Тёмный

The cable calculation procedure for an EV (Electric vehicle) charger 

JPElectric
Подписаться 7 тыс.
Просмотров 3,9 тыс.
50% 1

A basic cable calculation guide, and some comments on installing an EV charge point.
Installing an EV charge point is not that straight forward, and new issues are coming to light all the time.
Guidance is constantly changing, so I think it's important to keep up to date with the changes, and if possible go on a recognised course provided by a reputable trainer. Such as the 2921-31 for domestic or for more complex installs 2921-32 or the 2921-33.

Опубликовано:

 

16 июн 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 21   
@no_short_circuit
@no_short_circuit Год назад
As far as videos covering cable size calcualtion go this has to be one of the best for any learner. Clear and understandable principles explained in laymans terms - thank you very much for taking the time to shere your knowledge with us.
@JPElectric
@JPElectric Год назад
Thanks again. Very kind of you to say
@jollyfinequality9865
@jollyfinequality9865 Год назад
I concur with the first two comments above. A really good breakdown of the necessary steps. Great to follow. Thank you for putting it together.
@JPElectric
@JPElectric Год назад
Thanks for watching jollyfinequality9865 really appreciate it.
@mb-electricalservices
@mb-electricalservices 2 месяца назад
I use software to carry out design calculations which is incredibly accurate and great for my clients as a full report can be sent confirming all calculations meet the requirements. The problem with this method is that, as an electrician, you become lazy and lose the ability to manually do the calculations. You've given me a bit of food for thought here because it's clear to me that I have become reliant on software. Thanks for the video. Great stuff for learners and old sparkies like myself. 💪
@angelofranklin1
@angelofranklin1 2 месяца назад
Software is great until the computer breaks down
@JPElectric
@JPElectric 2 месяца назад
Thanks very much for watching. I do like to work out with a pen and paper, then I use software to confirm my working out, and visa versa.
@mb-electricalservices
@mb-electricalservices 2 месяца назад
@@angelofranklin1 Very true!! Fair point...
@mb-electricalservices
@mb-electricalservices 2 месяца назад
@@JPElectric You're welcome bud. 👍
@Rossisearle
@Rossisearle Год назад
Been looking forward to next video.. Your layout and drawing are amazing.. very helpful
@JPElectric
@JPElectric Год назад
Thanks very much Rusko_Customs
@highgatehandyman6479
@highgatehandyman6479 11 месяцев назад
Love your vids. Im nearly able to self certify. I understand the principles of solenoid but thought a bs60898 only applied to ac circuits. But you mentioned a type A mcb because of DC currents. I would love you to discuss this topic further. Thanks for these excellent videos
@JPElectric
@JPElectric 10 месяцев назад
Thanks for the comment. We are talking about AC circuits. But lots of modern tech has electronics which produce DC current, and this can appear on the AC installation. LED lighting, EV charging, Washing machines. Basically anything with an electronic circuit can introduce DC current onto an installation. The standard AC RCD can be 'blinded' by this current i.e be desensitised, so it will not pick up an imbalance in the supply. This is how loop testing was made possible with multifunction testers (Dlock) it saturated the RCD coil with DC current to enable the loop test with out tripping the RCD. Type A RCDs can work with around 6mA of DC current, and are now currently required. AC RCD are all but extinct. Type A is also not ideal, but its what is generally available. This issue will be ongoing for some time
@highgatehandyman6479
@highgatehandyman6479 10 месяцев назад
Ok. Excellent information. Thank you !
@avantgarde70
@avantgarde70 7 месяцев назад
This is great.
@JPElectric
@JPElectric 7 месяцев назад
Thank you avantgarde70
@ja_adam_
@ja_adam_ Год назад
Great video as always, id like to politely point out though that you have It and Iz the wrong way round.. Iz is the figure you get after applying factors. It is the current carrying capacity of the cable you select from the table in BS7671 hence the term “tabulated” as it comes from a table.
@JPElectric
@JPElectric Год назад
Hi Ja_adam. Thanks for the comment My understanding is.. Iz is the current carrying Capacity for the cable for continuous service. It is the value we get, which must be ≥ the value we get by dividing the In or Ib by the relevant correction factors.
@JPElectric
@JPElectric 11 месяцев назад
Hi Ja_adam Just to clarify my answer. You are correct. The values we look up in BS7671 is the It - the tabulated value. I am doing another video which I hope will make this point clear. Thanks
@icetin9235
@icetin9235 Год назад
great explain thanks can you do about EICR VIDEOES WHAT WE LOOK FOR Many Thanks
@JPElectric
@JPElectric Год назад
Thank you , Yes would like to do an EICR video. Massive subject though. Will think on it.
Далее
How Many Amps Do You Need For Home EV Charging?
26:08
Просмотров 422 тыс.
Tom🍓Jerry 😂 #shorts #achayanarmyfamily
00:14
Просмотров 14 млн
Transposition of electrical formula  and practical uses
30:02
Home Charging Installation Risks and Advice
26:48
Просмотров 163 тыс.
Maximum Earth fault loop impedance
27:21
Просмотров 10 тыс.
The solution to external EV charging installations
9:23
Tom🍓Jerry 😂 #shorts #achayanarmyfamily
00:14
Просмотров 14 млн