Good job sir, the only things you try to avoid is telling the person asking you are just an electrician, always assumed that either they are trying to tricked you if you know the answer or just explained to them without looking down the person trade level. Sa trabaho bilang HVAC/R we are not allowed to do load calculations because we have our own electricians and that is against the NEC, after the disconnect we do all the sizing of the wirings base on the load calculations. Keep your ego as you are above the level from your students, some questions may be sounds like they are going to challenge your knowledge, the simplest way is we have to answer base on the questions they asked. If it’s just a general question as you said previously then have to answer the general ways. If you can give them more answer more than what they are asking for, its better, but telling you are just an electricians is below the belt. Teachers don’t go down to the student level, stay as educator and not get to be educated. Anyway, your presentations are far more advanced and concise that is the what we wanna see your good presentation sir. From Leyte Philippines.
...respect din dapat ng ekectrician sa engineer eh kung pabalahura yung pagtanung ng electrician at minamaliit yung engineer ng sabihin ba mali yung engineer outright eh dapat din sagutin ng pabalahura yung ekectrician na feeling alam ang lahat..
Pag nasagot naman natin ito ng tama, base sa computation, na mahinahon at walang pag aalipusta, mas masakit na sampal ito sa kanyang mukha ,na mayroon pa pala siyang dapat pag aralan, kaya lang pag natuto ng husto ang electrcianna ito ay higit itong bastos at mayabang.....
Sorry po sa tinaman !base in actual at computation po sana para po yung computation po sana kahit actual ng kahit sino electrician man po o engineer or pee po e doon palang po sa sa computation kahit actual basta tama po compute sa actual sure na di magugulhan po lahat ng mga electrician man po o hindi!renerespito ko naman po kayo na gusto ninyo lang po sagutin po yung nag tanong po sa inyo!wag naman po kayong magalit sa sinabi ko gusto ko po kasi na malaman talaga kung match po yung computation doon sa actual at theory ninyo po na pinagbasihan po ng pinagkunan ninyo po ng computation?
Maraming salamat sir Ang linaw Ng paliwanag mo sir,,,, salamat sa Dios nauso Ang online teaching 🙏🙏🙏 Hindi parin KC Ako perfect when it comes to electrical theories 👌👍
Salamat sa pagshare ng knowledge mo. I think, simpleng pagtatanong lang ang sinabi ni Arlan, gusto lang nya matuto at hindi naman nya kinokontra ang kaalaman mo. ✌️
Salamat po sa very informative video tutorials ninyo. Dagdag kaalaman po habang pinapanood ko ang video ninyo. Sending my full support po sa inyo mula po dito sa Canada 🇨🇦.
Sir, napakaliwag ang explanenation mo dito sa lecture mo.sana marami kapang edea mabigay sa katulad namin electrician. Magaling kang mag paliwag sir. Salamat sayo ng marami
New subs. Po sir! Galing nyo po sa pagtuturo ang linaw2x … maraming salamat po, dag2x kaalaman po!. Firs time ko kasi mag electrical wiring sa 2 story na bahay.. im not electrician, automotive 2 yrs course lng po ntapos ko! But now im doing construction worker, so sa youtube lng ako kumukuha ng ideas..at ngayong araw nkilala ko po kayo masaya po dahil napakahusay nyo po magturo!:) I salute you po! Godbless you always!
Sa load compution ang ginagamit ko sa name plate rating ng motor or sa PEC table na 1hp= 8amp., 1.5hp=10amp and 2hp = 12amp + 25% D. F. for single phase and sq. rt. of 3 para sa 3 phase.
Salamat sa pagtuturo mo Sir, Ang galing mong magpaliwanag, building wiring electricity ako, pero kulang pa po ako sa knowledge kaya subscriber mo na ako ngayon
Pls dont look down the profession as an electrician, di man kinokontra ang kaalaman mo kundi nagtatanong lng para sa karagdagang kaalaman. Thank you sir sa kaalaman
Okay nakasunod tayo jn ganyan din ako sayo idol engineer tama din pala Yung compute ko salamat idol kahit papano my basihan na ako na tama pala ang compute ko aabangan kupa mga susunod mong upload para pag mag xsam ako ng RME pumasa na ako
Sir good evening po. Sana po sa next video nyo ay ituro nyo naman yung tamang computation ng welding machine sa load schedule natin. Hindi po malaman ng mga kasama ko yung tamang rating in terms of watts or amperes ng isang typical na welding machine.
Comment lang po, dapat kasi sa load schedule ay dapat Volt Amperes (VA) at hindi watts ang ginagamit.. Yang Watts kasi ay kalimitan lang ginagamit if ang mgprepare ng load sked ay mga Architect laang, pero for us REE or Registered Elect'l Engrs. dapat talaga naka VA.
sana maging maingat sa pananalita lalo, wag yong makakasakit ng damdamin,wag gagamit ng salitang,isa ka lng ganito marunong ka pa skin,magtulungan tayo wag magpataasan ng ihi,pare pareho bagsak niyan sa lupa,mag galangan tayo,sa poem na DESIDERATA,meron sinabi,even the dull ang the poor they too have their own story,bawat isa meron kwento d alam ng isat isa,kaya pakinggan natin,avoid hurting comment,may kasabihan din sampalin mo na lng ako,wag mo lng ako sabihan ng masasama,ang latay nawawala,ngunit ang boses lagi rw naaalala,ngunit alin man sa dalawa,wag magtatanim ng galit,magtanim ng kamote at makakain pa at mauutot ka pa at pang alis ng kabag hehehe salamat po
Engr respeto naman po sa electrician. Pati di rin nyo po naipaliwanag ng maigi kung san nanggaling ang 10amps na galing sa PEC. I am talking about behind the scene kung paano nakuha ang 10amps na equivalent sa 1.5Hp accdg sa PEC. Dahil po ba pag start ng motor eh sobrang taas ng current kumpara sa rated current ng motor? Kaya disregard na 4.86Amps na pwede proteksyunan ng 10Amps dahil lagi magtitrip ang breaker at worse case ay sunog sa kable.
1. SIr Matanong lang po, ano ba ang Resistance nang Multimeter or Tester bago mag measure nang Resistance, 2. Saka ilang Amperes ba ang pwede mag Kill nang isang tao? Saka paki show lang nang Reference kung myron man. 3. At saka Sa Circuit Brake ano ba ang ibig sabihin nang Duty Cycle, and Time Response To Trip. Thanks po.
Good explanation ..however dapat may basis explanation ka kung bakit ang ginamit na reference ay yung naka specify sa PEC ..Yes this is correct for motor load..You should explain why. To understand fully the ampere selection...You should tell the motor load charateristic during starting and at during stable load of the motor ...I hope you understand what I mean. Thank you.
Dahil kayo po ang nakakaalam kahit na general or specific ang tanong ipaliwanag niyo sa madaling pamamaraan at madaling maintindihan ng nag tanong at ng mga manonood. Salamat po
Sir tama po yung ginawa sa isang unit ng condo dto sa pinagtratrabahuan ko po na ginamit branch circuit breaker at 30 A sa 10 pcs.na convinience outlet 2 gang
Sir sa motor meron tayong tinatawag na 100% load 80% load. At no load siguro tama yong 1 hp = 3.2 a. Kapag may load nayan tataas ang ampere. Yong limit na sinasabi sa electrical code ay yong size ng alambre na gagamitin mo kaya yong 8 amp. Na nababanggit dyan ay limit para hindi magastos sa alambre. Ang motor nagbabago ang amp. Depende sa load.
Ang tanong cguro ay; saan nggaling yung data ng pec? Ano ang basis? Ksi kung ecompare sa formula malayo, almost doble. Ano ang knonsider doon? Pra lng maintindhan.
Actually in practice those tables of Motor HP Current Rating are in Phil Electrical Code & others like IEC, BS etch std tables. They are computed according to the ambient temperatures, the effcy, pf, servive factor etch and are in the Namaplate of the motors. I found those values in actual experience true, almost equal to the std tables.
1.5hp - 1119watts x 230volts = 4.86amper for running current 4.86amper x 2.5 full load current = 12amper for staring current in actual po yan kaya po yung 10amper sa pec tama naman
Maraming salamat po sir sa libring knowledge na ibinahagi mo sa amin, marami Po kaming natutunan. Ang Tanong ko Po sir, ano or cnu Po ba sundin natin lagi sa kanila Yong Phil. Electrical code or Yong Phil. Distribution code?. Maraming salamat po ulit
Sir yong sinabi mo pec ay load computation para sa power supply na ilalagay mo na size of wire preparation. Ang question po ni arlan ay watts for 1hp not for load preparation ng power supply at load preparation kelangan pa po ba bang sabihin nyo na sya ay electrician lang at kayo ay engeneer. Sharing lang po ng kaalaman wag po sana nating sukatin ang educational background ng bawat isa dahil lahat tayo may kanya kanyang expertis. Tulungan nalang po tayo kung pwede po
Yun pala papasukan ng Phil electrical code eh dehins nman alam ng ordinaire electrician yan. Nag base ang electcian sa basic formula regardless of any effing code. Pero prang nalait ang electrician ahh.
para sakin hindi yon panlalait. in fact sinabi pa nga nya na kanya kanya tayo ng trabaho. di nyo kasi nakuha ang sinasabi nya base sa halimbawa na isang electrician ay kumbaga kinikwestyon ang computation nya bilang isang engineer. real talk lang, madami din talagang ganyan sa trabaho di lang mga electrician na akala mo mas marunong pa sa engineer sa lahat ng bagay.
@@ericcruz3149 kaya nga yung electrician hindi gumagawa ng plano. Electrical plan yan kaya kailangan mo ng standards para kung meron mangyari hindi ka kakasuhan ng bumbero at insurance company.
Sir, avoid the words "ka lang "or electrian ka lang. They ask, they want to learn. We have electrical code to follow. And we have Code of ethics to be reminded of our profession.
May kulang lang sa explanation po kaya nag tataka yung ibang electrician po na iba,tama po yang NASA pec kaya ganyan ang amper sa 1.5hp - 10amper actual ko sa starting current po nung actual ko staring current ng ACU na 1.5hp umabot ng 12amper pa baba tapos ng naka buwelo na na nag running na NASA 4.86 amper nalang po talaga
Wrong choice of word. Wag naman ganun na electrician ka lang. Mas maganda pa rin maging ma ingat sa mga salitang ginagamit ng hindi makasakit ng kapwa tao. God bless po