Variable Capacity vs. Variable Speed Compressor 

HVAC TV
Подписаться 12 тыс.
Просмотров 11 тыс.
50% 1

In this video, we discuss the difference between a Copeland Digital Scroll Compressor and a Danfoss Variable Speed Compressor. These two HVAC modulating scroll compressor technologies accomplish similar results but are constructed differently.
Video Description:
The Copeland Scroll Digital offers compressor modulation from 10-100 percent, allowing cooling systems to automatically adjust capacity as needed while reducing energy consumption. This scroll technology allows for precise HVAC system control, is more efficient than on/off compressors, and allows for almost continuous operation during dehumidification modes. Variable-capacity control is accomplished by timing the compression by engaging and disengaging the top scroll while motor speed remains constant. Advantages are efficiency, precise control, very low turn down to 10%, and constant velocity refrigerant allowing for effective oil return. For some of the compressor sizes, the "modulating" can produce unwanted noise. Special considerations for location and attenuation are recommended.
Emerson’s Copeland Scroll Variable Speed compressors are designed with AC drive controls that modulate the compressor speed. This compressor speed modulation allows for precise capacity control. Advantages are efficiency, low acoustical characteristics, and precise control. Special considerations are required to ensure oil return which usually prohibits low turndown capabilities. Usually, the minimum allowable turn down is in the 10-25% range.
Thank you for watching and please let me know if you have any questions!
----------------------------------------------------------------------------------------------------------------------------
Get in touch with me:
Call me: 828-712-4769
Email me: tmormino@insightusa.com
Visit our website: www.insightusa...
Connect with me on LinkedIn: / tony-mormino
View current line card: www.insightusa...
----------------------------------------------------------------------------------------------------------------------------

Опубликовано:

 

19 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 15   
@jsevold
@jsevold Год назад
Great video, very informative, thanks for comparing the two compressor types so thoroughly. We've had issues with acoustics of the VCC when located on the roof of a residential building.
@HVAC-TV
@HVAC-TV Год назад
Thanks for watching!
@sivasubramaniansksabapathi2587
It's a very simplified and illustrated way of explanation. Hats off, sir. Do we need a minimum charge quantity of refrigerant in both VCC and VFD Scroll compressor ?
@HVAC-TV
@HVAC-TV Год назад
I’m not sure if there is a minimum charge. Thanks for watching!
@VTdarkangel
@VTdarkangel 3 месяца назад
Variable capacity is a more generic term. Variable speed is a type of variable capacity. Digital compressors do it by PWM over a 15 - 20 second cycle. Variable speed does this by changing the speed of the motor.
@wasimsaliby6720
@wasimsaliby6720 Год назад
Great presentation!!
@HVAC-TV
@HVAC-TV Год назад
Thank you!
@chrisasian45
@chrisasian45 Год назад
Extremely helpful! Thank you.
@HVAC-TV
@HVAC-TV Год назад
You’re welcome!
@varuna.v9108
@varuna.v9108 2 года назад
It was really a helpful video
@TimothyBaker-j2x
@TimothyBaker-j2x 16 дней назад
Why is an electronic expansion valve required with a vfd controlled scroll compressor?
@rcinfla9017
@rcinfla9017 9 месяцев назад
If you are looking for good efficiency at lower system purchase cost, two speed compressor is best compromise. With new utility smart meters, more attention and regulations on appliance power factor, digital VCC compressors will not be around long as they are difficult to impossible to control utility grid load power factor. Oil circulation is an issue with both variable and VCC compressors. The short compression on-off duty cycle of VCC is not long enough to make an impact to average oil circulation. The critical oil circulation is determined by suction line vapor mass flow and by the time vapor exits evaporator, the VCC pressure pulses have smoothed out to an average (lower) mass flow rate. If the liquid pressure pulses of VCC are too great it would also cause problems for the EEV expansion valve refrigerant regulation into evaporator. The pressure pulses of VCC are pretty much smoothed out by gas compression in first part of condenser. It takes 10-30 minutes at full run speed to flush system distributed oil back to compressor. On most residential systems, when you drop below about 50% of capacity you end up with a net loss of oil in compressor. During low capacity run time you are running on compressor oil sump reserve. This is a primary reason why two speed compressors only drop to 60-65% capacity level.
@mpgravol
@mpgravol 11 месяцев назад
Can you explain how a variable speed compressor in a car works without having any of the fancy communication and control systems that are needed when VRF is used for residential and commercial buildings? The compressor in a car is usually directly driven from the engine. The engine speed typically varies somewhere between 500 RPM and 3,500 RPM under normal conditions. A receiver and expansion valve appear to be all the equipment necessary to keep the system in balance even when there are wild swings in load and capacity (compressor speed). The cabin is maintained at a comfortable temperature and humidity level even with massive swings in heat and humidity demand over short periods. Thanks
@eDoc2020
@eDoc2020 5 месяцев назад
The car A/C will cool more the faster the engine spins. If this would result in overcooling the heater is often at the same time. This is obviously inefficient but nobody cares.
@parasdesai2408
@parasdesai2408 4 месяца назад
Any job opportunity in Houston? I am a Sustaining Design Eng at Daikin…
Далее
Diagnosing a Locked Compressor 3D
10:02
Просмотров 56 тыс.
Редакция. News: 60-я неделя
41:13
Просмотров 1,7 млн
What Types of Motors Can Be Used with VFDs?
6:58
Просмотров 70 тыс.
Commercial HVAC was SABOTAGED! How we found out!
14:42
Copeland diGital Scroll by temperzone
9:28
Просмотров 161 тыс.
AC Pressures, Subcooling and Superheat
29:52
Просмотров 256 тыс.
Bosch IDS Light 15 Seer Overview & Training
12:13
Просмотров 3,4 тыс.
Copeland Discus™ Digital Demonstration
2:54
Просмотров 157 тыс.