Is it just me or is Trane symbio turning on the wrong compressor? simple fix on this one. 

HVAC Tool Porn!
Подписаться 459
Просмотров 1,9 тыс.
50% 1

settings were to have a discharge temp sensor disabled that function and jumped y1 and y2 to get both compressors running at the same time...

Опубликовано:

 

11 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 21   
@joshuaricks7730
@joshuaricks7730 15 дней назад
Cool 1 is NOT the same as compressor 1. Compressor 2 is the smaller of the two compressors. That will always be the first on last off. This is stated in the manual a couple times. The contactor failure faults you are having is because you have Y1 and Y2 jumped out. If the aux switch makes without a call it thinks the contactor is welded.
@Millertime1717
@Millertime1717 21 день назад
I agree it's not what we're use too but y1 energizes compressor 2. It's gonna take some getting use too.
@lccerrillo
@lccerrillo 2 месяца назад
Just investigate one with that proving lockout alarm with tandem circuit, it was overcharged
@scottsnider3511
@scottsnider3511 3 месяца назад
I have the same issue on a 7.5ton proving switch 1st stage issue, and tech supports no help. I replaced the contactor and aux without resolution. Did you find a solution?
@hvactoolporn188
@hvactoolporn188 3 месяца назад
We replaced contactor and micro switch and 2 days later ordered a Dainkin unit. We are experimenting with gutting controller on a few units but have not made a final decision to what methods we will use in the future....
@Kdavis8377
@Kdavis8377 2 месяца назад
Bottom contractor is actually circuit #1. Schematic is labeled wrong. Small compressor is 1st stage. Don’t ask me how I know. Had this exact issue and scratched my head for awhile. Check incoming voltage. Trane taps all their transformers for 240v. Had to tap the transformers for 208v. Haven’t had a single trip since. My control voltage went from 23.2v to 27v. Tranes are super sensitive to anything below 24v
@hvactoolporn188
@hvactoolporn188 2 месяца назад
Yeah we replaced the switch and have not been back..
@kylewhite291
@kylewhite291 2 месяца назад
Anybody having issues with these units not dehumidifying in 1st stage cooling? 33% cooling capacity and 66% fan speed. 50+ degree saturated suction temperature not below RAT dew point. I’ve lowered the “max fan speed” as a temporary fix but then when unit runs 100% cooling capacity it like 230cfm/ton.
@alessichris07
@alessichris07 27 дней назад
Circuit 2 is stage 1 cooling, the smaller compressor. I've seen the proving error, caused by discharge temp sensor.
@kratosdgo
@kratosdgo 2 дня назад
I got same issues on 10 ton unit trane symbol is pain in the butt
@hotcoolheatingcooling3850
@hotcoolheatingcooling3850 28 дней назад
Same problem I have compressor number 2 start first
@marvinsellers4457
@marvinsellers4457 3 месяца назад
Buddy I’ve have the same problems gut it rewire as long as your warranty is not in place they do some really dumb things
@hvactoolporn188
@hvactoolporn188 3 месяца назад
How are you running the blower?
@hvac402
@hvac402 2 месяца назад
Can you just move the 24 V wires from one contactor to the other
@hvactoolporn188
@hvactoolporn188 2 месяца назад
No, the board will fault out. First thing I tried.
@joshuaricks7730
@joshuaricks7730 15 дней назад
Cool 1 is NOT the same as compressor 1. Compressor 2 is the smaller of the two compressors. That will always be the first on last off. This is stated in the manual a couple times. The contactor failure faults you are having is because you have Y1 and Y2 jumped out. If the aux switch makes without a call it thinks the contactor is welded.
@nevermind3965
@nevermind3965 25 дней назад
symbio controls are garbage.If you can get it to start anything, just go with it.
@benahmedahmed831
@benahmedahmed831 Месяц назад
Perblam E2 model SERVICE FIRST Trance Rooftop SENO 1577 ‏termstat
@doubleocryptojames1053
@doubleocryptojames1053 4 дня назад
Thermostat errors for running on conventional?
Далее
Symbio startup
11:36
Просмотров 4,9 тыс.
When DUMB Cops Shot Their Own Partners
18:31
Просмотров 2,1 млн
УДОЧКА ЗА 1$ VS 10$ VS 100$!
22:41
Просмотров 227 тыс.
Decompress small game, have time to play it!
00:35
АХХАХАХАХАХАХАХАХ
00:16
Просмотров 205 тыс.
Новый уровень твоей сосиски
00:33
Compressor Won't Start On Trane RTU @ Data Center
8:15
50% of all 4090 will end up in trash and here is why
14:26
TRANE VOYAGER NOT COOLING
23:21
Просмотров 120 тыс.
Diagnosing a Locked Compressor 3D
10:02
Просмотров 61 тыс.
American Standard Trane Symbio 700 intro and wiring
9:32
УДОЧКА ЗА 1$ VS 10$ VS 100$!
22:41
Просмотров 227 тыс.