Modbus TCP MBTCP Aveva Wonderware SP2020 Basic Guide 

Automation Control Hub
Подписаться 683
Просмотров 10 тыс.
50% 1

Опубликовано:

 

5 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 14   
@tayyang2265
@tayyang2265 5 месяцев назад
Thabk u so much, u saved me
@automationcontrolhub
@automationcontrolhub 3 месяца назад
you are most wellcome
@umairahmed3100
@umairahmed3100 Год назад
How to configuration and requirements for SIdirect server
@zonaotomasi
@zonaotomasi 2 года назад
Good one. Thank you for sharing.
@salaheldineghennai7743
@salaheldineghennai7743 10 месяцев назад
Hello Sir, that is very great explanation, i just wanna know why you didnt use galaxy IDE
@automationcontrolhub
@automationcontrolhub 3 месяца назад
Because I dont have license for the galaxy IDE.
@OliverCHO-o1w
@OliverCHO-o1w Месяц назад
Is there Modbus Serial Driver? I need RS485 communication.
@automationcontrolhub
@automationcontrolhub 28 дней назад
for RS485 with COM connection, you can install old modbus serial driver but there is some modification in configuration file since that driver no longer support recent version of SMC UI. You should edit the configuration as xml file and you good to go.
@trifff40
@trifff40 7 месяцев назад
oi mbtcp in my smc dont appear, any solution sir please? i have downloaded the oi mbtcp driver sir
@scottgriffiths5315
@scottgriffiths5315 2 года назад
You mean how to connect to Intouch HMI...
@umairahmed3100
@umairahmed3100 Год назад
Can be configuration Aveva 2023 in to s7300 ,4000?
@automationcontrolhub
@automationcontrolhub 11 месяцев назад
I'm not testing it yet. I'll try it.
@tiapathe7109
@tiapathe7109 3 месяца назад
I follow your steps, but intouch don't show any data ,and log viewer show DASProtFail MBTCP Error in Reading from PLC for item New_TCPIP_PORT_000.New_ModbusPLC_000.40003 F DASProtFail MBTCP The PLC New_TCPIP_PORT_000.New_ModbusPLC_000 reported receiving an ILLEGAL DATA ADDRESS from the OI Server. PLC errorcode 02 Do u mind tell me how to fix it?🥲🥲🥲
@automationcontrolhub
@automationcontrolhub 2 месяца назад
there are some possibility that could make illegal data addres happen : - the device id from modbus slave couldnt be reach by wonderware. Since I use demo version, it seems like only address 255 is allowed for configuration - the range of modbus address configured in wonderware more than what modsim (as a modbus slave) can be served or the range is offset. Kindly make sure wether you configured in 0 based or 1 based address.