A/s Sir..... According to NFPA 13 Ordinary group 2 hazard in that 25Dia pipe we use 2 no's sprinkler Can I use 4no's sprinkler in 25 dia....there is any possibility for this.... Btw Jazakallah aap axhha kam kr rhe ho❤
I don't recommend to bypass the standard because at a time these 4 sprinklers activate then less flow of water will be there in each sprinkler which is violation of standard requirements.
@@TanweerAhmed Sukriya Sir, Can I bypass standard through hydraulic calculation Like can I calculate overall hydraulic calculation for the FPS system and bypass the standard.. Is it possible or not sir, Or According to the standard if I'm going for installation there is a need to calculate hydraulic calculation ? Please sir, reply to this I'm so confused about this.... Jajakallah khair
@@star_ultron As per NFPA 13: The water demand requirements shall be determined by either the pipe schedule method or the hydraulic calculation method. The minimum water supply requirements for light and ordinary hazard occupancies protected by systems with pipe sized according to the pipe schedules method and for extra hazard occupancies shall be based on the hydraulic calculation methods.