In this tutorial video, we will learn how to generate 4-20mA signal in our Lab, using DC power source and variable resistance.
We hope this video will be helpful to begineers, technicians and students who are new to automation systems.
Subscribe us so that you don't miss any tutorial.
Click here to subscribe: goo.gl/XbeUf3
Promoted by satyaraosiddharth

Опубликовано:

 

13 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 60   
@emmanuelescalante3264
@emmanuelescalante3264 2 года назад
This is basic... But you presented it intelligently... I never thought that... i only need a potentiometer to produce a current source... 😄 Thanks so much sir... Bravo.... Now i can test my positioner...with this simple cicuit device 😄 😄 😄
@arslanahmad7000
@arslanahmad7000 6 лет назад
Thank u soo much sir Actuelly we have a lot of ultrasonic sensors in our water treatment plants and with some other equipments as well Thats y i requested for it Plz make more videos to do more simplify this importent topic
@venkataramanramanan619
@venkataramanramanan619 6 лет назад
Arslan Ahmad
@allanminers1662
@allanminers1662 3 года назад
VERY GOOD, WELL DONE
@youtuuba
@youtuuba 6 лет назад
This video does a disservice to viewers who are hoping to learn more about making 4-20mA current loops work. It supposes that all one needs to make a 4-20mA current 'source' is a variable resistor. Well, in fact one can use a variable resistor by itself, as shown in the video, but it will never be a reliable 4-20mA controller. This is because it cannot monitor the actual resulting loop current, and cannot automatically adjust to variables in the current loop. If the power supply voltage wavers, the current will change. If the loop resistance changes (for any reason, including temperature, connection resistance, etc) the current will change. If another receiver is added to the loop, the current changes. The upshot of this is that a simple variable resistor can be used to vary loop current on a crude, temporary basis. But it cannot work effectively in real applications. Only a proper 4-20mA "transmitter" can do this, because a transmitter not only adjusts its own resistance automatically, it also monitors the loop current so it can compensate for resistance changes elsewhere in the loop.
@starautomation
@starautomation 6 лет назад
Yes, dear friend you are right. It is a very basic form of current source through which you can test any instruments operational working, which needs 4-20mA signal at its input terminals.
@mobmt6239
@mobmt6239 3 года назад
How many watts? Please advice.
@youtuuba
@youtuuba 3 года назад
@@mobmt6239 How many Watts what? If you even need to ask about Watts for a 4-20mA application, then you probably don't understand the theory.
@upendrarao4055
@upendrarao4055 6 лет назад
Very good job sir jee. Please make a lot of in this type vidio. God bless you
@starautomation
@starautomation 6 лет назад
+Upendra Rao Thank you.
@athilaldurry5880
@athilaldurry5880 4 года назад
Many thanks, was useful
@samiinvertersfsd
@samiinvertersfsd 4 месяца назад
🎉super
@vishalgovekar6369
@vishalgovekar6369 6 лет назад
Thank you so much
@mohammadshafiullakhan5604
@mohammadshafiullakhan5604 4 года назад
Good info...thanks
@machineryoverhaulretrofitm6607
@machineryoverhaulretrofitm6607 4 месяца назад
thanks
@gkpgeo
@gkpgeo 3 года назад
What if we know current output somewhere 400-1000 ma , varying voltage 25 -400
@eknathkulkarni2692
@eknathkulkarni2692 5 лет назад
What was the current rating for the vdc 24 volt which you used...let us know
@jovencagualpa
@jovencagualpa 6 лет назад
Very good video, just 1 question, why the R variable (potentiometer) have 3 wires? Resistance wire "A" go to + 24 vcd Resistance wire "B" go to multimeter (+) Resistance wire "C" go to ????? Thanks
@starautomation
@starautomation 6 лет назад
Potentiometer say 5k ohm has three wires, A B and C. So, resistance between A and C will always remain 5k ohm. When we rotate the knob of potentiometer, resistance between A and B will increase and at the same time resistance between B and C will decrease. B is called as wiper terminal of potentiometer.
@jovencagualpa
@jovencagualpa 6 лет назад
@@starautomation SO THE TERMINAL "C" we can leave without wire, wright?
@KD-xp4di
@KD-xp4di 6 лет назад
Atahualpa Gaytán the main reason is that it works as a voltage divider. it's like two resistance in one. if you connect only one leg it's like you have only one resistance. the difference is that using a voltage divider gives you more stable output that just one resistance.
@eng.aymanelsayed5159
@eng.aymanelsayed5159 6 лет назад
very nice video . thank you . need alot from you .
@starautomation
@starautomation 6 лет назад
+Ayman Elsayed Thanks for appreciation
@brightwinshah8980
@brightwinshah8980 6 лет назад
Nice, it will be better if there is display.
@sahajahanhossain7376
@sahajahanhossain7376 4 месяца назад
input 24v out v?
@eng.aymanelsayed5159
@eng.aymanelsayed5159 6 лет назад
wait for your new videos . thank you
@justingeorge1876
@justingeorge1876 8 месяцев назад
IF YOU TURN THE POT TO LOW RESISTANCE POINT, IT WILL BE LIKE SHORTING THE 24V, HIGH CURRENT CAN DAMAGE THE MULTIMETER OR THE FUSE WILL BLOW, EITHER INSIDE METER OR THE POWER SORCE
@trif169
@trif169 7 месяцев назад
Correct! though most trimming pots have limits set so they don't venture to that minimum resistance if so it will be open cirucit and show a fault on the control loop either on your DCS or control panel. Usually it will indicate fault that the valve has overtravelled or something along those lines
@SAIFulISLAM-mf3jx
@SAIFulISLAM-mf3jx 4 года назад
Sir i am connect but may be I am wrong plz clear me connection of pot meter it have three terminal one common which two wire need to connect Regards
@rksharma8534
@rksharma8534 Год назад
This is for generating current source from external DC power supply. How to simulate 4-20 mA current in loop powered instrument system??
@bigben046
@bigben046 6 лет назад
You may have mentioned this in the vid but, my hearing is not that good. Is the pot 10 turn? Is it carbon or wire wound. Thanks.
@starautomation
@starautomation 6 лет назад
It is wire would ten turns potentiometer.
@HERO846s
@HERO846s Год назад
wiasou sei denn de videos oooolbm ve sette kommischn inder de koan enlisch dorredn gmocht. bleibs in enkrn versifftn lond. ess pailts es jo decht net gorasou sso
@sharifhossain8830
@sharifhossain8830 4 года назад
potentiometer 3 k, voltage 5 vdc So how much mili ampere??
@3deesuk
@3deesuk 3 года назад
This is very dangerous to any instrument, you need to put one resistor in series first to limit the current not go up more then 20 mA,
@jayanttiwari4817
@jayanttiwari4817 Год назад
If potentiometer is at zero resistance then, load will receive direct + 24V, and it will damage the load
@amitpatelpatel144
@amitpatelpatel144 6 лет назад
Nice video but I need more precise current.
@starautomation
@starautomation 6 лет назад
For precise variation in current, you need precise variation in resistance as 24vdc is constant. You can use ten turns potentiometer for precise variation in resistance.
@haha2562
@haha2562 6 лет назад
Здравствуйте,R(resistor)=12000 Om? или 5 кОм?
@BB-eo8mo
@BB-eo8mo 5 лет назад
I have a doubt .. you are checking current from positive and negative terminal. How it is possible
@kumar337
@kumar337 5 лет назад
By checking with meter probes circuit gets closeed in series
@siddharthasiddhu7562
@siddharthasiddhu7562 6 лет назад
Can we use directly as a m.a for vfd ? Or use R to I converter in between ? Please replay me
@starautomation
@starautomation 6 лет назад
Yes. It is mA and can be used at analog input of vfd
@naananiaziz20082009
@naananiaziz20082009 4 года назад
That's wrong,This isnt a current source. a current source must give a constant current. That cun be using bipolar or FET by making Vb constant then Ic constant or Vgs constants then Id constant.
@MrPsghodasara
@MrPsghodasara 11 месяцев назад
This is wrong. It can not be used to test any instrument. Bacause instrument resistance will be added in series. Ideal current source keep current constant regardless of load resistance.
@MahmudulHasan-by7zq
@MahmudulHasan-by7zq 3 года назад
I TRY IT BUT ITS NOT WORK.....
@mustaqpeerjade6452
@mustaqpeerjade6452 Год назад
Not work
@rfdave3980
@rfdave3980 6 лет назад
Oh brother, are you serious.
@GHEBIANDGAYAR
@GHEBIANDGAYAR 6 лет назад
Current source
@GHEBIANDGAYAR
@GHEBIANDGAYAR 6 лет назад
This is not a source children stuff
@aforabbottabad7977
@aforabbottabad7977 5 лет назад
You have connected wrong
@starautomation
@starautomation 5 лет назад
It is all tested. What you want to say, please clarify
@pratikbhagat9028
@pratikbhagat9028 2 года назад
Not correct method. This is jugadu method
@zahidmahmood3081
@zahidmahmood3081 3 года назад
Very bad idea, think again
@aungmyintsoe105
@aungmyintsoe105 2 года назад
Thanks you so much
@starautomation
@starautomation 2 года назад
Happy to help
@MrSiddhantamonkar
@MrSiddhantamonkar 6 лет назад
Thank you Was useful
@starautomation
@starautomation 6 лет назад
☺️
@pradeepkumar-dt4yj
@pradeepkumar-dt4yj 5 лет назад
Thanks
Далее
Constant Current Source
17:23
Просмотров 42 тыс.
when you have plan B 😂 @andreyreactions
00:11
Просмотров 4,4 млн
OG Buda, Слава КПСС - LAZER SLAVA
01:58
Просмотров 121 тыс.
Mat pembersih pink untuk ibu hamil
00:21
Просмотров 1 млн
EEVblog 1397 - DC Voltage & Current Source Theory
23:50
Making a Tiny 4-20mA Current Loop Tester
1:23:49
Просмотров 29 тыс.
4-20mA sensor explained with a simple Arduino example!
11:44
4 to 20 mA, 1-5 V, 3-15 psig Lesson #1
16:20
Просмотров 57 тыс.
4-20 mA signal measurement with Arduino
31:25
Просмотров 20 тыс.
Active and Passive 4-20mA - What's the Difference?
3:31