My New Trane is making a noise! but why?  

Everything HVACR
Подписаться 9 тыс.
Просмотров 1,5 тыс.
50% 1

this service call was created by a noise, only noticed by the person who was contracted to replace the air filters. this is a large manufacturing facility with a temperature controlled warehouse. the filter company replaced the filters and left the unit off. let's see if we can figure out where our noise is coming from. Give some good tips for any commercial technician working on a roof and some important things to look for during your package unit preventive maintenance.

Опубликовано:

 

12 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 66   
@mechanicalenvironments
@mechanicalenvironments 5 месяцев назад
Good find! That wheel is done for sure. They are lucky it didn't break apart and throw a chunk into any other components.Looks like that housing can potently even be reused, if they want/need to. We go through a ton of zip ties cleaning up nonsense wire management, in the end it benefits you and the customer like you said. Regularly cleaning up wire management, makes finding electrical shorts a breeze when you know the common rubout spots for each model. Plus, it is a treat to come back to a unit you cleaned up, when you can easily trace wires and take amp draws. making your future service more efficient. Great knowledge here for sure, thanks for the video!
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
I agree completely, thanks, MechanicalEnvironments!
@subcoolHVAC
@subcoolHVAC 5 месяцев назад
Great video, I had a 25ton Trane condensing unit installed a couple years ago and the fan motor brackets broke , fan blade went right into the micro channel coils. Not even a month old. Trane had to repair.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, Subcool. It doesn't take much to damage those coils for sure.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 5 месяцев назад
Had it happen to me, except it blew the wheel all to hell. The wiring....well...it hasn't ever gotten any better....slapping lipstick on a pig. Except AAON they seem to care a little bit better than the big 3 do. Another great video Steve-o...thanks for sharing
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Hey, thanks, Jason! I don't know if it's the wheels being junk or we could be running too many rpm. A tachometer check might reveal an issue
@neilcvids2583
@neilcvids2583 5 месяцев назад
I have Aaon door panel hold open brackets I had to "trim" to clear suction and discharge lines, let alone wires also, 2015 units, 2018 unit, everybody is junk
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yeah, this seems to be the cards we've been dealt. Adapt and overcome 💪. Thanks, Neil C
@Eddy63
@Eddy63 5 месяцев назад
Steve-o doing what he do Nice job as usual ... Thx
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, Eddy! 💪
@helmsajr
@helmsajr 5 месяцев назад
Great job Steve has always.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, Jr!
@haldermand
@haldermand 5 месяцев назад
I take care of a building with a pile of 15-25 ton Voyagers around the same age as yours there. They’ve been one problem after another. Lots of consecutive serial numbers so I suspect a manufacturing issue. Compressors, VFD’s, lots of blower assemblies. I just order a new wheel, shaft, and both bearings. I’m not wasting my time trying to save the shaft and bearings. It goes alot quicker that way. Another good video man.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, Haldermand. I would tend to agree. It's easier if you have all the parts and will save you some time in the end.
@zekenzy6486
@zekenzy6486 5 месяцев назад
Great Video. Thank you for sharing.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thank you, ZE
@jamesortolano3983
@jamesortolano3983 5 месяцев назад
Another good catch, bet that was some serious racket up there when the pm guy were gettin close to it 😅,definitely can be nerve rackin down below as well. That was definitely manufacturers f'up. Thankx for the post
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, James! Yeah, I bet it was loud 😆
@WswRefrigeration
@WswRefrigeration 5 месяцев назад
If you look hard enough you’ll always find issues. You’re killing it. Your company is lucky to have you as a tech
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thank you, WswRefrigeration. Yes, you can always find something if you know where to look. I appreciate the kind words 🙏
@jaymartin5095
@jaymartin5095 5 месяцев назад
Interesting find on what was broken and what was going to break next. I assume you wrote up all the PM stuff that should be done and let them decide if they want it done? Then what about all the same PM stuff on all those other RTUs? Things are out of control: need super knowledgeable tradesmen, stuff corrected that wasn't done right at assembly time, and no one wants to pay for any of it.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
I did make notes about the issues I found. We can correct issues with this unit when repairs are made, then next time a p.m. is performed, we need to look out for the wiring issues on the others. It doesn't take long to secure the wires. We just need to be on the lookout for these issues. Thanks, Jay!
@ccthepope
@ccthepope 5 месяцев назад
Great video!
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, r aeronca!
@simonharvey3872
@simonharvey3872 5 месяцев назад
I was wondering were the music was coming from on the middle of roof until you showed the return 😂😂😂 great find Steve!
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
😆 Thanks, Simon!
@stevencossaboon3237
@stevencossaboon3237 5 месяцев назад
Another great video Steve. Thank you for the knowledge.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thank you, Steven!
@Paul-IE-Repairs
@Paul-IE-Repairs 5 месяцев назад
sweet, that must be one of those new Variable Vein blower wheels that self adjust with static pressure.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Lol, thanks, Paul! It self adjusted, alright 😆
@johnwaby4321
@johnwaby4321 5 месяцев назад
That fan does not look like an easy job to get out 😯 A few wiring issues and bad connections to sort out as Well 👍👍
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
It's not a fun job, especially with the location of this one. Thanks, John!
@spirosdoulakis4364
@spirosdoulakis4364 5 месяцев назад
Actually just found the exact same problem a week ago on a 4 year old voyager with a high static kit.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Interesting, I've heard multiple people had the same issue.
@qomco
@qomco 4 месяца назад
We had 20 something voyagers installed, about half with unaligned pulleys and one where the pulley flew off within the 1st year
@EverythingHVACR
@EverythingHVACR 4 месяца назад
This building is the same deal, I found most of these were out of alignment. Thanks, qomco
@myHVAClife
@myHVAClife 5 месяцев назад
They have all outsourced quality control jobs to the far east! Just give "BOB" in India a call and he can help with all that!
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
😅. Yeah, I've talked to Bob before.
@shifter8207
@shifter8207 5 месяцев назад
We installed 6 of those new Trane s 4 hrs out of town and when we came back found the blower wheel did the exact same thing and blew apart the spider and the wheel dropped. Luckily the belt blew off and didn’t make it worse
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Interesting, I had a feeling I was going to hear people who experienced the same issue. We're going to have to start putting a tachometer on these things in the field, I wonder if that would catch something on start-up. Or if that's even the issue, they might just be junk blower wheels. We do see a lot of junk these days.
@shifter8207
@shifter8207 5 месяцев назад
@@EverythingHVACR the junk aspect and lack of entering the wheel a bit better seemed to be what we experienced
@hellhound-si5oz
@hellhound-si5oz 5 месяцев назад
The blower wheel grenade
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
😆. Thanks, hellhound
@mikemoseley8711
@mikemoseley8711 5 месяцев назад
Bad quality is not just Trane/American Standard. It’s all the manufacturers are getting very sloppy putting these units together. Especially commercial package units
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Agree completely. Thanks, Mike.
@kieranthompson1982
@kieranthompson1982 5 месяцев назад
The fins on the wheels are getting lighter and lighter when installing it even if you rub the fins on the outside shroud the wheel becomes unbalanced and each revolution it cracks along the spot welds where it joins to the arbor plate then its just time before it wobbles enough to hit the sides of the shroud, saw a tech try to weld one up he thought he was top dog at fixing it i told him if it doesn’t shake the bearings to pieces it will just break again , plus you have unbalanced it further by adding weld weight to it, buy new and install properly and dint accept damaged replacement from oem either
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Thanks, Kieran. I agree, if its out of balance, it will tear everything apart eventually.
@kieranthompson1982
@kieranthompson1982 5 месяцев назад
@@EverythingHVACR so much weight hanging one side on paper thin metal was always going to be recipe for disaster never had problems working on trade winds stuff they used 12ga metal no problems at all as soon as company bought out by accellair group they started using pressed 24ga metal damned things broke every 5 yrs
@musicnerd72
@musicnerd72 5 месяцев назад
Apparently you CAN stop a Trane! 🤣
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
😆 It seems like all the tranes I see have stopped.
@joshstevens9826
@joshstevens9826 5 месяцев назад
On a building that big, who the F* sold them on rtu's? Should have been a chiller plant and ahu's
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Im not sure who sold them on rooftops. the building is an existing manufacturing building that is in operation. This was probably cheaper and less invasive to their manufacturing process, I would assume. The original building only had the office area conditioned and only exhaust in the warehouse.
@fshn76
@fshn76 5 месяцев назад
Wire ties = Cheap insurance
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yessir, thanks, Bryan!
@user-su5ft8lc9q
@user-su5ft8lc9q 5 месяцев назад
Guss what, you can STOP A TRANE !!! THEY ALL OUTSOURCE THE PARTS TO THE CHEAPEST BIDDER.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yeah, it's not too hard to stop anything these days.
@ronaldclark8187
@ronaldclark8187 5 месяцев назад
Horrible engineering and lousy quality control. All those rubouts in areas that could cost thousands in the aftermath. Assembly without aptitude
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yessir, I agree. Thanks, Ronald!
@grandinosour
@grandinosour 5 месяцев назад
They will only engineer and quality control a machine so it will just make it through the warranty period... After that is just pure luck.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
@grandinosour luck, or a thoughtful technician. 🤔...I agree, it does seem like they always just last long enough to be out of warranty.
@KevinKinder-ey9gv
@KevinKinder-ey9gv 5 месяцев назад
Quality sucks nowadays
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yes, it does. Thanks Kevin
@ianpalmer1482
@ianpalmer1482 5 месяцев назад
Unsecured wires and crap, cheap parts. Factory issues all the way.
@EverythingHVACR
@EverythingHVACR 5 месяцев назад
Yeah, sad, smh. Thanks, Ianpalmer!