setting off fire sprinkler and fire alarm system activation. Testing my sprinkler system 

NIC’S - SYSTEMS & ELECTRIC
Подписаться 28 тыс.
Просмотров 39 тыс.
50% 1

Развлечения

Опубликовано:

 

3 июн 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 136   
@nics-systems-electric
@nics-systems-electric Год назад
I know in this video I said I was happy with the flow rate and coverage however I've decided I need more so I will be making more videos in the future of getting more flow out of the system I have done the work already the videos will be coming out in the next couple months
@ThetrainguyYT
@ThetrainguyYT Год назад
16:54
@ForTheBirbs
@ForTheBirbs Год назад
Hi from Sydney, Australia. I worked in the fire research area of Aus Govt primary research organisation. A bit of trivia - Australia has the oldest sprinkler systems in the world, and no deaths in a sprinklered building. Cheers!
@That_2_guy2T
@That_2_guy2T Год назад
That sprinkler head had a quicker reaction than I thought, Nice demonstration
@J19_vlogger74
@J19_vlogger74 Год назад
I've been told that blow toarches burn at over 3,000°F. As far as I'm aware, these are designed to activate at 155°F.
@ZakChlebowski
@ZakChlebowski Год назад
Life savers when they work, not only do they assist people get out the building, but they assist fire fighters with quickly knocking down that fire.
@nics-systems-electric
@nics-systems-electric Год назад
True
@UpcraftConsulting
@UpcraftConsulting Год назад
Only fun thing that would make the demo better. Start a little fire underneath in your fir pit we see on the patio and see how well it puts a real fire out. (do not repeat the entire test, just rig it up again the same way and turn on the water to the tripped head and see how well it deals with a real fire.
@michaelwillis9449
@michaelwillis9449 Год назад
Great video as always. I love the way you always explain things. Keep up the good work
@nics-systems-electric
@nics-systems-electric Год назад
Thank you glad you enjoyed
@MrDjaspire
@MrDjaspire Год назад
this was so freaky. As you was testing the Fire Alarm's our adjacent Apartment complex's central emergency fire alarm system which triggers EMS Dispatch sounded and there was legitimately a fire inside an apartment.
@elevatorfan1559
@elevatorfan1559 Год назад
Great video love the sprinkler activation
@nics-systems-electric
@nics-systems-electric Год назад
Thanks glad you liked it
@marcberm
@marcberm Год назад
Finally! I think we all knew this video was coming eventually lol.
@Reidsbusesanditems
@Reidsbusesanditems Год назад
Finally he’s doing it!
@CapStar362
@CapStar362 Год назад
love your videos, i bet your neighbors love you too sounding those alarms no offense intended :P
@nics-systems-electric
@nics-systems-electric Год назад
Yeah they're pretty chill it's not a good neighbourhood to move into if you are bothered by noise as there is the elementary school right behind the house on that can be a crazy place at night
@CapStar362
@CapStar362 Год назад
@@nics-systems-electric yeah, i figured as much, i can handle kids :P my daughter runs me rampant wild sometimes with her friends, but we do have a understanding, when i say lower the volume, she makes SURE to get it down. but yeah, the cardboard security alarm incident, the fire alarms.... personally, id be like, ahhh nic over there setting shit off again LOL!! I was honestly being sarcastic about that, i wouldnt bother me at all.
@nics-systems-electric
@nics-systems-electric Год назад
@@CapStar362 yeah I am a little noisy but my noise gets overshadowed by the school with the nighttime activities the most popular is jumping up on the wall and ripping the sprinkler heads off the outside setting the fire alarms off and the fire department rushing down at all hours of the night and lighting stuff on fire on the side of the building is another common one fireworks overdoses and just general people being idiots etc.
@CapStar362
@CapStar362 Год назад
@@nics-systems-electric lol
@stevo7096
@stevo7096 Год назад
enjoy your videos you are a genius (Steve Australia)
@akshonclip
@akshonclip Год назад
The only way to add a pump to increase the GPM is to add a buffer tank. You need 110 gallons reserve per head to cover 11 GPM. That’s @ 10 minutes. If the requirement is 20 minutes you need to double the reserve capacity.
@nics-systems-electric
@nics-systems-electric Год назад
I am going to start by changing the really restrictive barbed Pex fittings that restrict it down to like a quarter inch first and see if I can increase my flow that way if that isn't enough then I will have to do buffer tank for sure
@jimmyssnowremoval1075
@jimmyssnowremoval1075 Год назад
Dude needs to come to the place I work at and fix our Honeywell, alarms abs system
@GeeWillikersMan
@GeeWillikersMan Год назад
FYI if no one has mentioned it yet, garden hose has its own thread type. Next time what you want are 3/4 GHT fittings.
@nics-systems-electric
@nics-systems-electric Год назад
Yeah I was a complete idiot I completely did not think about that
@mtgau2000
@mtgau2000 Год назад
Nice video. You deserve more subscribers. New subscriber btw
@nics-systems-electric
@nics-systems-electric Год назад
Thank you, appreciate it
@TwilightVaramek
@TwilightVaramek Год назад
for years i have wanted to set up a fire alarm system i constantly brows ebay for used systems and alarms itrs all quite expensive for somone on a fixed income so i just have to live with watching thease videops insted wich i still enjoy.. would love to have a base building game were you can build a fire alarm and sprinkler and electrical system im very tehcnical minded and like to mess with that sorta thing wich is why in games such as 7 days 2 die i make complicated electrical networks through the entire base
@chrispratt7363
@chrispratt7363 Год назад
You should make a video about what is in your electrical bag please I would love to watch it keep up the good work
@nics-systems-electric
@nics-systems-electric Год назад
I will at some point
@chrispratt7363
@chrispratt7363 Год назад
Ok
@brisummer-cl3st
@brisummer-cl3st Год назад
Like I said I love your vids keep up the good work 😊
@nics-systems-electric
@nics-systems-electric Год назад
Thank you
@brisummer-cl3st
@brisummer-cl3st Год назад
@@nics-systems-electric you're welcome I will always support your channel
@2003AcuraTL
@2003AcuraTL Год назад
Nice ceiling upgrade
@Systemsensorman
@Systemsensorman Год назад
You should do a video of building those demonstration boards
@nics-systems-electric
@nics-systems-electric Год назад
They're already built
@jasonmacauley7352
@jasonmacauley7352 Год назад
Love the videos
@nics-systems-electric
@nics-systems-electric Год назад
Thanks
@tcttc5549
@tcttc5549 Год назад
You don't have to buy brand new sprinkler, you just need that rod in it and it's easily to replace you., just have to turn off the water and then put that metal piece up and put the rod in.
@oaklynnmielcarek
@oaklynnmielcarek Год назад
I don't think that's how it works. The glass rod breaks and it is put into the sprinkler during manufacturing. You'd have to buy a new rod anyway and I don't think they sell the glass rod separately but if you have done this before, I am wrong.
@nics-systems-electric
@nics-systems-electric Год назад
If it was only for demonstration sure you can put some thing in but the sprinkler won't activate at its design temperature anymore and would be pointless you can't unscrew the retaining set screw in the sprinkler it is filled with a resin the way that I have done it just for demonstration is to put a small bolt and nut in place and tighten it where you can pull it out not a perfect seal though only good enough for a couple minutes until you pull it out
@psirvent8
@psirvent8 Год назад
@@oaklynnmielcarek Here in France they actually sell similar rods as a spare for smoke vents. These are basically roof windows or skylights that are opened by pneumatic cylinders and CO2 cartridges. Manual stations allow to open the smoke vents by pulling a handle that will puncture the cartridge, however there are also automatic devices that have a glass vial (or "rod") like sprinkler heads, except their failure will not release water but a spring-loaded pin that will puncture another CO2 cartridge in order for the smoke vents to open on their own as well. These vials also come in various colors, one for each temperature, just like sprinkler heads. They are really meant to be replaced individually as well as the CO2 cartridge since the actuating device itself is reusable. Not sure if these vials would fit on sprinkler heads though.
@richthepontiacguys1412
@richthepontiacguys1412 Год назад
Not many people demonstrate that cool
@nics-systems-electric
@nics-systems-electric Год назад
I'll be doing more once I upgrade the water and have more flow
@SOU6900
@SOU6900 Год назад
10:17 Where'd you get the Canadian National step? I want a Southern one if its from an online store.
@Bdf3604
@Bdf3604 Год назад
I was a Firefighter for 23 years. Stopping the water coming out of a sprinkler head sucks. But if the sprinkler head gets knocked off accidentally, you have to stop the water to prevent property loss.
@Sdifirealarms
@Sdifirealarms Год назад
Nice video !
@nics-systems-electric
@nics-systems-electric Год назад
Thanks
@r3tr0nic
@r3tr0nic Год назад
Garden hoses use GHT (Garden Hose Thread) whereas pipes use tapered threading (NPT in USA/Canada and ???, BSP elsewhere). Usually when I need flexible hose to attach to piping, I'll use barb adapters and hose clamps. These are usually carried in most hardware stores. You just have to make sure what you use is meant for piping, and not garden/lawn. One scenario where GHT is used, is typically hot water storage tank drain valve. I have not added sprinkler system to my home, though I contemplating it. I have an unusual situation, where there are 3 booster pumps the size of a large cargo van each that were recently added at the end of my block (in a faux house)... and I found out from my local water council that my home's feed is tied into a 200mm (8 inch) main, just 30 meters (100ft) from my house. I had to use 2 PR valves to reduce my pressure to normal domestic levels... Due to burst flex pipes in dishwasher after water council added these pumps/booster station. I hooked up a 100PSI gauge and it pegged. 200PSI gauge... it pegged it... Finally I added a large 2000kPa fire sprinkler gauge and it nearly pegged it. Gauge only has kPa markings, but doing conversion, this was near 300PSI! Come to find out after council did an evaluation around the block, that someone had connected my main where it wasn't supposed to be, and council moved it to a 100mm/4 inch feed. However, pressure still is over 1700kPa(250PSI). Bad for house, but tempted to test and see how it performs with sprinklers tehehe! I remember watching the pump station being built, and somewhere still have photos of the in and out supply piping to that place. The pipes were almost 1 metre in diameter. Absolutely huge
@nics-systems-electric
@nics-systems-electric Год назад
Yeah, I learned that after the fact I should've known better. I do need to find some sort of adaptor for sure. and that definitely does sound like an interesting situation at your home!
@glonkfpv
@glonkfpv Год назад
You have 250PSI of water pressure in your home?
@nics-systems-electric
@nics-systems-electric Год назад
@@glonkfpv yeah that would be insane highest I've seen in a house is 120-130 psi
@glonkfpv
@glonkfpv Год назад
@NIC’S - SYSTEMS & ELECTRIC On a well, right in the well room, I see around 75 or so after it replenishes the pressure after a shower or something. 250 would have explosive results on a shower or at a sink faucet, let alone a fire sprinker.
@r3tr0nic
@r3tr0nic Год назад
@@glonkfpv Had, yes. unfortunately... I came home to a flooded kitchen and laundry room because the hose for the dishwasher burst, and the valve in the washing machine (modern plastic crap) also burst. That's when I went through the gauges, upping in size until I did not peg them anymore and was blown away by what I was seeing... I also had wierd pulsations in the pipes. I can only surmise this is due to however the council runs the pumps (the system that controls the demand of them and operating parameters). I do not know what they run, but it seems as either there is an out of balance issue between the three pumps, there is harmonic resonance/feedback loop in supply piping, or something else. The pulsations stopped after council changed me to a smaller mains tap. Craziest thing I ever seen. All the piping in my house is copper and soldered. No PEX, push fits/sharkbites or any of that kind of stuff.
@BR-ft2xg
@BR-ft2xg Год назад
The test would have been more fun had it been one year old black stagnant water first coming out. 😂….
@raiden-shogun200
@raiden-shogun200 Год назад
Nice video
@Mikey_the_Protogen
@Mikey_the_Protogen Год назад
No it isn't usually glued it's usually so u don't have to even remove the whole sprinkler as long as you have the plug.
@Dave-uj8fs
@Dave-uj8fs Год назад
How long is a water flow switch supposed to take to activate in Canada? NYC requires 30-90 seconds.
@nics-systems-electric
@nics-systems-electric Год назад
They have to be set at no more than 90 seconds
@Roxy_gacha24
@Roxy_gacha24 Год назад
Hey nic, love the videos. That sprinkler really spewed didn’t it? Lol! You are great at testing this stuff. See you in the next one. Also, /e pin
@SodiumInduction-hv
@SodiumInduction-hv Год назад
L
@That_2_guy2T
@That_2_guy2T Год назад
Series
@SodiumInduction-hv
@SodiumInduction-hv Год назад
@@That_2_guy2T 😂 😂 😂
@Mikey_the_Protogen
@Mikey_the_Protogen Год назад
Our high school has FM-100 gas release for the one specific room
@psirvent8
@psirvent8 Год назад
One with computers perhaps ?
@Mikey_the_Protogen
@Mikey_the_Protogen Год назад
@@psirvent8 That's what I was thinking, it could be where the main hub for the internet for the school district is at.
@An_Official_Scratcher
@An_Official_Scratcher Год назад
So that will keep spraying as long as you don't turn off the sprinkler line or the main water in line?
@nics-systems-electric
@nics-systems-electric Год назад
Yes
@gradymcclintock6160
@gradymcclintock6160 Год назад
I never seen these tested before
@NiddNetworks
@NiddNetworks Год назад
You said you might need to buy new heads... Over here in the UK you can buy replacement triggers and parts, keeping the main casting in place - surely cheaper? Do you not have that in Canada? (Obviously if activated due to a real fire you wouldn't recycle, that's a given lol)
@nics-systems-electric
@nics-systems-electric Год назад
Some of them I think you are able to replace the bulbs however not these ones they have a resin filling where the set screw is I'm not sure if it would be legal to replace your own glass as that may be altering the device I have a feeling CSA would not allow that and you would need to replace the whole thing
@NiddNetworks
@NiddNetworks Год назад
@@nics-systems-electric thanks for responding. I'm not in the business, so I don't know the ins and outs of what's allowed, but I came across a box of "sprinkler spares" in a plant room I was clearing - there were heads, adapters, and a couple boxes of glass vials, with a temperature rating. I wonder if there just for accidental activations. They could also have been a throwback to years gone by, as the system had long since been fully drained... Love the videos regardless!!!
@Turkeyman16286
@Turkeyman16286 Год назад
Awesome video
@nics-systems-electric
@nics-systems-electric Год назад
Thank you
@Turkeyman16286
@Turkeyman16286 Год назад
You welcome
@dennisnichols7123
@dennisnichols7123 Год назад
No delay on your flow switch? That can be a source of false alarms if city water pressure is fluctuating
@nics-systems-electric
@nics-systems-electric Год назад
No delay no, a slight delay would be nice but it hasn't caused any problems yet
@BR-ft2xg
@BR-ft2xg Год назад
I’m surprised that there is no delay. Usually there is a dial to adjust the timing. I always had to have fire alarm activate within 90 seconds of a sprinkler head going off to meet NFPA. This delay in the alarm allows pressure fluctuations. I also don’t see a backflow preventer. This keeps the stagnant water from getting sucked back into the city water supply if there was a water main break. First time seeing this channel and very intrigued by why a residential house is set up like a commercial building with em light, fa panel, smokes, sprinklers, signage. Just curious as to why? Also the horn strobe combo on the outside is usually mounted above the FDC fire department connection so they know where to hook up the pumper. I bet the neighbors love it when you are testing the system. I honestly haven’t seen a house set up like this before.
@enricodigi
@enricodigi Год назад
What’s that white box mounted to the back of the fire alarm panel?
@nics-systems-electric
@nics-systems-electric Год назад
What I used to receive messages if it goes into an alarm
@jody5661
@jody5661 Год назад
I thought that was going to be more of a gentle water fall rather than a aggressive spray. Tho that does make sense
@GothGuy885
@GothGuy885 Год назад
I have forgotten what liquid is in the glass vials? alcohol / acetone? from my studies a few years back each color represents a certain burst temperature and each vial color has a different sized bubble in them for expansion, to make them go off at that temp
@nics-systems-electric
@nics-systems-electric Год назад
It's glycerin-based that's all I know
@GothGuy885
@GothGuy885 Год назад
@@nics-systems-electric ok thanks Man 😀
@Fire_Alarm_Duude
@Fire_Alarm_Duude Год назад
So excited
@VOLTRONDEFENDER4440
@VOLTRONDEFENDER4440 Год назад
Nic did you see what I posted for fire alarm related on my community post?
@bigfoot13s80
@bigfoot13s80 Год назад
Nic you are super amazing with your videos. I love watching them. I was wondering have you considered the concealed sprinkler heads for your drop ceiling area?
@nics-systems-electric
@nics-systems-electric Год назад
The concealed ones take up a lot of room in the ceiling I would have to make the whole ceiling lower for them
@bigfoot13s80
@bigfoot13s80 Год назад
@nics-systems-electric also is there anyway I can chat with you? I have questions about security systems
@nics-systems-electric
@nics-systems-electric Год назад
@@bigfoot13s80 I am not too experienced with security systems though you can privately message me on Instagram
@josephfrye7342
@josephfrye7342 Год назад
i would say in the green hill/emerald hill community college career center services building will use the johnson controls water aqua-mist fog system series besides these traditional fire sprinklers. since it will reduce the flood and electrical water damage ish hazards. which would be a more efficient and safer alternative to reduce and minimize the risk.
@nics-systems-electric
@nics-systems-electric Год назад
I don't know how much I trust those they say they use less water but at the end of the day it's pretty simple the more water you get on the fire the better sprinklers are supposed to put out a lot of water the only place I would see them being acceptable is may be server rooms and similar
@Twentytwo22-entertainment
@Twentytwo22-entertainment Год назад
How did you get the WF delay?
@nics-systems-electric
@nics-systems-electric Год назад
There is no delay it's programmed just as straight water flow
@thomaswhitten468
@thomaswhitten468 Год назад
5:06, not only it would make a mess but it would cause water damage and possibly mold, good idea to do it outside
@psirvent8
@psirvent8 Год назад
Actually, setting it off and shutting the valve RIGHT AWAY wouldn't be worse than say, dropping a water bottle on the floor, or accidentally splashing water while doing the dishes or cooking, see what I mean ? Basically everyday mishaps that don't usually end up with mold or even much damage at all except perhaps if electronics or unsealed wood get wet, it might leave some spots for the latter at most. ( *Read more* ) Sure, it would be annoying to mop the water, however it's not like a commercial system that will pump way more water every second and will keep flowing for hours until the arrival of the fire department and building manager or whoever has the rights to shut down the system.
@thomaswhitten468
@thomaswhitten468 Год назад
@@psirvent8 i got you, makes sense now, thanks
@ObamnaSoda513
@ObamnaSoda513 Год назад
are you gonna start uploading more often because you dont usually upload on sundays
@nics-systems-electric
@nics-systems-electric Год назад
No I just have extra videos that need to get out of the way
@FirealarmJae
@FirealarmJae Год назад
Wet location shouldn’t that be seal tight?
@nics-systems-electric
@nics-systems-electric Год назад
What do you mean by that?
@FirealarmJae
@FirealarmJae Год назад
@@nics-systems-electric non metallic raceway, I’m just giving you a hard time. Nice set up
@nics-systems-electric
@nics-systems-electric Год назад
@@FirealarmJae if you're referring to the EMT on the wall you can absolutely use EMT outside with rain tight fittings it just isn't rated for burial
@FirealarmJae
@FirealarmJae Год назад
@@nics-systems-electric 👍
@Random_Emergency_Light
@Random_Emergency_Light Год назад
Today is my birthday
@nics-systems-electric
@nics-systems-electric Год назад
Happy birthday
@brandongotzpowers
@brandongotzpowers Год назад
It needs a little more pressure just a bit
@nics-systems-electric
@nics-systems-electric Год назад
Flow not pressure needs more flow
@brandongotzpowers
@brandongotzpowers Год назад
@@nics-systems-electric yes it needs a bit
@user-lv9zh3yr9j
@user-lv9zh3yr9j 4 месяца назад
Okay that's a good comment
@Honekawasuneo646
@Honekawasuneo646 2 месяца назад
It can recycle, I recycle it into water plant system
@Splintza1
@Splintza1 Год назад
Ayy yo
@Sonic_withShadow
@Sonic_withShadow 29 дней назад
16:54
@a.r.aproductions1569
@a.r.aproductions1569 Год назад
Nic👏🏻does👏🏻not👏🏻miss👏🏻
@nics-systems-electric
@nics-systems-electric Год назад
Thanks Bro
@SodiumInduction-hv
@SodiumInduction-hv Год назад
Where did my other comment go?
@psirvent8
@psirvent8 Год назад
It could have been deleted automatically or manually if it contained something like a link or a curse word, or even if you edited it too many times in a row. Happens to me quite often.
@SodiumInduction-hv
@SodiumInduction-hv Год назад
@@psirvent8 oh
@psirvent8
@psirvent8 Год назад
@@SodiumInduction-hv Yes ! That's annoying to be honest (And polite, otherwise my comment wouldn't be visible either).
@sharnimassey4969
@sharnimassey4969 Год назад
Fun way to water your grass
@nics-systems-electric
@nics-systems-electric Год назад
For sure
@Bluscream
@Bluscream Год назад
Your poor neighbors
@fredandtillychatfield7867
@fredandtillychatfield7867 Год назад
Falling off for
@fredandtillychatfield7867
@fredandtillychatfield7867 Год назад
Microsoft is to the best thing about you can use,so ujbmoj?oh well done for your yes I'm sorry I've ever
@trainsandplanesproductions2004
16:54
@connorwelsh1
@connorwelsh1 Год назад
16:54
@fortniteinminecraftt3794
@fortniteinminecraftt3794 Месяц назад
16:54
@dand2559
@dand2559 5 месяцев назад
16:54
@biggreenhat
@biggreenhat Год назад
16:54
@lucasmessink9326
@lucasmessink9326 Год назад
16:54
@ChristianGammad-yf1rq
@ChristianGammad-yf1rq Год назад
16:54
@20v552
@20v552 Год назад
16:54
@karimalvarado7098
@karimalvarado7098 Год назад
16:54
Далее
Testing of the new demo Board  with CJ9899
9:16
Home Fire Sprinkler Demonstration
13:17
Просмотров 1,1 млн
How to change out bad fire sprinkler head.
18:32
Просмотров 7 тыс.
Fire alarms going off! false fire alarm.
14:41
Просмотров 26 тыс.