Тёмный

PID Settings | Proportional-Only Control 

RealPars
Подписаться 1,1 млн
Просмотров 84 тыс.
50% 1

▶ C'mon over to realpars.com where you can learn PLC programming faster and easier than you ever thought possible!
▶ You can read the full post here
realpars.com/pid-settings
⌚Timestamps:
00:00 - Intro
00:50 - A typical flow control loop
01:53 - Proportional-Only control
03:14 - Examples
05:41 - Offset in PID control
=============================
In this video, we’re going to look at the effects of Proportional-only action on a flow control loop.
Proportional-only control is the simplest of the PID controller actions but is seldom used in industrial production processes.
The problem with P-Only control is something called Offset. In this video, we’re going to explain Offset and show you how and when it occurs.
The controller in our loop is typical of most controllers. We can adjust the setpoint and switch between auto and manual. In manual control, we can adjust the controller output to the exact amount we want.
Our flow loop has a pump to move our process fluid. We can turn the pump on or off which will be very helpful for observing PID responses in static and dynamic conditions.
Let’s start investigating the effects of adjusting the amount of Proportional action on our flow loop.
The controller output range is 4 to 20mA representing 0 to 100%. When the process is stable, the controller output will be at some value between 4 to 20mA.
The Process Variable is also represented by a 4 to 20mA signal from the Flow transmitter. This signal represents 0 to 100% of the process variable.
The controller’s job is to ensure that the Process Variable is the same as the Setpoint. The controller is always looking at the difference between the Setpoint and the Process Variable. This difference is often referred to as the Error.
Proportional Action is an Amplification of the Error. This Proportional amplification has no units and often is referred to as Gain. This amplified result is added to the current controller output.
We have a simple math formula:
New Controller output = Previous Controller output (CO) + (Gain × Error)
Let’s look at an example of Proportional Action and how that math formula applies.
We’ll start with the pump OFF. With the controller on Manual, we’ll set the output to 50%. We’ll set the Gain to 1.
We’ll set the controller to Auto. With the pump OFF, the PV or Process Variable will be 0.
The Setpoint change of 10% produced a 10% change in Controller output. Why? The Controller Output (CO) changed by 10% from 50% to 60%.
Because the Gain is 1, the proportional action will only add 10% to the controller output. The Controller output was at 50%, so adding the proportional response will move it to 60%.
With the Pump OFF, we have no possible change in the process variable therefore our Proportional Action is acting on a static condition.
Once the pump starts, we are in a dynamic environment and variables are changing with time.
We start with the Process Variable at the setpoint value of 75%.
When we introduce a setpoint change to 65%, the Controller initiates Proportional Action and attempts to change the Process Variable to move to 65%. But, the Process Variable only goes to 69% and stays there!
A proportional-only controller does the job expected of it, at least until a disturbance, process variable, or setpoint change happens.
A process disturbance will cause the process variable to change and the controller will act.
Unfortunately, the process will recover back to a condition of stability, BUT NOT with the process variable at the set point.
The difference between process variable and setpoint is called Offset and occurs in Proportional-Only Controllers.
=============================
PID Controller Basics: learn.realpars.com/courses/PI...
=============================
Missed our most recent videos? Watch them here:
realpars.com/thermocouple-plc
realpars.com/variable-frequen...
realpars.com/lvdt
=============================
PID Controller Explained realpars.com/pid-controller
How to Tune a PID Controller realpars.com/pid-tuning
What Are PID Tuning Parameters? realpars.com/pid-tuning-param...
=============================
To stay up to date with our last videos, make sure to subscribe to this RU-vid channel:
bit.ly/realpars
=============================
TWEET THIS VIDEO: ctt.ac/f9Zte
=============================
Follow us on Facebook 👉 / therealpars
Follow us on Twitter 👉 / realpars
Follow us on LinkedIn 👉 / realpars
Follow us on Instagram 👉 / realparsdotcom
#RealPars #PID #Industry

Опубликовано:

 

7 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 72   
@SEALTRONICS
@SEALTRONICS 2 года назад
I don't know how to explain my anxiety and happiness when u post such awesome videos, please guys keep it up, love you, i want you to open a branch in Zimbabwe please, i will be the ambassador of RealPars in Zimbabwe 💞💞💞💞💞💞
@realpars
@realpars 2 года назад
Thanks a lot for your kind comment and support, Amos! We're happy to hear that.
@Diski76
@Diski76 2 года назад
As always the land talks RealPars👌👌
@hectorenriquesantandermeza5208
@hectorenriquesantandermeza5208 2 года назад
Very Well Explained Real Pars! It will be awesome if in the future you can make a video related to Adaptive Control for Non-Linear Systems.
@realpars
@realpars 2 года назад
Hi Hector, Thanks for your topic suggestion! I will pass it on to our course developers. Happy learning!
@asadiqbal87
@asadiqbal87 2 года назад
thanks real pars another great video
@realpars
@realpars 2 года назад
Glad you enjoyed it!
@maryambayani568
@maryambayani568 2 года назад
Well explained!
@realpars
@realpars 2 года назад
Thank you, Maryam
@aircates
@aircates Год назад
I really appreciate these videos. I am a Master Toyota technician and what I find interesting is how much the automotive industry industry is incorporating some of these technologies into their systems. A case in point, is our direct injection engines which now use a brushless 3 phase fuel pump and fuel pressure transducers to monitor pressure. It is really not much of a stretch to understand the mechanics of PLC operation.
@realpars
@realpars Год назад
Hi @aircates. Thanks for your comment. As you know, a car is loaded with computers. ECM's, ECU's....etc...etc..... And of course loaded with active sensors that detect everything from flow to pressure to temperature.....and much more!
@aircates
@aircates Год назад
@@realpars absolutely correct!! I’m seriously considering changing professions from automotive to industrial troubleshooting. This is much more interesting to me and the way the systems interact is not unlike many automotive systems. In fact, some of the illustrations you use to explain some systems are automotive.
@mustaphaaitsidimou9177
@mustaphaaitsidimou9177 Год назад
Really i appreciate these videos. Thank you very much
@mustaphaaitsidimou9177
@mustaphaaitsidimou9177 Год назад
In a control loop I found it already setting the P,I &D . But the measurement always exceeds the setpoint at 14% and then it returns stable. in this case it is necessary to act on P,I or D. Thank you for your response 😊
@realpars
@realpars Год назад
You're very welcome!
@eugenepohjola258
@eugenepohjola258 Год назад
Howdy. Credits to RealPars for taking the time and effort to make these educational videos. As a curiosity. The European understanding of positive control is that the control output follows the set value. Increasing set point increases control output. Default in Siemens controllers. The American way of positive control is that the control output follows the process value. An increase in process value increases the contol output. Default in Omron controllers. Positive European: "Controlling of heating." Positive American: "Controlling of cooling." Regards.
@realpars
@realpars Год назад
Thanks for your support, Eugene! We appreciate that
@eugenepohjola258
@eugenepohjola258 Год назад
@@realpars Howdy. Sirs, Ma'ams. You are most kind to say so. Yeah. Back in my career days I remember almost gone nuts not getting the flippin' Omron to control. I only got it to bang-bang from rail to rail. So eventually I checked the manual and switched the direction. Voila'. Began to work like magic. Regards.
@aminokamad1681
@aminokamad1681 2 года назад
Awesome 🔥🔥🔥
@realpars
@realpars 2 года назад
Thank you, Amino!
@s001b
@s001b 2 года назад
Thank you
@realpars
@realpars 2 года назад
You're welcome!
@anatolyterpugov4627
@anatolyterpugov4627 2 года назад
I understand correctly that at 4:39 the setpoint should change to 10, and not to 20, how is it with you?
@realpars
@realpars 2 года назад
Hi @Anatoly Terpugov. You are correct. The value in the controller setting SP window should show 10 and not 20. The graph correctly shows that the SP is 10. Thanks for pointing that out!
@benhurley280
@benhurley280 2 года назад
Awesome 😎
@realpars
@realpars 2 года назад
Thank you!
@montesdeocaf.2797
@montesdeocaf.2797 Год назад
Very good!!!
@realpars
@realpars Год назад
Thank you!
@vazgen6672
@vazgen6672 9 месяцев назад
Still great video as always
@shrikantsharma2321
@shrikantsharma2321 2 года назад
Please make video on siemens vfd starter software . Your videos are very helpful. Love from India.
@realpars
@realpars 2 года назад
Hi Shrikant, Thanks for your comment! We have quite some video courses on VFD, feel free to check those out over here ru-vid.com?search_query=+siemens+vfd+realpars Happy learning!
@bitebonumbere1426
@bitebonumbere1426 2 года назад
@ 6:23: "In our next video..." Please don't fail to release this next video very soon. Thanks RealPars. 😊
@realpars
@realpars 2 года назад
Thanks for your support, Bitebo!
@mrtechie6810
@mrtechie6810 Год назад
I want to add PID temperature control to my 240VAC instant hot water heater. What controller and sensor would you recommend? Is there such a thing as proportional heater control? A heater controller that factors in flow rate?
@realpars
@realpars Год назад
Hi Mr Techie. Thanks for reaching out. I'm curious about why you want PID control for your hot water on-demand heater. I'm gonna go out on a limb here and suggest that an add-on PID control is not practical or easily accomplished. I don't know what vendor made your heater, but I assume it has a built-in controller already. Can you provide any additional info please?
@mrtechie6810
@mrtechie6810 Год назад
@@realpars It has manual switches for two heating elements: low, high (or both). Further adjustment is by manually adjusting the water flow rate. No electronic nor mechanical thermostatic control (except for a thermal safety cutoff in case of overheating). Atmor brand, model Super 900
@jbpilon02
@jbpilon02 2 года назад
Hello, thank you for this video. I don't understand the formula CO=CO+(gain x error) because, after each scan, CO would augment to reach 100%. In a E5AR Omron controller, there is a parameter called manual reset which is a fixed value added to (gain x error). Then, the formula would be CO = (manual reset value)+(gain x error). So, even if the CO change depending on the error, the manual reset velue will always be at 50%. Am i correct ?
@realpars
@realpars 2 года назад
Hi @jbpilon2. Thanks very much for your question. I’m not sure what you mean by “each scan” as an analog control loop is continuous. In any control loop, it is desirable that the controller output (CO) never reaches 100%, or 0% as the final actuator is at maximum or minimum. If that happens, the controller has no further effect on the PV. In a perfect world, let’s assume the CO is at 50% for a PV of 50%. We want to ensure that the Gain is not high enough to drive the CO to 100% or 0%. I’m not familiar with the E5AR Omron controller but I assume it is a temperature controller. I’d be interested in hearing more about the “manual reset value” that you describe. In most PID controllers, the term “reset” is another name for “Integral” or the “I” in PID. I’m looking forward to your response.
@jbpilon02
@jbpilon02 2 года назад
@@realpars Hello, interesting conversation. In math calculation, if i programmed the formula CO=CO+(gain x error), at each scan of the computer, CO will augment. I think we retreive a parameter like "manual reset value" in many controllers. It is a fixed value and it is used to manually remove the error when the process has reached his stability. When error=0, the output will continu to be activated with the manual reset value. In some controller, we also retreive the parameter "automatic reset" which is another name for the integral. So the formula could be CO=MRV + (gain x error). MRV = Manual reset value. Thank you again for the video. I wil use it in my courses. JB
@kimaipet
@kimaipet 2 года назад
@@jbpilon02correct formula is CO = gain * error
@jbpilon02
@jbpilon02 2 года назад
@@kimaipet Hello, What's happen when the error=0 ? No command ? Even if the error=0, we need a command to maintain the temperature=set point. In a Proportionnal control loop, the manual reset value will do it. CO=MRV+(gain x error). So if error=0, CO=MRV.
@kimaipet
@kimaipet 2 года назад
@@jbpilon02This is the main disadvantage of P controller. It always has offset error.
@mohammadibrahim-om9qe
@mohammadibrahim-om9qe Год назад
Ia have a question please. I deal with PID level actuator, I put the set point (it's level controller). The problem is when tge the PV varies, the actuator goes to it's maximum output (fully closed or fully open) 0% to 100%. this leads to a big oscillating in flow rate, even when using a small gain, what can I do to get semi stable level and flow rate?
@realpars
@realpars Год назад
Hi mohammed ibrahim. Thanks for contacting us. I can’t answer straight away as I don’t understand your loop quite yet. I’m not sure what your PV is. Are you measuring level or flow? Are you controlling level or flow? Is the flow rate you refer to a measure of the flow going through a pipe and into a tank where the level is being controlled? Is the flowrate a measure MV of a flow transmitter? I’ll keep an eye out for your replies.
@hamdaniyusuf_dani
@hamdaniyusuf_dani Год назад
I had some similar problems many years ago. It turned out that the cause is in control valve positioner's settings and pneumatic connections to the actuator. Can you control the opening of the control valve manually? Try to send 4 mA (0%) to the positioner, then increase it bit by bit, to 25%, 50%, 75% and 100%.
@mutiuadegboye3827
@mutiuadegboye3827 2 года назад
Can you please tell me the software/tool you used to design your figure (figure at 1:50)?
@realpars
@realpars 2 года назад
Hi Mutiu! Thanks for your comment! I am actually not sure about that as all our designs are created by our Graphic and Animation department.
@isakoqv
@isakoqv 2 года назад
Great way to gain some intuition! Maybe do a crash course on model predictive control when you're done with PID?
@realpars
@realpars 2 года назад
Thanks for the topic suggestion! Great one, I will happily pass it on to our course developers. Happy learning and thanks for sharing!
@mutugimaina7841
@mutugimaina7841 2 года назад
How does simple water purifier machine operate. Explain each parts function .
@realpars
@realpars 2 года назад
Thanks for your feedback and suggestions, Kennedy! I will happily pass this on to our course developers for possible future video courses. Happy learning!
@prasadadavi6618
@prasadadavi6618 2 года назад
Hi, can you please help me understand the root cause of offset?
@realpars
@realpars 2 года назад
Hi @Prasad Adavi. That's a tough question to answer quickly. In a nutshell, the controller's proportional action acts on the error signal and does its best to bring the PV back to SP. Unfortunately, after its' initial action, the PV does not reach the SP and no further action will occur. That's why Integral action is introduced. Integral action will continue to move the controller output until the PV does equal the SP and offset is eliminated.
@alexcaceres3060
@alexcaceres3060 2 года назад
💓
@clsullad
@clsullad 2 года назад
Please make videos on omron plcs , Thank you
@realpars
@realpars 2 года назад
Thanks for your topic suggestion, Chinnaraj! I will pass it on to our course developers. Happy learning!
@clsullad
@clsullad 2 года назад
@@realpars Thank you so much for your consideration , looking forward for Omron plc topics
@Korystuwatch42
@Korystuwatch42 Год назад
4:32 Are you sure there is no calculation mistake? Because if the SP is 20, and the PV is 0, we get an error of 20. Multiply it by the Gain of 2, and we get 40%. 50%+40% = 90?
@realpars
@realpars Год назад
Hi there. You have a good eye. Thanks for reaching out. There is an error in the graphic. Please refer to 4:46. The SP window shows an SP of 20. The SP window should indicate 10, not 20. The video narrative states a SP change of 10. The Error value in the calculation is 10. If the SP was changed by 20, we would get an error of 20. And, if we multiplied by 20, we would indeed get an increase in output of 40%.
@mike-EE
@mike-EE 2 года назад
cant wait for the integral. the most difficult part
@AlexandreSantos-gg9il
@AlexandreSantos-gg9il 2 года назад
Could you do a video on safety relay? from Brazil, thanks
@realpars
@realpars 2 года назад
Thanks for the topic suggestion, Alexandre! Will happily pass it on to our course developers. Happy learning!
@laithjawad9208
@laithjawad9208 2 года назад
This is FT200 flow transmitter not DP . Thanks
@realpars
@realpars 2 года назад
Hi @laith jawad. Hey....thanks for your feedback! You are correct. FT200 is indeed a flow transmitter. At the same time, it is a differential pressure (DP) flow transmitter. The high and low ports of this DP flow transmitter are located on either side of an orifice plate.
@enginerepairguy
@enginerepairguy 2 года назад
It sad as a student that you charge yearly for your pro subscribtion. Its amazing value but a bit steep as an student for a whole year 😔
@realpars
@realpars 2 года назад
Thanks for your comment! We understand this price is not always doable for everyone. We do also offer a monthly subscription plan, which is €19,99 per month, but can be cancelled on a monthly basis. Luckily, we provide new video courses each week for free on our RU-vid channel. Hopefully, you are able to join our course library soon!
Далее
PID vs. Other Control Methods: What's the Best Choice
10:33
What is a PID Controller? | DigiKey
22:19
Просмотров 70 тыс.
СМОТРИМ YOUTUBE В МАЙНКРАФТЕ
00:34
Просмотров 1,4 млн
How Flow Meters Work
6:09
Просмотров 571 тыс.
How to Tune a PID Controller
8:43
Просмотров 776 тыс.
PID Math Demystified
14:38
Просмотров 461 тыс.
PID Controller Explained
9:25
Просмотров 808 тыс.
Empirical PID gain tuning (Kevin Lynch)
7:08
Просмотров 157 тыс.
How to Determine the Motor Size for Your Project?
15:08
How to Program a Basic PID Loop in ControlLogix
13:12
Просмотров 376 тыс.
Tuning A Control Loop - The Knowledge Board
21:51
Просмотров 438 тыс.
Thermocouple Explained | Working Principles
7:51
Просмотров 143 тыс.
СМОТРИМ YOUTUBE В МАЙНКРАФТЕ
00:34
Просмотров 1,4 млн