How to clean a plate heat exchanger! 

Central Heatking
Подписаться 5 тыс.
Просмотров 4,4 тыс.
50% 1

In this episode we have a call to intermittent hot water on a combi boiler,
Boiler ignites then shuts down and repeats the process, it should modulate the flame down and then up again as it reaches temperature.
So we opt to clean out the plate heat exchanger, I show the full process of this. What would you have done… cleaned or replaced? #tools
Shout out to ​⁠‪@bluebulldog_uk‬ on this one #plumber
A day in the Life of a jobbing plumber! Thank you for your continued support!
Most tools featured are here…
amzn.to/3jPFOjG
#plumber #tools #tradesman #leaks #apprentice #business #selfemployed #contentcreator #instagram #tiktok #apprentice #leaks #business

Хобби

Опубликовано:

 

11 сен 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 91   
@Heatking
@Heatking 10 месяцев назад
Giveaway at 2k! Be sure to subscribe and hit a the like on the video ❤❤❤
@AllenHart999
@AllenHart999 9 месяцев назад
not long now
@Heatking
@Heatking 9 месяцев назад
@@AllenHart999 cheers buddy. Thank you for your help!
@AllenHart999
@AllenHart999 9 месяцев назад
you haven’t got any tags on this video@@Heatking
@AllenHart999
@AllenHart999 9 месяцев назад
seo score is 5 out of 100 @@Heatking
@user-li8gr8ur8l
@user-li8gr8ur8l 3 месяца назад
Another top job Dan. It is a shame the obstacles in the way of the plate make you have to cut pipe work or remove the pump assembly ❤
@Heatking
@Heatking 3 месяца назад
Cheers mate. Yeh it is a shame, seen as other manufacturers make it so you don’t have to take anything out the way to replace it!
@AllenHart999
@AllenHart999 9 месяцев назад
Good video. Worcester Bosch Plate Heat Exchangers are not the easiest repair on them old ones. The new Worcester Bosch 4000 is amazing though. Really good video for Trainee gas engineers. Thanks.
@Heatking
@Heatking 9 месяцев назад
Thank you Allen. The 4000 plate removal was so simple at your house, litterally only needed a Philips screwdriver to do the job 😂
@AllenHart999
@AllenHart999 9 месяцев назад
you mean the worcester bosch 4000 lol @@Heatking
@AllenHart999
@AllenHart999 9 месяцев назад
or the worcester bosch 4000 combi boiler heat exchanger that gets blocked on dirty central heating systems@@Heatking
@Heatking
@Heatking 9 месяцев назад
@@AllenHart999 oh yes. Best than that ‘Navien boiler’ 😂😂
@AllenHart999
@AllenHart999 9 месяцев назад
do you mean the worcester bosch boiler is easier to repair a blocked plate heat exchanger than a Navien gas combi boiler @@Heatking
@brendanfisher2528
@brendanfisher2528 10 месяцев назад
If you ever have the worcester with the vent tube on top of the kebab heat exchanger.. what I do it drain the boiler at the point by the diverter. Then put the vent tube into a bottle of system cleaner, open the vent tube and syphon all the cleaner into the boiler..... pressurise the boiler, isolate flow and return, and run the hot tap on low temp and it will flush just the plate out.. Once it's been ran for a while until temps are stable on high... flush cleaner out and open flow and return valves... always works for me..
@Heatking
@Heatking 10 месяцев назад
I knew about that strategy mate but for some reason didn’t associate it with the plate, I just assumed it cleaned out the main hex.. what a donut haha. Thanks for the advice Brendan! 🫶🏽
@douglaughton7626
@douglaughton7626 Месяц назад
I have always cut away the hot or push it out of the way. I fit new plate as well. Nasty stuff drain acid. Top video.👍
@Heatking
@Heatking Месяц назад
Yeh it is nasty stuff! I hate cleaning them mate, but yeh hot or cold out the way definitely helps 💪🏼
@mcDarkD
@mcDarkD 18 дней назад
finding drain acid hard to get now. idiot students round here are forever letting the plastic covers from razors go down the plughole. bit of hair and that acid problem gone..... it is nasty stuff used in the wrong place i agree. but it had its uses.
@trevorjarvis3021
@trevorjarvis3021 10 месяцев назад
Great video - learning all the time.😊
@Heatking
@Heatking 10 месяцев назад
So am I mate 😂😂😂 cheers 🫶🏽
@Paul_YHPS_uk
@Paul_YHPS_uk 10 месяцев назад
Good content. Thanks again mate.
@Heatking
@Heatking 10 месяцев назад
Thank you Paul. Anytime 🫶🏽
@AllenHart999
@AllenHart999 9 месяцев назад
plumber cleaning boiler a fault on a worcester bosch gas boiler with no hot water, gas engineer and plumbing repair. gas man loves worcester worcester repair gas engineer gas safe boiler breakdown worcester bosch greenstar 30i erp plate heat exchanger plate heat exchanger blocked heat exchanger heat exchanger repair worcester boiler
@martinthornley237
@martinthornley237 Месяц назад
Listen to Alan he's the daddy of youtube!! Love your work guys keep up the good contents both of you
@capraniplumbingandheating
@capraniplumbingandheating 10 месяцев назад
Mint video Dan, I use a acid called Jebsol lethal stuff mate but does the job. All honestly In 16years I’ve never swapped a plate always cleaned Keep at it Hustler 👊🔥
@Heatking
@Heatking 10 месяцев назад
Cheers Nath, I’ll check that stuff out, where do you get it from please? 🫶🏽thanks for the support mate.
@johnward5006
@johnward5006 10 месяцев назад
All plates can be cleaned using similar chemicals,they're mostly made by specialist companys. A tip I was given was measure hot outlet and return temp and expect ideally 1c diff. Yes advise power flush and filter if not fitted. Top tip 2litres of the best known inhibitors is the ideal on average property, it will bring the ph closer to to neutral ph.
@Heatking
@Heatking 10 месяцев назад
Cheers John! I’ll use this tip going forward! Thank you.
@cputilitysolutions
@cputilitysolutions 10 месяцев назад
Love a woosta plate job! Great vid Dan 👊🏾
@Heatking
@Heatking 10 месяцев назад
Thanks mate 🫶🏽 cheers for the support 🫶🏽
@AllenHart999
@AllenHart999 9 месяцев назад
Them Worcester Bosch Plate heat exchangers are so easy lol.
@paulj9022
@paulj9022 10 месяцев назад
Well done 😊
@Heatking
@Heatking 10 месяцев назад
Cheers Paul 🫶🏽
@paulj9022
@paulj9022 10 месяцев назад
@@Heatking 😀 ❤️
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
I used to work for Worcester and in my opinion the 25. & 30i ERP is the best model Worcester ever made. The easiest way to test a plate blockage is to measure the flow temp by the display temp and then measure the hot water outlet temperature either at the tap or pipe underneath. The temperature difference should be 10 degrees max. So if tap reading 50, boiler should display 60. If more than this like 20 degrees etc, plate is blocked. 👍
@Heatking
@Heatking 10 месяцев назад
Thank you Kev, would you say this method above only works on Worcesters or all plates? I was always taught to measure the flow and return difference in the boiler like I’ve done on this.
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
All boilers are different. Manufacturer specific. This as far as know only works for Worcester. Ideal you would test return temp and hot water outlet temp, less than 5c is good, 10 or above etc would be blocked. I’ve done a video on the ideal on Allen hart channel ages ago.
@Heatking
@Heatking 10 месяцев назад
@@kevincranfield5235 I’ll try find it mate and take a look! Thank you.
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
m.ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-W5OkuLJ4NLY.html
@MrVacuumCleaner
@MrVacuumCleaner 10 месяцев назад
I’m still keen to know what that extra tap on the bath is for……😂
@sultanmahmood1398
@sultanmahmood1398 10 месяцев назад
Another way and tip I do to remove the plate from Worcester’s is taking off the left hand manifold and the pipe that links from the hot water out and it comes out soo much easier
@Heatking
@Heatking 10 месяцев назад
Great tip that mate, really appreciate the advice! 🫶🏽
@MrVictorvolvo
@MrVictorvolvo 10 месяцев назад
Mate, just come across your videos, as a Gas engineer they're very informative to watch. As we like our tools, that little gadget you got for the silicon grease where can I get one, looks mint!?
@Heatking
@Heatking 10 месяцев назад
Thank you for the kind words mate! And if you search ‘mini grease gun’ on Amazon you’ll find them 🫶🏽
@MrVictorvolvo
@MrVictorvolvo 10 месяцев назад
Thank you, much better then carrying a tube of lube which almost always splits at some point!
@Heatking
@Heatking 10 месяцев назад
@@MrVictorvolvo yeh you’re right, I find you use a lot more out a tube aswel. And it’s not the cheapest of stuff!
@Heatking
@Heatking 10 месяцев назад
@@MrVictorvolvo yeh you’re right, I find you use a lot more out a tube aswel. And it’s not the cheapest of stuff!
@simonsalter8300
@simonsalter8300 10 месяцев назад
Hot and Cold taps in the basin on the wrong way round!!
@Heatking
@Heatking 10 месяцев назад
Yep I noticed that 😂
@ChelseaFC190512
@ChelseaFC190512 10 месяцев назад
Any more install vids coming up mate?
@Heatking
@Heatking 10 месяцев назад
I certainly bloody hope so mate. I could do with boiler boiler jobs haha. But yeh we got one first week of oct 🫶🏽
@macpatel7810
@macpatel7810 10 месяцев назад
Wooster Wooster. Why do you love them so much Dan. They really dont love you. 😂. Good content pal.. As others have said, i think cutting the hot pipe is probably a bit easier. But as you stated baxi plates vertually just slide off on their own. Lol
@Heatking
@Heatking 10 месяцев назад
Yeh hot I think I’ll do next time.. always learning.. haha. It’s a love hate relationship we have mate 😂😂😂 Cheers Mac 🫶🏽
@macpatel7810
@macpatel7810 10 месяцев назад
@@Heatking lol. You love them but they hate you 😭😂
@Heatking
@Heatking 10 месяцев назад
@@macpatel7810 yep that’s exactly it haha
@wolvolad25
@wolvolad25 10 месяцев назад
Im sure its a staple of the plumbing community 6:05 😂😂
@Heatking
@Heatking 10 месяцев назад
😂😂😂😂
@wolvolad25
@wolvolad25 10 месяцев назад
@@Heatking but seriously another interesting video thanks
@Heatking
@Heatking 10 месяцев назад
@@wolvolad25 thank you mate 🫶🏽🫶🏽🫶🏽
@Handymandavid
@Handymandavid 10 месяцев назад
Hi, thanks for always great videos, just a simple question, have you listened to your videos? The music is too laud and when using headset it's going to make you deaf.
@Heatking
@Heatking 10 месяцев назад
Yes I edit the videos so I do listen to them. Do you mean the intro music, I think that’s the only music I’ve had on for a while. If so, I’ll look to try and turn that down mate . Thank you. 🫶🏽
@raul835
@raul835 10 месяцев назад
Easiest way on these is to disconnect expansion vessel pipe and take pump out.. plate will come out.
@Heatking
@Heatking 10 месяцев назад
Cheers mate, seems I did it the hard way 😩
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
Another tip to get the plate out. Remove the hot pipe connection from the boiler and the plate wil drop out. I think Geoff needs has made a video on how to do it. Dead easy
@Heatking
@Heatking 10 месяцев назад
Yeh the cold didn’t really do me any favours on this one 😂😂
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
m.ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-QcCc3mmhKWo.html&pp=ygUZR2VvZmYgbmVlZHMgcGxhdGUgaGVhdCBleA%3D%3D
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
Next time you do one, try that. Dead easy and hydraulics are very similar.
@Heatking
@Heatking 10 месяцев назад
@@kevincranfield5235 cheers Kev!
@kevincranfield5235
@kevincranfield5235 10 месяцев назад
I think your videos are great by the way. 👍 forgot to mention that.
@connerhuetson3581
@connerhuetson3581 10 месяцев назад
What’s the silicone grease dispenser thing called? 😅 cheers
@Heatking
@Heatking 10 месяцев назад
Amazon ‘mini grease gun’ matey 🫶🏽🫶🏽
@connerhuetson3581
@connerhuetson3581 10 месяцев назад
@@Heatking life saver, cheers mate
@Heatking
@Heatking 10 месяцев назад
@@connerhuetson3581 anytime mate
@Purebeltersteve
@Purebeltersteve 10 месяцев назад
Just be careful on worcesters, youve got to realise that boiler can only produce approx 11l per min, if your opening up that hot tap fully at start, it looked alot more than that and the heat transfer wont happen and cause the boiler to overheat. Its one of the biggest callouts i get and when i tell customer to turn hot tap open a quarter of way it will give the heat transfer the best chance and pretty much make boiler stay on. Also worth noting on those 30i erps, the diverter motor/paddle tend to get weak and put heat down the flow due to blocked plates. In my opinion, there one of the worst theyve made, cdi range is so much better. Good video though mate. I would never use acid, just replace. Ive seen blokes getting some nasty burns.
@Purebeltersteve
@Purebeltersteve 10 месяцев назад
Also for those plates, but a black rubble bags, the ones you get from screwfix and it will catch pretty much all the water.
@Heatking
@Heatking 10 месяцев назад
Thanks Steven, good call on opening the tap up full at the start. I’ll not do that in the future. Yeh I’ve heard about the paddles. I’m Not sure if you could see but I kept putting my hand on the flow pipe to check it wasn’t seeping down there, thanks for the advice mate 🫶🏽
@Heatking
@Heatking 10 месяцев назад
Another good idea!! 😂🫶🏽🫶🏽
@brianmayne6513
@brianmayne6513 10 месяцев назад
Do you like vaillant eco tex
@Heatking
@Heatking 10 месяцев назад
I’m not a fan of Vaillants to be honest, I find them expensive to buy and expensive to repair, but they are reliable.
@AllenHart999
@AllenHart999 9 месяцев назад
do you like navien combi boilers i heard the plate heat exchangers are easy on them, better than the worcester bosch lol @@Heatking
@Heatking
@Heatking 9 месяцев назад
@@AllenHart999 I don’t know where you heard that. The navien combi boiler I worked on, the plate heat exchanger, required the expansion vessel to be removed first! Worcester Bosch boilers and baxis boilers are much easier for a gas safe engineer to work on 😂
@paulbooth1335
@paulbooth1335 10 месяцев назад
Jesus, that boiler looks like a bag of crap to work on. Why people like Worcesters I'll never know, hateful things.
@Heatking
@Heatking 10 месяцев назад
Haha they’re not normally too bad mostly. I probably Made it look harder than it needed to be 😂😂😂
@AllenHart999
@AllenHart999 9 месяцев назад
Gas engineers and plumbers have to repair any gas boilers they get called to. The worcester bosch is easier than some.
Далее
HOW TO CLEAN - Plate Heat Exchanger - What’s Inside
18:09
I nearly miss diagnose a boiler fault 😬#plumber
18:44
What Am I Doing Wrong?! #plumber
21:13
Просмотров 2,6 тыс.
Worcester Bosch 30i heat exchanger replacement
15:37
Просмотров 4,4 тыс.
WHAT IS THAT SMELL?? #plumber
16:14
Просмотров 2,8 тыс.
One moment can change your life ✨🔄
0:32
Просмотров 33 млн
Отнимают ребенка ч.7
0:55
Просмотров 3,6 млн
Amazing
0:37
Просмотров 36 млн