Guest Speaker John Siegenthaler, P.E., will explore hardware and sizing of thermal storage in a variety of systems, including those supplied by boilers, solar thermal collectors, heat pumps and biomass boilers.

Наука

Опубликовано:

 

2 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 22   
@EliteHydronics.
@EliteHydronics. 5 лет назад
The best informative content regarding hydronic systems on RU-vid! kind regards Dave
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 5 лет назад
Thank you so much!
@paulmcguckin9140
@paulmcguckin9140 9 лет назад
Have been using these systems in ireland since 2009. Have loads of case studies .
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 9 лет назад
Paul Mcguckin And you installed our products as well, maybe?
@alexzavgorodni1350
@alexzavgorodni1350 9 лет назад
Excellent presentation. Just in time topic -- as I'm looking to incorporate a new boiler with a buffer tank into a new design with a future wood burning boiler considerations
@hvacdesignsolutions
@hvacdesignsolutions 3 года назад
I like the idea of having a PHEX instead of an indirect DHW Tank. Saves on space and standing losses.
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 3 года назад
Thank you for your feedback, Damian. Plate heat exchangers do work well.
@goodgod77
@goodgod77 9 лет назад
great slide show.
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 9 лет назад
+goodgod77 Thank you!
@DowieFarm
@DowieFarm 3 года назад
Could you point me to a source for comparing buffer tanks? I have a Navien Propane Tankless with dual heat exchangers, and a Ecoheat Pellet boiler on a hydronic baseboard system in New Hampshire. I'm having some issues finding equipment to compare online. I'm just learning about the buffer tank, but my propane heat definitely short cycles a lot. The Pellet boiler is being installed as I am writing this. Thanks! Very informative!
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 3 года назад
Thank you for your question and comments! We would recommend that you contact your local installer for recommendations. As well, for further information on thermal storage, we would recommend the 17th edition of idronics: Thermal Storage in Hydronic Systems. Here's a link to that resource: www.caleffi.com/sites/default/files/coll_attach_file/idronics_17_na.pdf
@berryberry3295
@berryberry3295 4 года назад
Great silde show! Could I receive that silde show files?
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 4 года назад
Thanks for your inquiry. Please email us at marketingadmin@caleffi.com with your request. Happy learning!
@RobinWhistles
@RobinWhistles 3 года назад
Great content...could you do a heatpump with woodpellet as back up on a 2 pipe system?
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions 3 года назад
Thanks for your question. Yes, it would be possible to combine a heat pump with a pellet boiler, although the expense would be high. The distribution system would still need to be designed for low water temperature to ensure compatibility with the heat pump.
@RobinWhistles
@RobinWhistles 3 года назад
@@CaleffiHydronicSolutions I have all the equipment already..it's just a matter of connection. With 2 buffers in series, wld the 2 pipe system be optimal, with 4 sensors.I found the woodpellet with one sensor was pointless as the burner was almost coming on with the demand. ive 2500ltrs of storage...and significant solar contribution also.
@RobinWhistles
@RobinWhistles 3 года назад
@@CaleffiHydronicSolutions I used to supply and install these systems but no text book or entity has the depth or understanding as ye tbh. Most have entry level designs and people end up falling back on condensing oil boilers due to poor design and poor craftsmanship.
@kristofergule123
@kristofergule123 2 года назад
what if i would like to use the 2 pipe figuration but i want to connect on the top of the tank, i only have a 1 inch on top and 2 return pipes 1 1/4 inch in the bottom of my tank, i thinking of the "stirring problem u talked about? my wonder so i can skip configure or buy a new tank..
@kristofergule123
@kristofergule123 2 года назад
and also how big should the connection be to not lose flow for the 2 pipe system, 1 inch minimum=?
@castirondude
@castirondude 10 месяцев назад
16:00 short cycling , I would think even 10 minutes is quite short. Maybe okay for a basic gas furnace. Ideally things like heat pumps and chillers would cycle no more than twice a day.
@amirseyal
@amirseyal Год назад
idronics 17 page 35 (also mentioned in the video) states that "The stainless steel heat exchanger should be sized for a maximum approach temperature difference of 10ºF. This refers to the temperature difference between the water entering the primary side of the heat exchanger from storage and the water leaving the secondary side of the heat exchanger." Why is this the maximum temperature difference? What is the problem with installing a brazed plate heat exchanger with a higher temperature difference for a single thermal mass combisystem?
@CaleffiHydronicSolutions
@CaleffiHydronicSolutions Год назад
The appropriate approach temperature design will depend on the size/cost of the heat exchanger and the maximum temperature output of the heat source. In this particular case, 10F was the number used. There is a more detailed description of approach temperatures on page 45 of idronics 29, which focuses entirely on heat exchangers. www.caleffi.com/sites/default/files/file/idronics_29_na.pdf As always, reach out if you need help with a specific application: techsupport.us@caleffi.com
Далее
Glycol - That Colorful Hydronic Fluid
58:20
Просмотров 3 тыс.
Applying Air to Water Heat Pumps in Hydronic Systems
49:43
Thermal Energy Storage
5:39
Просмотров 11 тыс.
ModCon Boiler Piping for Peak Performance
1:06:49
Просмотров 12 тыс.
Hot Topics with Hot Rod Episode 1: Buffer Tanks
1:10:33
Просмотров 2,9 тыс.
Hydronics System Components
12:31
Просмотров 371 тыс.