Troubleshooting Noisy contactor, humming contactor reasons and solutions. 

Electrical Engineering
Подписаться 20 тыс.
Просмотров 34 тыс.
50% 1

Telegram: t.me/electricalengineeringpor...
Facebook page: / electricalengineeringch
Facebook group: / electrical.engineering.ch
Twitter: / electri88225030
Troubleshooting Noisy contactor, humming contactor reasons and solutions.
If the contactor is humming, and noisy, it is a sign that you have a problem.
Check your contactor nominal coil voltage?
Normally written between A1 and A2 terminals, or the front side of the contactor.
UNDER VOLTAGE CAN GENERATE NOISY COIL.
Measure the coil voltage just the contactor is powered up.
Put the multimeter probes into the contactor terminals A1, and A2.
Power up the contactor and check the voltage measurement.
It should be more than 80%, and less than 110% of the coil nominal voltage.
For example, the contactor coil voltage is 220 volts.
So, the accepted measurement should be from 176 volts to 242 volts.
Contactors, if used in a dusty environment, are at a risk of dust deposition on the core and armature.
Dust also could generate noise during contactor power up time.
The contactors IP normally is 20, which is protecting from objects bigger than 12.5 millimeter, but dust particles are smaller than 1 millimeter.
So, to protect the contactor from dust, the enclosure must be IP 50 or more.
Mounting position also could be the reason.
These positions are permissible without derating.
But if the contactor position was one of those positions, it must be derated, for the derating percentage check the contactor datasheet.
Electrical, Power, Motor, substation, transformer, contactor, control panel, classic control, ABB, Eaton, schneider electric, siemens, contactor repair, magnetic contactor, contactor wiring diagram, contactor wiring, submersible starter, dol starter, humming noise, power contactor, electrical wiring, electrical engineering, electrical engineering basics, electrical wiring basics, electrical fails, electrical engineering day in the life ,magnetic contactor connection, electrical safety
#troubleshooting #Maintenance #Electrical #electricity #engineering #contactor

Опубликовано:

 

8 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 16   
@monirulislammonir9784
@monirulislammonir9784 2 года назад
Excellent 👍👍
@archive9994
@archive9994 3 года назад
Appreciated
@monirulislammonir9784
@monirulislammonir9784 2 года назад
Awesome 👍
@bat2ball.comofficials862
@bat2ball.comofficials862 2 года назад
Beautiful
@md.shamimreza5064
@md.shamimreza5064 2 года назад
nice videos
@tubakhatun3070
@tubakhatun3070 2 года назад
Nice
@Abdulla__420
@Abdulla__420 2 года назад
nice
@naimulislam41
@naimulislam41 2 года назад
Good
@paulndungu730
@paulndungu730 2 года назад
Does contactor noise make electronic gadgets burn or blow off components
@shreyaskumarkj568
@shreyaskumarkj568 3 года назад
Hi sir, I have a abb power contractor of 25A 220V auxiliary supply ..i need a VA ratings of the auxiliary coil but it's not mentioned.. So how to calculate VA ratings for this
@ElecEngineer
@ElecEngineer 3 года назад
You have to check the contactor's datasheet
@bishudatto1068
@bishudatto1068 2 года назад
Wow
@al2207
@al2207 Год назад
easy fix: use Moeller electric contactor , they build contactor not buzzer
@soimhossen3023
@soimhossen3023 2 года назад
Beautiful
@kamrultelecom7901
@kamrultelecom7901 2 года назад
Nice
@ahamadhamidi6048
@ahamadhamidi6048 5 месяцев назад
Nice
Далее
TOP 5 CONTACTOR Troubleshooting Problems!
7:05
Просмотров 293 тыс.
Я тоже так могу
00:12
Просмотров 1,5 млн
Control Panel Testing - Tips and Tricks
5:09
Просмотров 184 тыс.
Troubleshooting a Motor Starter
10:45
Просмотров 317 тыс.