How To Diagnose Daikin VRV EEV Powerhead 

Mechanical Pros
Подписаться 5 тыс.
Просмотров 4 тыс.
50% 1

How to diagnose and maintain Daikin VRV expansion valve powerheads.

Хобби

Опубликовано:

 

14 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 19   
@pyroguy3
@pyroguy3 Год назад
What I have found to work well to get the snap style EEV's off is to let a little squirt of Kroil soak down through the gap while I finish getting panels off for inspection. What I've found is that if you can get that driver to twist free at all, it will eventually come off with a little persuasion. After the cleaning is done I'll wipe everything down with a rag and then coat the driver's surface with a fingertip-full of 100% silicone plumbers grease. Units I have done this too have looked pretty much untouched when I check them out on the next years inspection. Thanks for the informative content!
@jasonjohnsonHVAC
@jasonjohnsonHVAC Год назад
Love this channel....to bad i found it only a few months ago...great content and education
@gaillaffer7579
@gaillaffer7579 Год назад
If no 21 mode is used the bolt on ones must have the pin retracted into the body before reinstalling. (Factory new replacement parts are already.) You do this by temporarily switching the blue and yellow wires and turning the unit on for no more than 15 seconds x 3 times on and off. This reverse polarization winds the pin In. If you do no do this you run the risk of the extended motorized pin slipping off the valve seat and jamming down the side possibly puncturing the metal bellows. Make sure to put wires back in proper place when completing job
@musakavalci9470
@musakavalci9470 Год назад
Great content 👌🏻👏
@taqmeemalam8852
@taqmeemalam8852 Год назад
@@MechanicalPros oh nice electronic Xpensan volvo & eev
@sameerpremlall8124
@sameerpremlall8124 2 года назад
Very informative 👏 thanks for the content
@sameerpremlall8124
@sameerpremlall8124 2 года назад
@@MechanicalPros can you guys do a video on service checker data analysis please. What to look for, maybe scenarios like over charge, under charged, poor oil return. That would be great if it is possible. Thank you for your efforts
@sameerpremlall8124
@sameerpremlall8124 Год назад
@@MechanicalPros thanks guys. I can't wait
@HungPham-ff2wj
@HungPham-ff2wj 2 месяца назад
Thank anh.anh co the cho em quyen sach do duoc không
@sengguanwong3905
@sengguanwong3905 5 месяцев назад
I have questions on eev. I took out the eev bolt type. I found dirty and i tried to clean it out the black greese or oily stuff at the head. But it cant be screwed it back the EEV due to the head is came out. How can i make the pin or head go inside so that i can screw it back?
@malteselexy123
@malteselexy123 11 месяцев назад
I have an eev on a casette that wownt budge even with spray lubricant. Any ideas how to remove it ? Pls
@MechanicalPros
@MechanicalPros 11 месяцев назад
That's a tough one. Soak it and give it time and pressure. Don't force it until you're ready to replace it.
@architectelevator
@architectelevator Год назад
Thanks for the fantastic videos! For an VRV indoor unit, you mention looking at the evaporator thermistor readings to diagnose a failing EEV. Would a normal liquid side temp reading and an almost room temp gas side reading (plus lack of cooling) hint at a failing EEV that's refusing to open (assuming airflow is all fine)? EEV coil resistance is OK, so is there any additional test that can isolate the EEV as the culprit over other issues?
@architectelevator
@architectelevator Год назад
​@@MechanicalPros Thanks for the reply! You guys are awesome! Sadly the "Indoor unit status" on the wired remote doesn't show anything for this unit (it's an older VRV III indoor unit, not sure that's the reason), so I can't see the EEV pulse count. Hadn't seen EEV Mate - looks neat. I tested again with another unit running and the liquid-side temp drops quickly to 0-5 deg (Celsius). Where it''s get wonky is after that - gas side drops slowly but then shows odd values like 5 liquid / 5 gas before jumping instantly to 18 deg. Sometimes I lower on gas side than liquid side. I am now suspecting the gas-side thermistor. Every time a new detective story!
@architectelevator
@architectelevator Год назад
@@MechanicalPros The gas-side sensor was certainly dreaming values up and the EEV looked and measured resistance alright but seems to have worn out (it's a bolt-on, which I believe has gears inside). Much better now with new thermistor (can those be any harder to reach?) and EEV. EEV opens to 800-900 clicks to maintain ~ 6*C superheat. According to the Daikin folks, EEV motors and thermistors fail to the point where on any fan coil unit > 6 years old they just replace them all before spending extra time diagnosing... thanks again for the advice!
@nategadow4482
@nategadow4482 Год назад
Can you post a link to those meter leads?
@shannonedwards1872
@shannonedwards1872 2 года назад
How does rust get into the EEV and is there any thing we can do to prevent that problem?
@Louisyongcool2328
@Louisyongcool2328 Год назад
Hi I have a problem with a Daikin vrv today, cooling mode is fine but when it on heating mode it come into a vacuum is this the EEV problem ? Thanks
@Louisyongcool2328
@Louisyongcool2328 Год назад
@@MechanicalPros my service checker can’t connect it don’t know why. But is a heat pump I put on cooling is fine, but when I put on heating it become a vacuum
Далее
How to Diagnose Daikin VRV IV Condenser Drive Fans
5:56
EEV Valves and Power Heads
8:01
Просмотров 10 тыс.
Редакция. News: 125-я неделя
48:25
Просмотров 1,5 млн
Testing an EEV
3:15
Просмотров 29 тыс.
The 3 Pillars of Daikin Service Checker Analysis
20:55
HOW TO TEST DAIKIN EEV COIL.
12:23
Просмотров 13 тыс.
Checking the Magnetic Pulse control of an EEV
1:54
Просмотров 35 тыс.
КУАР КОД✍️
0:11
Просмотров 1,8 млн