Supplementary Protective Bonding and Touch Voltage 

JPElectric
Подписаться 7 тыс.
Просмотров 6 тыс.
50% 1

An overview of the testing procedure for supplementary protective bonding.
I also talk about "My' take on touch voltage. Comments on this most welcome, as I find it a complex issue.

Опубликовано:

 

4 июн 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 26   
@RaxTubeYou
@RaxTubeYou 4 месяца назад
Wow and wowsers, the BEST detailed explanation and I've seen 10's of tutorials. Thank you so much and please keep up this good work!
@JPElectric
@JPElectric 3 месяца назад
Thanks RaxTubeYou, really appreciate your kind comment. Yes plan to keep on doing videos, as long as people find them useful
@cfgman1
@cfgman1 3 месяца назад
This is the only video which clearly makes the distinction between the purpose of CPC and PBC respectively - one limits the duration of the fault and the other limits the level of the fault. This is a very important concept which is quite difficult to grasp but once understood makes sense. I must admit these videos are impressive - I suspect you have taught this subject ...if not you should !
@JPElectric
@JPElectric 2 месяца назад
Thank you cfgman1, No not a teacher, just an electrician, trying to pass stuff on.
@euanwylie8046
@euanwylie8046 27 дней назад
great explanation and great work, gives me better understanding now it about main bond calc i will see in ur next vid
@RatBikerNotts
@RatBikerNotts 4 месяца назад
Thanks, finally a clear explanation.
@JPElectric
@JPElectric 4 месяца назад
Thank you RatBikerNotts
@Weaselspleen75
@Weaselspleen75 4 месяца назад
Well explained and it’s finally became clear 👍
@JPElectric
@JPElectric 4 месяца назад
Thanks Weaselspleen75, glad you found it helpful.
@eddie_pegasus_electrical
@eddie_pegasus_electrical Год назад
Good explanation on Supplementary Protective Bonding and Touch Voltage. Good revision, especially as I don't work in bathrooms and the like. Back in about the late 80s we were involved in a refurbishment of some blocks of flats 12 storeys +, we had to bond the metal window frames throughout each flat. My governor at the time with technical teams argued against it, still had to be done 🤷‍♂🤦‍♂. Thank you. 👊😎👍💙
@cestemshow
@cestemshow Год назад
Underrated video, deserves more views. Top job ❤️
@JPElectric
@JPElectric Год назад
Thanks very much, really appreciate your comment. I have been trying to put a video together for a while on transposing formula. Something I still struggle with. Looking at your channel, you have some great content on that.
@peterbradley4916
@peterbradley4916 9 месяцев назад
Surprisingly good!
@JPElectric
@JPElectric 8 месяцев назад
Thank you 🙂
@ja_adam_
@ja_adam_ Год назад
Hi, are you supposed to test between extraneous and exposed conductive parts on an EICR and EIC? I’ve never been taught to ever test if this is needed
@no_short_circuit
@no_short_circuit 2 года назад
Thanks for the video. I've always struggled with this topic but the graphics using hypothetical resistances helped. Confused when you said at 17.39 you say you can "calculate the Volt Drop on the R1 leg", then realised you'd included the external element of 0.175 ohms. Certainly helps and I'll bookmark this video for future reference. Just a quick question, why 240 volts and not 230 volts as used in most other calculations?
@JPElectric
@JPElectric 2 года назад
Thanks for the comment. I used 240, because I was using the touch voltage scenario from Paul Cooks Comment on the wiring regulations book, and he used 240V.
@ningis21
@ningis21 2 года назад
Hi...Thanks for the video. I was under the impression that 230 volts multiplied by the Cmin, was to be used in this type of callculation. ... Also, that the 50 volts was for use on a TT system, and you should use 230 volts on TN systems which if used along with an RCD would give 1667Ohms with 59 volts but 7667 ohms with 230 volts?
@JPElectric
@JPElectric 2 года назад
Thanks for the comment. You only need to use Cmin, to account for fluctuation in the supply voltage when finding Zs values. 50 volts in the maximum touch voltage allowed. The 1666 reading --- Supplementary bonding test is 50V not 59V ( 50/ 0.03 is 1666.66666...) Often rounded up to 1667. And the 230 V is for the extraneous CP test so for a 30mA RCD that would be 6.67kΩ, as you take 1000Ω off for the impedance of the human body
@heron9524
@heron9524 Год назад
@@JPElectric great video. So why is supplementary bonding test is at 50 volts? And extraneous bonding test is 230 volts? They both can indroduce a dangerous potential! I assume the supplemtary test is at 50 volts because water is more likely present! I.e water tap, radiator pipe etc.
@ja_adam_
@ja_adam_ Год назад
Can you explain how you would know if you need supplementary bonding? Are you supposed to test between exposed and extraneous part in a bathroom
@ja_adam_
@ja_adam_ Год назад
I’ve never been tought to test between tap and exposed conductive part for example? Is this always supposed to be done ?
@heron9524
@heron9524 8 месяцев назад
Best to test with a megger as in insulation resistance test.. Put one lead of the megger onto a known earth in the bathroom i.e the earth in the light fitting and test it to the extraneous conductive part i.e the Tap in the bath. If the resistance is less that 1667 ohm there is no need to supplementary bond. If the resistance is between 1667 and 22000 ohms then it needs to be supplemtary bonded. Take a 2.5mm earth from light fitting and bond to tap. 50 volts is minimum touch voltage and resistance of human body is 1667 ohm approx. Divide 1667 into 50 volts result is .02 miliamps which is 20 miliamps. All bathrooms should be 30ma rcd protected. So that means rcd will trip as resistance has a low enough value for fault current to flow.
@leroycfc
@leroycfc Год назад
Do you have an Instagram page ?
@JPElectric
@JPElectric Год назад
Hi Leroycfc, Not really, something I plan to get going.
@leroycfc
@leroycfc Год назад
@@JPElectric awesome mate ! Could you do a video to break down under floor heating systems?
Далее
Testing Zs - Why it is so important?
29:50
Просмотров 22 тыс.
Using a TT earth where a TN earth already exists
23:49
skibidi toilet multiverse 039 (part 4)
06:06
Просмотров 2,3 млн
СОБАКИ ГОЛОДАЮТ ИЗ-ЗА ЛЕРЫ 🥲
01:00
Maximum Earth fault loop impedance
27:21
Просмотров 10 тыс.
What is Electrical Bonding? Bonding VS Earthing!⚡
6:05
Where Does Grounded Electricity Actually Go?
19:36
Diverted Neutral Current - Description Overview Part 1
24:35
Earthing and Bonding Part 1 - A SparkyNinja Webinar
1:18:51