20 year Instrument Tech here. Problem: New Fisher 6200 on new Fisher rotary valve with 24VDC Delta V supply (AO card), shield landed at fuse block. Emerson AMS TREX & 475 "NO COMMUNICATION" & "NO VOLTAGE DETECTED". Reading 6.3VDC Fluke 789. Loop power disconnected at DVC = 24VDC with 789. Check wire resistance, disconnected at DVC and Delta V fuse: + to - = OL, + to shield = OL, - to shield = OL. Homerun = GOOD. Check loop resistance from DVC to Delta v card, disconnected at DVC: + to shield = OL, + to - = 25M, - to shield = 92K. To verify DVC, connected another new DVC to DeltaV at valve, SAME THING, "NO VOLTAGE DETECTED", "NO COMMUNICATION". End to end homerun loop check = "OL" on all ckts. Valve strokes through DVC using 789 4-20mA and TREX supplied power, but NO COMMS & NO VOLTAGE DETECTED with Delta V 24VDC loop power. WTF?!