Тёмный

Three-phase grid converter control: video 1 Grid tied inverters 

Franky De Bruyne
Подписаться 2,4 тыс.
Просмотров 23 тыс.
50% 1

Grid tied inverters
Equation for ippmaxL2 (37:43) is wrong ! The correct equation is in the following link. (Thank you
T3KTONIT: / @t3ktonit )
drive.google.com/file/d/191fQ...
Real-valued Fourier series: • Signals, systems and c...
Complex-valued Fourier series: • Signals, systems and c...
Sampling theorem: • Signals, systems and c...

Опубликовано:

 

9 авг 2020

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 44   
@praneethmannu6552
@praneethmannu6552 2 года назад
there is no such video explanation like this on a grid-connected inverter. elaborated explanation, constructive and sequential manner explanation.. thank you sir
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for the nice feedback.
@razimuhammad6824
@razimuhammad6824 2 года назад
excellent video, thank you for your sharing, professor! I will keep following your subjects. Respect from a Chinese student.
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for the nice comments.
@OmarBouyahia
@OmarBouyahia 3 года назад
A very good explanation, thank you so much ! we are waiting for other videos in this field !
@Nana-tq7px
@Nana-tq7px 2 года назад
Thank you very much for sharing the information really needed most these days.
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for your kind feedback. 🙏
@poopface011
@poopface011 2 года назад
wow this is an outstanding presentation of this. And you included a modelling technique... great job man
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thanks for the nice feedback !
@ayoubamayou5990
@ayoubamayou5990 3 года назад
Awesome, you’re a very good explainer 😃
@frankydebruyne9842
@frankydebruyne9842 3 года назад
Thank you for the nice comment !
@AbhishekMishra-wn3dw
@AbhishekMishra-wn3dw 3 года назад
Thank you very much sir for this beautiful video......your explanation and clarity is awesome.....thank you very much for sharing it with us....
@frankydebruyne9842
@frankydebruyne9842 3 года назад
Glad to be of help ! Thank you
@zxyll8260
@zxyll8260 2 года назад
Thank you sooooo much!
@rcinfla9017
@rcinfla9017 2 месяца назад
Tricky part of PWM output filter design is the dampening required when loads are switched off/on and when load has high crest factor with pulsing high current peaks. Sets PWM filter ringing.
@frankydebruyne9842
@frankydebruyne9842 2 месяца назад
See Video_7_Interlocks for strategies to enable the inverter appropriately.
@TuyenLe-kg9dz
@TuyenLe-kg9dz 2 года назад
22:41 Ripple current and L filter 35:46 Ripple and LCL filter
@ahmedladhibi6893
@ahmedladhibi6893 2 года назад
Thank you sir for your videos! I have a question if we connect the 3Ph inverter direct to the Grid without any Passiv filter, would be a current flow from the Inverter to the Grid? ( the Grid alone is for the inverter like an L+R : so theoretically we dont need filter for the energie flow ?)
@frankydebruyne9842
@frankydebruyne9842 2 года назад
For a strong grid, the grid inductance is very small. The current will become uncontrollable in practice. Anyway, you have to take care of the ripple on the current. You can connect a 3ph inverter directly to a motor: the motor inductance is high enough to control the current and the current riple is not an issue.
@ghayyurhassan3421
@ghayyurhassan3421 2 месяца назад
Great video, I am designing a grid following inverter. for that i want to design the PLL considering 5% of 3rd harmonics at 150Hz and 5% of negative sequence. But i don't know how i can play with my PLL to make it such. I have used SRF PLL which controls the current.
@frankydebruyne9842
@frankydebruyne9842 2 месяца назад
Thank you for your comment and feedback. You will some Information on PLLs in later videos. Best regards.
@MAFatourechi
@MAFatourechi Год назад
Many thanks. one question: if we want to connect the inverter to a 4 wire grid side, is it necessary to have a star/delta transformer with star grounded to get neutral point? can we use DC bus midpoint as neutral instead of transformer?
@frankydebruyne9842
@frankydebruyne9842 Год назад
Or you can implement a 3ph + N grid coupling; you will need four legs !
@tikuetanya6759
@tikuetanya6759 Год назад
Very powerful explanation. Please i which to model the grid tie inverter in state space. Can you help me with a video link for that. Thank you
@frankydebruyne9842
@frankydebruyne9842 Год назад
Thank you for your feedback. Unfortunately, I have no plans for a video on grid convertor control using state-space methods.
@anant814
@anant814 Год назад
Sir, your lectures are very interesting. Where I can get access for further information about your lectures
@frankydebruyne9842
@frankydebruyne9842 Год назад
Thanks for the feedback. Unfortunately the slides are for ECAM students only. I hope you understand. Regards.
@ravivarma9373
@ravivarma9373 2 года назад
Sir, Thank you so much for these wonderful videos... Will you kindly share the links for downloading the related MATLAB file folders
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for the feedback. Unfortunately, the slides and code are only for ECAM students. I hope you understand.
@ravivarma9373
@ravivarma9373 2 года назад
@@frankydebruyne9842 Ok Sir
@shubhranshuranjansharma4892
@shubhranshuranjansharma4892 2 года назад
Thanks sir for wonderful videos. Sir how I can make state space model of inverter with spwm.
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for the feeedback. From a control point of view, the inverter model is not necessary. The duty cycle can be computed from the the average inverter voltage produced by the algorithm as is shown in the videos (control perspective). You will find inverter models in the literature. I hope this is helpful.
@asarekoduah1064
@asarekoduah1064 2 года назад
I am not so clear about getting the transfer function for the VSI. can you help me
@frankydebruyne9842
@frankydebruyne9842 2 года назад
There is a transfer matrix for the LCL filter: see 49:00 The inverter is "modeled" using the very simple law linking the average Vinv to the duty cycle: see 44:00 The controller produces a Vinv (see later videos) and this has to be translated to a duty cycle using this simple law. I hope this helps.
@nashaatyaseen-suitableforp5857
@nashaatyaseen-suitableforp5857 2 года назад
Please can you inform me how can i control the magnitude and phase angle of the fault current output from inverter interfaced renewable energy Thanks in advance
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Control is considered in the next videos. But the application is grid coupling and faults currents are not considered.
@nashaatyaseen-suitableforp5857
@nashaatyaseen-suitableforp5857 2 года назад
@@frankydebruyne9842 thanks a lot Dr
@MsTroudi
@MsTroudi 2 года назад
A very good Thank you very much, Sir where have you the link of the zip file thnks a lot
@frankydebruyne9842
@frankydebruyne9842 2 года назад
Thank you for your feedback. Slides and other material are only for ECAM students. I hope you understand.
@djallaleddine1935
@djallaleddine1935 2 года назад
Hello sir i need this book please
@frankydebruyne9842
@frankydebruyne9842 2 года назад
The slides are only for ECAM students. I hope you understand.
@T3KTONIT
@T3KTONIT 6 месяцев назад
I think equation for ippmaxL2 (37:43) is wrong the modulus is : 1/|1 - L*C*Wsw^2| 😁😁
@frankydebruyne9842
@frankydebruyne9842 6 месяцев назад
Right ! Thank you for your input. The correction is in the link below.
@frankydebruyne9842
@frankydebruyne9842 5 месяцев назад
drive.google.com/file/d/191fQMYzKgCNPR55TB6eXXkIDggkm-bjN/view?usp=sharing
Далее
Three-phase grid converter control: video 2 Exercise 1
14:55
Nima ovqat qilay?😂
01:01
Просмотров 628 тыс.
Simulation of a single phase grid connected inverter
26:16
EV CHARGER TOPOLOGIES | TECH SIMULATOR
7:06
Просмотров 4,2 тыс.
Andrew Isaacs: Why Grid Forming?
37:16
Просмотров 4,6 тыс.