430
@lanthonyperdum6430 5 лет назад
Explain in more detail please...I’m thinking you are speaking of disconnecting the 3 power line leads and checking the motor leads in between windings is that correct ???
@bombebomb
@bombebomb 5 лет назад
0:32 the truth
@akhileshkr03
@akhileshkr03 8 лет назад
what is PPE ?pls explen it.
@soviethammer
@soviethammer 8 лет назад
Personal Protective Equipment. (Safety Gear)
@akhileshkr03
@akhileshkr03 8 лет назад
+Rand Mitch, thank yous sir
@charliewilley5004
@charliewilley5004 6 лет назад
Your link to printable version doesn't work.
@jeradLiberty
@jeradLiberty 5 лет назад
Most 3 phase systems in the us are 480v???? Hu?
@robertosteen6621
@robertosteen6621 5 лет назад
Its true
@tedlahm5740
@tedlahm5740 Год назад
@@robertosteen6621 Ungrounded Delta?
@nathanmueller8994
@nathanmueller8994 6 лет назад
No fuses & no transfer switch....
@3cressidas
@3cressidas 6 лет назад
Your link to printable doesn't work.
@TheCommonSenseProfessor
@TheCommonSenseProfessor 5 лет назад
Your written version and simple print link is bad.
@circuit-maker7971
@circuit-maker7971 8 лет назад
Print link = 404
@bigmedge
@bigmedge 5 лет назад
Uhh
@gregorybeard5294
@gregorybeard5294 8 лет назад
NEEDEED
@hg2.
@hg2. 5 лет назад
In an absolute sense, this is a good effort, but this is not a good "how to" video: the narration is too fast, it assumes extensive knowledge and experience by the listener. This is for experienced people only, and if they are already experienced, they don't need the instruction. Improvement can start by practicing the narration with no slurred/drop-offs toward the end of the sentence or idea. (Slurred end-of-sentence drop-offs alienate the listener because it shows an attitude that says "this stuff is so basic and elementary, and I'm bored with having to explain it to you.... " The narration should also have pauses between sentences and paragraphs, as opposed to the aggressive, pace here, which eventually sounds like an advertisement for the company, as opposed to an actual how-to video.
@dallas5374
@dallas5374 4 года назад
hg2 you should make a video showing everyone how it’s done....duh!!!!
@russelsprout2155
@russelsprout2155 Год назад
How to videos shouldn't exist for electrical stuff. It's too dangerous. Only licenced electricians should be messing with this stuff
@hg2.
@hg2. Год назад
@@russelsprout2155 ^^ Union protectionist, right?
@hg2.
@hg2. Год назад
@@dallas5374 I'll look for a competitor that does it better.
@russelsprout2155
@russelsprout2155 Год назад
@@hg2. well when someone you know dies because they're trying to be a jack of all trades then you'll understand
@josephsmith6075
@josephsmith6075 Год назад
Good vid. But you talk too fast 😕
@travissmith383
@travissmith383 Месяц назад
video could have been much better. Couldn't fully see what you were doing
@koarivera9151
@koarivera9151 4 года назад
Talks way too fast wow
@PBS-nm1uu
@PBS-nm1uu 6 лет назад
to fast video is terrible
@ronancahill2487
@ronancahill2487 4 года назад
Slow down. You talk too fast. I could not keep up
@rjsmith1630
@rjsmith1630 4 месяца назад
This is incorrect!! If your resistance phase to phase is low means you phase insolation is weaker and your about to phase out!
Далее
Troubleshooting a PLC Output
7:25
Просмотров 33 тыс.
Վարդավառը Գյումրիում
00:15
Просмотров 103 тыс.
Electrical Wire Color Coding Used By Electricians
16:14
Checking Windings in a 9 Lead 3 Phase Motor
7:55
Просмотров 288 тыс.
Troubleshooting 3 phase motors
11:45
Просмотров 4,3 тыс.
HOW TO TEST 3 Phase Motors PROPERLY
39:04
Просмотров 19 тыс.
Motor Control 101
15:59
Просмотров 1,9 млн
3 phase motor test
10:58
Просмотров 1,6 млн
How Auxiliary Power Units Work | Part 2 : Power
8:24