PAGKAKAIBA ng Addressable FDAS / Conventional FDAS | Fire Detection Alarm Systems 

Подписаться
Просмотров 32 тыс.
% 629

Main Difference between Conventional Fire Alarm and Addressable Fire Alarm Systems
The conventional fire alarm system is that in case of fire indication, it will only detect the whole floor. It cannot pinpoint the exact location of the triggered alarm in the floor. The reason is that the sensors and devices triggers when the input cross certain threshold and send electrical signal to the main control panel through the common wire. Therefore, the main penal detects it as the whole zone (circuit).
Since it cannot pinpoint the exact location of the fire in the building, it is difficult for fire fighter to find the exact location and extinguish the fire before it cause further damage.
The addressable fire alarm system assigned each individual devices a unique address. It is a digital updated version of the conventional fire alarm where each detectors or sensors have unique identity. Therefore, each device has its own identity which makes it easier to identify which device has been triggered and spot the location of fire. The system quickly notifies the local responders to take the necessary action to stop further damage.
Overall, the conventional fire alarm is inexpensive and used in small building. however, the addressable fire alarm is very smart and sophisticated system which is very expensive but it is more reliable. Bottom line, conventional fire alarm should be installed in building where it is easier to spot the fire (such as in building having fewer rooms) While the addressable fire alarm should be installed in large buildings.
If this video helped you out, share it with your friends and give it a thumbs up, please drop a like and leave a suggestion or comment below.
----------------------------------------------------------------------------------------------------------------
Our daily routine as Maintenance Technician in our company.
#Please_Like_Share_and_Subscribe​_RACkabayanTECH​​
➦ For more videos please SUBSCRIBE! 👍
©️ Disclaimer Under Section 107 of the Copyright Act 1976,
allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research.
Fair use is a use permitted by copyright statute that might otherwise be infringing.
Non-profit, educational or personal use tips the balance in favor of fair use.

Опубликовано:

 

27 май 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 59   
@RACkabayanTECH
@RACkabayanTECH 3 года назад
This video presentation is for educational purposes only
@edinaguilar12
@edinaguilar12 3 года назад
Grabe galing tlaga ng bro ko..very helpful tlaga. Keep sharing brother.
@pinoymaster1067
@pinoymaster1067 2 года назад
Ayos yan master my natutunan nNMn ako
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Thanks
@niloyu105
@niloyu105 Год назад
New subscriber watching from Al Khafji Saudi Arabia Support Filipino Vlogger especially 55sec. Ads
@RACkabayanTECH
@RACkabayanTECH Год назад
Thanks kabayan👍
@jenwellnieves2274
@jenwellnieves2274 11 месяцев назад
Good day sir…pwede tutorial ng FACP programing or configuration
@olybernardo6019
@olybernardo6019 2 года назад
Sir may video ka Kung pano mag synchronized and Isang bell sa dalawang Panel TIA👏👏
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Abangan nyo po sating channel.....isa din po yan sating TOPIC soon
@jillferrer6135
@jillferrer6135 Год назад
👍
@RACkabayanTECH
@RACkabayanTECH Год назад
😊
@benardbadiang2061
@benardbadiang2061 7 месяцев назад
PANO po malalaman Kong Ilan pisaso sa Isang zone..
@johnreymaliao3352
@johnreymaliao3352 Год назад
Master panu malalaman kung anu value ng resistor ilalagay..?
@kelvinwarrenlozada777
@kelvinwarrenlozada777 2 года назад
Kasi hirap kasi pag mag truoble conventional kasi lahat tingan ang device .
@rhiejhayferrer2272
@rhiejhayferrer2272 Год назад
anu po ung RM?
@miralynmalubay3853
@miralynmalubay3853 Год назад
Kabayan sa adrressable ba ang sounder Kasama na sa loof...sama na sa connection..or bokod ang wiring ng sounder....salamat poh
@RACkabayanTECH
@RACkabayanTECH Год назад
Kapag addressable fire alarm system ang gamit mo partner lahat ng initiating devices ay naka kabit sa isang loop lamang sana nakatulong👍😊
@joselitoalasas4152
@joselitoalasas4152 2 года назад
Sir sa conventional po. Pwd ba magkabit ng module para sa door access?
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Hi partner yes.... partner pwede maglagay lang po kayu ng module relay na pang conventional....sana nakatulong👍
@anthonynesortado1471
@anthonynesortado1471 2 года назад
Sir, ung sounder po ba sa addressable hiwalay po ba ang wire?
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Pag addressable FACP ang gagamitin nyo partner iisa lang po ang wire ng sounder at mga detective device.....
@markguibo3611
@markguibo3611 3 года назад
Saan ma's mura sir ang addressable or conventional alarm sestym?
@RACkabayanTECH
@RACkabayanTECH 3 года назад
Thank you! Good question! Overall, the conventional fire alarm system is inexpensive and used in small building. however, the addressable fire alarm is very smart and sophisticated system which is very expensive but it is more reliable. Bottom line, conventional fire alarm should be installed in building where it is easier to spot the fire (such as in building having fewer rooms) While the addressable fire alarm should be installed in large buildings.
@johnsvlog676
@johnsvlog676 Год назад
Conventional same po ba sa non addressable fire alarm system po?
@RACkabayanTECH
@RACkabayanTECH Год назад
Hindi partner magkaiba sila ng systema😊
@jamesryanpastor1326
@jamesryanpastor1326 2 года назад
Ano po ba ang MANUAL CALL POINT same lang po ba sila ni manual pull
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Same lang po yan partner👍
@user-fy5vf7li4g
@user-fy5vf7li4g 5 месяцев назад
Iln sounder ung 5 zone sir
@RACkabayanTECH
@RACkabayanTECH 5 месяцев назад
Naka depende po sa (FACP) innmy tutorial maximum 30 initiating devices lang po per Zone! Sana nakatulong😊
@jimenezlevie5517
@jimenezlevie5517 2 года назад
Okey lang ba yan, kahit ano Mauna ikabit.. tulad Ng smoke detector, at heat detector
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Ok lang partner👍
@julieannpadillo1913
@julieannpadillo1913 2 года назад
bakit po nakahiwalay ang sounder sa conventional
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Pag ang FACP nyo po ay conventional system hiwalay po ang Sounder nyan partner🤓
@pansitkanton1881
@pansitkanton1881 2 года назад
Sir tanong ko lang po tungkol sa Addressable Fire alarm System. Paano po kung maraming sounder sa isang loop? tutunog po ba silang lahat if ever na may na detect na smoke or heat? AT paano naman po kung meron pang 2nd loop, tutunog din po ba yung mga sounder sa 2nd loop kahit na sa loop 1 may na detect? Nag Subscribe na po ako sir malaking tulong po mga videos nio. ❤
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Hello partner, regarding sa tanong mo, sa default setting yes partner lahat ng sounder tutunog po at makikita mo sa FACP kung anong address ng device ang nag activate..... Second loop! Naka depende po sa program at nakapende din po sa kakayahan ng FACP na ginamit🙂 sana nakatulong🙏🏽
@pansitkanton1881
@pansitkanton1881 2 года назад
@@RACkabayanTECH thank you master. klarong klaro po
@darzdelfin8791
@darzdelfin8791 2 года назад
Sir yung sa adressable yung mcp ba at sounder kailangan paba yan lagyan ng resistor? Slamat
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Thanks partner.... regarding sainyong tanong....pag addressable yung system na ginamit mo hindi kailangan lagyan ng resistor o diode yan dahil naka loop lang po ang wiring nyan ibig sabihin yung pinaka huling device na ininstall ang wiring nyan babalik lang po yan sa FACP partner........sana nakatulong👍
@darzdelfin8791
@darzdelfin8791 2 года назад
Slamat master convincional lng kc na expirience ko sir slamat sa video mu sir
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Appreciated partner🤓
@RandomVideos-dr6zz
@RandomVideos-dr6zz Год назад
Semi addressable bosing sana
@RACkabayanTECH
@RACkabayanTECH Год назад
Salamat partner
@dennisgarque4224
@dennisgarque4224 2 месяца назад
For me po sir, mas magandang gamitan ang addressable type
@RACkabayanTECH
@RACkabayanTECH 2 месяца назад
Indeed partner
@neym9587
@neym9587 2 года назад
Bakit po nakahiwalay Yung sounder sa conventional?
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Pag conventional system partner nakahiwalay ang linya para sa sounder bawat zone.....Sana nakatulong👍
@kgiempire5951
@kgiempire5951 Год назад
Ilan po max load per zone ? 13 or 30 po?
@RACkabayanTECH
@RACkabayanTECH Год назад
30pcs partner
@kelvinwarrenlozada777
@kelvinwarrenlozada777 2 года назад
Sir madaling salita masmadali trouble lin ang addressable kaysa conventional sir.
@RACkabayanTECH
@RACkabayanTECH 2 года назад
Yes tama po kayo kabayan👏😊
@rb1m426
@rb1m426 Год назад
May conventional fire alarm kami dto master.Zone 1 may alarm master anong trouble yan master
@RACkabayanTECH
@RACkabayanTECH Год назад
Check nyo yung boung Zone1 na mga initiating/detective devices na naka install isa sa mga yan maraming alikabok sa loob ng sensor! kaya nag activate😊 malalaman mo dahil may red na ilaw nag blink-blink👍 i blower mo lang tas ibalik mo then i reset sa FACP nyo🤔
@rb1m426
@rb1m426 Год назад
@@RACkabayanTECH salamat master 😊 napakamalaking tulong po yung advice mo 😊 ty po
@arielescamillas7180
@arielescamillas7180 10 месяцев назад
Paano sir mag address ng mga devices?
@RACkabayanTECH
@RACkabayanTECH 10 месяцев назад
May video na ako nyan sir panoorin mo nalang partner😊
@ritzchad
@ritzchad Год назад
Pag sa mall po ano po ang ginagamit?
@RACkabayanTECH
@RACkabayanTECH Год назад
Naka depende po sa kleyente, o sa dami ng initiating devices na ipainstall, at lawak ng pag iinstallan partner! Sana nakatulong👍
@ritzchad
@ritzchad Год назад
@@RACkabayanTECH hindi po pwede mag series sa sd to sd sir diba?
@RACkabayanTECH
@RACkabayanTECH Год назад
Walang series po sa FDAS connection dapat nakaparalel lang po partner👍