Hello, I am in trouble to connect inverter and battery. Is it possible to run the inverter without communication with the battery? The inverter I had before provided several configurations to adjust the behavior of the inverter without the need to connect inverter and BMS.
Hi Sir, thanks for your reaching out. If you don't want to communicate with the battery, you can choose the battery type to be "Lead-acid". For further support, please share us with you SN or send email to us: info@luxpowertek.com
PV input 17A. Mppt range 120-385v 385*17=6545 Watt. Why power limited 4000 watt per input? If i connect 10 panels * 465wt (400v open circuit voltage) on PV1 It will be work normally?
Hi Sir, Thank you for reaching out. Regarding your first question, we have designed a 4kW limit per MPPT due to heat management requirements. If the power exceeds 6kW per MPPT, the inverter will operate at a higher temperature, which can damage the unit. Therefore, we limit the PV power input per MPPT to ensure safe and efficient operation. For your second question, if you connect a total of 4.65kW input to PV1, our inverter will automatically limit the input power to a maximum of 4kW.