Love being an electrician in Queensland as we can totally alter your metering wiring as required. Other states in Australia they require a linesman to perform this simple task.
Noticed I misspoke some of the terminology whilst editing, mostly about our meter neutrals and the lack of circuits without RCD protection. Sorry about that meter maids and newcomers to the trade. Never knew you lot would watch this shit, otherwise I would of filmed it better; This was just for the apprentices IMHO
contact me: trev@highovoltage.com and I can sort out any electrical issues.

Опубликовано:

 

28 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 94   
@tyreecenouds6113
@tyreecenouds6113 Год назад
Those joiners are neat as will look at them next time. Keep up the great vids mate.
@mattisfahani6021
@mattisfahani6021 Год назад
No-one could better elaborate on perplexing contents than Ausie tradesmen . Always watcher-friendly and easy to follow , no wonder Australia is a great nation
@michaelcostello6991
@michaelcostello6991 Месяц назад
Very interesting to watch. Thanks
@TradieTrev
@TradieTrev 26 дней назад
Glad you enjoyed it mate!
@qwertyui90qwertyui90
@qwertyui90qwertyui90 3 месяца назад
Do you need to have the metering box on the outside of the wall ? can it be inside out of the weather ?
@TradieTrev
@TradieTrev 3 месяца назад
Yes. Must follow QEMM guide lines.
@qwertyui90qwertyui90
@qwertyui90qwertyui90 3 месяца назад
@@TradieTrev any chance of a link ? What about if you're 100% off grid not connected, just using solar + batteries
@Em-PoweringElectrical
@Em-PoweringElectrical 6 месяцев назад
Hi Trev what brand screwdrivers are them black and white ones mate? That extra long flat head looks sick 👌
@TradieTrev
@TradieTrev 26 дней назад
Nash! Local mob made a limited set, but never made money from them.
@johnlennon1151
@johnlennon1151 Год назад
Awesome video mate, so when you're Meggering your ccts at the end of the video have you just got the alligator clip on the earth bar or for each individual cct? Also sounds stupid but when you use the f set to find a cable and it shorts out, does that mean there's a short or a load on it?
@TradieTrev
@TradieTrev Год назад
Earth is earth IMHO. So if you zero out your lead and say add a short it doesn't help with your f-set.
@nigelaubrey7743
@nigelaubrey7743 Год назад
Wicked video
@MickWootton
@MickWootton 6 месяцев назад
Not trying to be an ahole, but will probably accomplish that task, but when Meggering on 250 v scale, ir reading is half the indicated reading , according to a friend 😅 (ie, 1.5 Mohm on scale is .75Mohm in reality). Nice vid btw
@TradieTrev
@TradieTrev 6 месяцев назад
Still proved the hotplates didn't test well, but totally understand the fact at the fact of the meter at scale. If I had a better job I could afford an MFT and that wouldn't be a question.
@Dog-whisperer7494
@Dog-whisperer7494 8 месяцев назад
No wonder Australia is desperate for uk sparks to move to Australia.
@TradieTrev
@TradieTrev 7 месяцев назад
What so they can make ring circuits using 32A breakers on 2.5mm2 cable with type B breakers lol?! We don't need your ill fated methods like the Americans.
@wazza33racer
@wazza33racer Год назад
Imagine the drama when all the climate warriors plug in their electric cars LOLOLOLOLOL Meter box doesnt have enough capacity, street transformer doesnt have enough capacity, substation doesnt have enough capacity, state grid doesnt have enough capacity...........
@TradieTrev
@TradieTrev Год назад
I'm using the right type of breakers here with DC blocking. Go for it! I've implemented the protection already! I could go even further also using AFDDs if you want the gold standard but most people can't afford the expense and it's not a legal requirement by law.
@jacobinglis4499
@jacobinglis4499 Год назад
Wow so much different here in VIC, you have so much freedom to get the job done
@milanmakaveli7910
@milanmakaveli7910 Год назад
Nice video! Commercial sparkie here.. 1) I never knew you could re install the metering (I thought the suppliers had to do it) 2) it looks super neat how you extended the cables. I usually use blue points (for existing solid) and inline crimps for stranded.. what did you use? They look like fixed wagos? Also those red wattmaster pliers are amazing..
@TradieTrev
@TradieTrev Год назад
1) Joys of being a sparky in QLD with the training! Some may consider me a Level 2 NSW ticket holder. 2) Inlines are dope for neatness, but takes time... Guess at commercial rates that's what you get paid for lol. Domestics are boring I'd love to play with BMS's
@shanetripley875
@shanetripley875 Год назад
The stupid thing is if you are just swapping the board over we can do that with the meters but if you are moving the board to a new location you have to organise with energex or ergon.
@TradieTrev
@TradieTrev Год назад
@@shanetripley875 I don't see how being in Energex or Ergon areas if you're approved to do linework that's an issue. It was part of my apprenticeship relocating metering when subdividing properties.
@mwethereld
@mwethereld Год назад
fitter mechanic here, ive done heaps of metering and just call ergon/energex to reseal the meters, give em my lic number, never been an issue. so i dunno, im not a level 2 sp...
@Craigy82
@Craigy82 Год назад
Technically only the metering provider is meant to move meters, Energex previously didn't care much but now there are other players they are cracking down on it.
@Craigy82
@Craigy82 Год назад
Should have put some hair around that primary fuse holder for old mate😆 But on a serious note, lovely job mate👍
@TradieTrev
@TradieTrev Год назад
There's a follow up video where I rectified some wiring on this board following our local guidelines, ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE--ri4Dn5EPWA.html The apprentice found the flex I used originally in a roof space, left overs from someones solar job. I like to be resourceful and not waste copper.
@michaelwiseman6055
@michaelwiseman6055 Год назад
Gee that was painful, watching you knock those bricks out with a claw hammer. But everything else was a dream run and beautifully done. Good one Chief!
@TradieTrev
@TradieTrev Год назад
Boss didn't supply us with better tools TBH. I own a few sledge hammers myself but wasn't in the tool kit at the time.
@nicholaskeur
@nicholaskeur Год назад
upvoted for the algorithm
@username22199
@username22199 5 дней назад
What the p/n for those WAGO lever terminal blocks? I can’t find them.
@Chris-op7yt
@Chris-op7yt 24 дня назад
why the heck they make them recessed into walls? they could just make them face mounted sturdy instead. that way you could change over to whatever new size and not have to deal with bricking. does code require recessing?
@1Odama
@1Odama 10 месяцев назад
nice one cheers .... need a bigger hammer and grinder!! Old meter......
@TheLionsDenNews
@TheLionsDenNews Год назад
I just imagine big ass spiders hiding in those switch boxes.
@TradieTrev
@TradieTrev Год назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-XVkMOJ7A7x0.html yeah spiders we get, pointy ends are important!
@pchobo
@pchobo Год назад
Better than most 'upgrades' mate. No shoving an 8 pole enclosure in the old federal gap and walking away.
@TradieTrev
@TradieTrev Год назад
The meter maids would spit mdf chips at any contractor that would do that! They'll just defect it and the person has to pay twice!
@shiamjad
@shiamjad 2 месяца назад
what a weird place for the fuse.......... very dangerous
@TradieTrev
@TradieTrev Месяц назад
It's an isolation link; Read up on QEMM as it proves my install is legit.
@mwethereld
@mwethereld Год назад
super stoked, and super proud. Im not a fan of Voltex, but each to their own. Nice upgrade there mate.
@TradieTrev
@TradieTrev Год назад
If you've got a better job offer that pays over 80K I'm interested, just using what is provided to me as an employee.
@DeejayManii
@DeejayManii Год назад
@@TradieTrev can we get your take on voltex? a full teardown would be good
@TradieTrev
@TradieTrev Год назад
​@@DeejayManii It's a mixed mash, I guess they employee some young EE's fresh out of uni with no real world experience and us Tradies tell them like it is. There's been many of times I have a whinge, but it's the clients warranty that beats the top dogs everytime and the only reason why I keep using the junk. Latest one for me was the new "Voltex branded" solid mounting blocks with a different thread than we'd use traditional, it seems like they've got some good ideas but poor execution.
@Cymaphore
@Cymaphore Год назад
That sidecutter! Poor little thing is longing for some oil and cleaning! Thanks for the video, interesting to watch!
@huxelectrical531
@huxelectrical531 6 месяцев назад
That's actually epic work mate, well done!
@Dermtarbo
@Dermtarbo 4 месяца назад
Just curious, mate, was there a reason why chose parallel 4mm for the metering
@Dermtarbo
@Dermtarbo 4 месяца назад
Also with the stove joiner, how did you archive that? Connectors soldering?
@TradieTrev
@TradieTrev 26 дней назад
Min spec requirements and allows fora 3 phase and fast charging of EVs over 3 phases. Should the client want to change when I know 3 phase is in the field.
@deki-erena6291
@deki-erena6291 Год назад
Thanks mate
@jjessa
@jjessa Год назад
Thanks for the informative video. Is the meter upgrade then done separately? And is the preferred order first the switchboard, and then (smart) meter upgrade?
@TradieTrev
@TradieTrev Год назад
Dependant which state you're in will give you the best outcome. Knowing your local rules is super important, I have an anecdote telling you like it is: ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE--ri4Dn5EPWA.html
@Tonksyyy_
@Tonksyyy_ 10 месяцев назад
I’m just a boring commercial sparky but fuck me that’s a clean install compared to any other domestic board upgrades I’ve seen, love the wagos how good
@TradieTrev
@TradieTrev 10 месяцев назад
Always happy to preach about switchboard methods brother. I took a huge chunk out of and there's a follow up video where I fucked up in the wiring; Even quote standards. I always love commercial projects with some mad lighting automation; Hook a brother up!
@thaddeuspoole1704
@thaddeuspoole1704 6 месяцев назад
Can you pull pole fuses in qld as a regular sparky, or do you have an endorsement/ higher qualification?
@TradieTrev
@TradieTrev 6 месяцев назад
For sure mate! Done it since I was a first year; I'm a bit pissed why others can't do the same with some training. I've had my whinge why even us Aussies don't own our own grid if you look back further in my vids.
@crichton269
@crichton269 Год назад
Nice job ! I need to get this done on my home in Logan , how much Am i looking to pay just a a rough ball park figure ?
@TradieTrev
@TradieTrev Год назад
Logan is a bit far for me. Key points that'll change your price significantly is the location and existing mains conductor size. If the switchboard isn't located within 3mtrs of the property from the front, say in the backyard; You'll need a mains upgrade prior, unless you never want solar. Personally I like to future proof things, at the most with the hardest of tasks I couldn't give a genuine quote without looking at the job at hand. Keep that in mind others will try, but your best person is someone who scopes out the job properly in the first place to give an accurate assessment.
@damianhackett4761
@damianhackett4761 Год назад
Very neat, mate. Good stuff
@falseprofit4u
@falseprofit4u 6 месяцев назад
Nice work, It's always a chore removing the old "wheat bix" backed enclosures with the friable asbestos fireproofed ceramic fuse load centres from 60s-70s brick veneer walls, that RCD enclosure mounted in the bottom isn't uncommon to find and is dodgy work at best. Definitely overdue for the much needed upgrade😊 I had a job recently where past lazy electricians just added a seperate 300mm X 300mm enclosure to one side for the 90s legislated mandatory RCD additions to tenanted residences instead of upgrading to a standard domestic consumer enclosure with hinged panel and seperate load centre, which is basically unchanged from the 80s. I do prefer the new Hager enclosures with the twin 12 pole load centres and a six pack cheaper than the B&R unit old school DIN rail with metal escutcheon panel.
@TradieTrev
@TradieTrev 6 месяцев назад
Out of all my electrical videos people love me ripping out the old gear for new. This is how we modernise old homes to current standards!
@falseprofit4u
@falseprofit4u 6 месяцев назад
​@@TradieTrev Amen 🙏 to that, no comprise for quality work.😊
@bradleywilson6796
@bradleywilson6796 Год назад
i would never let you work on my house
@TradieTrev
@TradieTrev Год назад
You have rights also being in a housing commission property. www.qld.gov.au/housing/housing-providers-investors/community-housing-providers Let a tradie do his job to ensure safety of your family and friends!
@MitchellJackson-ow7ey
@MitchellJackson-ow7ey Год назад
where are the inline connectors from? They look neat!
@TradieTrev
@TradieTrev Год назад
Aliexpress, but I always test the crap out of them before I'm confident using them on a job. Typically tug/wank test works. The Chinese have been getting decent making them, but it's a mixed bag.
@lhaneyleofa7685
@lhaneyleofa7685 Год назад
How do you do ya polarity tests?
@TradieTrev
@TradieTrev Год назад
Disconnect the neutral & earth, use the earth as reference should be no voltage between neutral and earth and voltage present between A+E and A+N. If there is voltage present between N+E you've screwed up polarity ;) AS3017 details it further for your own knowledge.
@bonaminhrasmey42
@bonaminhrasmey42 11 месяцев назад
Wear your gloves young boy 😊
@TradieTrev
@TradieTrev 11 месяцев назад
Which dinosaur did you come from with all that liney talk? Agreed, but PPE is the last measure in risk management.
@bonaminhrasmey42
@bonaminhrasmey42 11 месяцев назад
I'm good enough for your grandparents 😌
@garycollinge633
@garycollinge633 Год назад
Nice work
@TradieTrev
@TradieTrev Год назад
Cheers Gaz!
@jarradwilliamson9830
@jarradwilliamson9830 Год назад
Nice work. How did you mount those wagos?
@TradieTrev
@TradieTrev Год назад
WIth a bootlace crimper like you would normally.
@jarradwilliamson9830
@jarradwilliamson9830 Год назад
Sorry how did you fix them to the back of the board? Some sort of bracket?
@BronsonTheCat
@BronsonTheCat Год назад
Nice devices!
@TradieTrev
@TradieTrev Год назад
The rcbos are much safer than wire fuses, but I love the traditional mechanical meters.
@BronsonTheCat
@BronsonTheCat Год назад
@@TradieTrev Yeah the old ceramic fuses should be confined to museum pieces. The old meters are brilliant devices. Good to see you passing your knowledge onto an apprentice. We need more people like you in this country!
@IAmThe_RA
@IAmThe_RA Год назад
What are those connectors with orange levers called?
@TradieTrev
@TradieTrev Год назад
Fakeos aka China alternative to Wagos. It really tidies up extending the wiring.
@IAmThe_RA
@IAmThe_RA Год назад
@@TradieTrev I won't use them in real installations bro. Are you allowed to use them in Australia? Where I live a product must be certified in order to use them legally.
@TradieTrev
@TradieTrev Год назад
​@@IAmThe_RA Why not? I thoroughly test batches prior to installation, also what public indemnity insurance is for. If you want to get picky I've demonstrated my EE skills in the Shed automation series and would design my own electrical products given the chance.
@IAmThe_RA
@IAmThe_RA Год назад
@@TradieTrev Just saying it's against code here. Every product used must be ENEC certified.
@TradieTrev
@TradieTrev Год назад
@@IAmThe_RA See I've mitigated the risk by testing the device prior, I've followed the same guidelines SAA use to get Aussie approvals. You'll see some more in depth testing of EMI & RFI on my automation control panel, I may not be an EE but I know the process to obtain approvals here locally.
@mrseanpride6449
@mrseanpride6449 Год назад
what size cable takes those rcd neutral from the busbar back up to the neutral link? i havent use one of those combination line and neutral bus bars
@TradieTrev
@TradieTrev Год назад
4mm2 flex, it's got a similar rating compared to 6mm2 building wire when looking at 3008 for the small distance used.
@TradieTrev
@TradieTrev Год назад
I parallel it up also, good for 63A easy.
Далее
How To Wire a Switchboard (Part 1)
23:34
Просмотров 178 тыс.
КОТЯТА В ОПАСНОСТИ?#cat
00:36
Просмотров 921 тыс.
Main switchboard upgrade
11:17
Просмотров 4,3 тыс.
Electrical Wiring Basics
23:40
Просмотров 2,9 млн
How to become a sparky in Australia | ONSITE CHAT
11:15