Тёмный

Viessmann Vitodens 100 No Hot water Boiler Service - Viessmann Boiler 

Allen Hart
Подписаться 127 тыс.
Просмотров 113 тыс.
50% 1

Combi Boiler - No Hot Water. Boiler Service. Viessmann Boiler. Cleaning a plate to plate heat exchanger. no hot water on a Viessmann Vitodens 100. This boiler is a 35 kilowatt boiler, so I'm going to go through some of the basic things to check. Also, this boiler, the water is fluctuating hot and cold. It goes up to temperature, so I'll show you that, and then I'll show you how to repair it as well.
First of all, let's have a quick look at the boiler. This is the Vitodens 100 WB1C, and it's a 35 kilowatt boiler. We would expect to get around 14 litres a minute from this at 35-degree rise. I haven't turned the power on yet on this, but obviously we'd check the power was on. That's the hot water selector. We would turn that up, make sure that's up onto full, and then we'll turn the boiler on. Then what I'm going to do, before we even take the case off, and before we look inside the boiler, we'll go run the hot water tap, and we'll check the flow rate just to make sure that it's not running too quick through the boiler. So we'll check that now.
The importance of checking this is if you've got too much flow going through the boiler, then the water will be cooler. It can only raise a temperature by 35 degrees, and that's at 14 litres per minute. We can see that clearly, it is about 14 litres a minute. We'll leave that running now, and then we'll go and have a look inside at the boiler temperature.
We've turned the hot water on now, and it's just going up to full. We would expect this normally to settle around 62 to maybe 67-ish, so maybe about 65 degrees we'd normally expect this to settle at. If it goes above that, then we would suspect it could have a problem with a plate heat exchanger, so we'll see what happens here now.
We can see it's going above what we'd expect it to be. This is getting a lot higher now than we would expect. This would indicate to me, or it would give me an idea that we've got a blocked or a partially blocked plate heat exchanger. Now what we'll do, we'll have a look inside, just where it's safe. This shuts off, but then we'll have a look inside and we'll strip it down. We'll take the plate heat exchanger out, we'll clean it out, and then we'll put it all back together. Then we'll do this again, and we'll see what difference we have. We can see that now the burner's just gone down. If we measured temperature of water now, we'd find that the hot water's probably not that hot because it's going on and off. It's going up to temperature, shutting off. You can hear it, it's gone down now. That's the reason for the problem with this boiler. Let's strip it down now, and we'll have a look.
As always, if you're going to take the combustion cover off a boiler, make sure you're gas safe registered, or get somebody who's gas safe registered to do it for you. You've got two screws under here. First of all, you turn the power off, and then we would do all our safety checks. We'd go under these two screws and then we'll just lift the cover off.
I've undone the screws below, and then the case just lifts off. As I say, this has got a seal on here, so you must be gas safe registered if you're going to work on this boiler. Let's have a look inside, and we'll have a closer look. If you want to get to the plate heat exchanger, just lift these flaps down. Then the plate heat exchanger is right at the back there. To make it easier, you're going to take the burner out. Now, this seems to say that it's been serviced 2017, which normally when people write stuff like this on, it means it's been fully stripped down. But when I look at the gas pipe here, I can see that it's still got the seal on there. So I would suspect that when we lift this out in a minute, this has never been serviced. We'll have a look, and we'll see. I've connected the pump onto this now. I'm just going to pump it out. There's no pressure on this at all. Obviously, it's never been checked ... well, it haven't because it was sealed. So I'm going to pump this up now. There's different calculations with this, depending on the system. I normally top them up the about one bar, so on that now, it's just over one bar. As I undo it off there, the pressure will drop a little bit.
I've just connected the expansion vessel back in now. As I said, very easy, just a nut up on top. One good thing about this boiler is everything is really easy to work on. Then the pipe, I've connected that pipe back on there, and then that just connects in. This just connects in back down there. You just push it in, and then you've got a little clip. Then that just clips in there, nice and easy.

Опубликовано:

 

28 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 232   
@Britec09
@Britec09 5 лет назад
Love your videos Allen, keep up the good work mate.
@AllenHart999
@AllenHart999 5 лет назад
Thank you for your kind words.
@reyanshtrey9361
@reyanshtrey9361 3 года назад
a trick: you can watch series on flixzone. Been using it for watching lots of of movies lately.
@fletcherpeyton1963
@fletcherpeyton1963 3 года назад
@Reyansh Trey Yea, I have been using Flixzone} for years myself =)
@clarkestephen8299
@clarkestephen8299 2 года назад
Thanks for videos. Saved me a lot of work and money. Went straight to the fault. Heat exchanger out. Cleaned, de scaled, re fitted. 3 hours later. Hot water again.
@jonohutton89
@jonohutton89 4 года назад
Just had this problem on my boiler. It's heating to 102 but water is Luke warm then cuts out with f2 error code. Thanks to this video and others I have narrowed it down to diverter valve or heat exchanger. Saved me bundle! Thanks
@imrancankaya4831
@imrancankaya4831 5 месяцев назад
Thank you, that is amazing teaching, step by step ❤
@simonehawksworth8924
@simonehawksworth8924 4 года назад
Another really useful video, Thankyou Allen for all your hard work on these.
@ICGedye
@ICGedye 4 года назад
Awesome, should help my 'I only fit Worcester' gas fitter no end. Thanks, and keep up the excellent service!
@heatpump8566
@heatpump8566 4 года назад
Excellent job as usual Allan. Thorough 👍
@AllenHart999
@AllenHart999 4 года назад
Paul Turner Thank You👍
@RajeshBangera-x8i
@RajeshBangera-x8i Год назад
Thanks Allen. It was really helpful as I was going to do a service soon on this boiler and has the same problem. Cheers
@larry2569
@larry2569 5 лет назад
Thanks Alan for all your help
@AllenHart999
@AllenHart999 5 лет назад
Larry 25 Thanks
@gerardlong5675
@gerardlong5675 5 лет назад
Nice video showing how it should be done Allen. When I’m changing the plate heat exchanger I normally crack open the cold water inlet nut to let air in when the hot tap is open to let some more water out so less mopping up 👍obviously can only do this if your tap is lower than the boiler 😆 Love the videos keep them coming 👍
@AllenHart999
@AllenHart999 5 лет назад
Thank you.
@paulclive3626
@paulclive3626 5 лет назад
Superb informative video as always, well done & thankyou
@AllenHart999
@AllenHart999 5 лет назад
Paul Clive Thanks 👍
@SalimKhan-gk1fh
@SalimKhan-gk1fh 5 лет назад
Another excellent video Allen ! Thanks for uploading it I’ve fitted quite a few viessmann’s and also maintain quite a few you’ll be surprised how many I’ve ‘brought back from the dead ‘! which have been condemned, all due to lack of proper servicing many had still got the factory paint on the Schraeder valveOn expansion vessel where they have never been unscrewed or been topped up! I think it’s a state of the industry at the moment to be honest, I may be wrong? Whilst the burner assembly is out you also need to clean and check the gaps of the spark electrodes and after refitting the burner assembly the condensate trap will need to be washed out. this particular boiler you are servicing Has suffered neglect and has been ran on a dirty system, The dirt and debris in the Heat exchanger coils has caused the boiler to partially fill up with condensate water I’ve seen it many times before through lack of servicing or proper servicing, shall we say? if maintained and serviced well these are a very good boiler giving great reliable service and excellent efficiency
@AllenHart999
@AllenHart999 5 лет назад
Salim Khan Thanks
@allthingsmf8008
@allthingsmf8008 10 месяцев назад
great video, thanks
@damiebgibbons5710
@damiebgibbons5710 9 месяцев назад
Hi Alan, just a question, if there is no flame when the hot water is on , is it still the heat exchanger, there is heating just no hot water and the three port vale is moving in and out when you turn on the hot tap, hope you can answer the question for me cheers
@misfortune5007
@misfortune5007 2 года назад
Can you tell me what resistance I should expect from the seson next to the burner bleeder? Its a high thermostat. It has the 47 numer on the wire plug.
@stewartnorton6386
@stewartnorton6386 3 года назад
Great video. My stopped working yesterday display showing 99 degrees no hot water or heating and the burner symbol doesn't come on, any ideas what that may be ?
@patrickahearne8770
@patrickahearne8770 5 лет назад
Another great video Allen, however I have a question about servicing. Would you recommend that servicing it is done based on time, ie once a year, or by usage? My Viesmann 100 is a couple of years old but It doesn't get a massive amount of use. I'm a single bloke living on my own, out working six days a week so not caning it like say a family of 4 running baths and showers and having the heating on all day long. All the plant items where work get serviced based on how many hours usage rather than an arbitrary once a year.
@AllenHart999
@AllenHart999 5 лет назад
Patrick Ahearne Manufactures recommendation is once a year 👍
@Bikebros27
@Bikebros27 Год назад
I’ve got 1 that’s doing the same boiler keep cutting out and temps are getting up to 82
@MattPasek
@MattPasek 5 лет назад
Like always top class video ..very interesting and helpful will definitely help when going for my gas training .. Any advice.or tips best way to complete the training .. Thanks
@AllenHart999
@AllenHart999 5 лет назад
mateusz Pasek Try and spend as much time as possible working with an engineer. 👍
@petersutton3054
@petersutton3054 5 лет назад
Hi Allen have you came across the F4 fault on these boilers
@AllenHart999
@AllenHart999 5 лет назад
Peter sutton Yes, normally needs a strip down service, it could also be other things as well, blocked condensate, lack of flame. Electrodes etc etc
@AllenHart999
@AllenHart999 5 лет назад
I have done this video. Hope that helps. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-va2n9UWW_QA.html
@vitallife14
@vitallife14 3 года назад
Love your videos Alan keep up the good work! My 30kw vitodens 100 has just developed this fault, its 1st fault after 6 years! My gas engineer just changed the plate heat exchanger for new but since the replacement my hot water flow rate has reduced noticeably at all my outlets. I checked all the service valves and stop tap and everything is fully open. I’m having small problem getting him back due to lockdown shielding.Just wondered is it possible that he’s reduced the flow rate on the boiler somewhere of is it possible that the plate heat exchanger has been fitted wrong,in terms of the wrong way around or up side down? Interested to know your thoughts. All the best
@rayc1503
@rayc1503 3 года назад
Possibly a smaller plate to plate heat exchanger was fitted.
@umark6695
@umark6695 5 лет назад
Hi Allen. Good video as usual. Where did you get that short probe for the Kane mate?
@umark6695
@umark6695 5 лет назад
Allen?
@AllenHart999
@AllenHart999 5 лет назад
Kane 😂😂😂😂
@pservice7957
@pservice7957 2 года назад
Does anyone know how to fix an F9 fault on a 12 yr old model. I’ve pressed the flashing reset button and it goes back to show the temp again but after about a minute it goes back to the F9 fault and the reset button flashes red again
@darrenappel9281
@darrenappel9281 5 лет назад
Hi Allen great video where did you get that heat exchanger cleaning blade?
@AllenHart999
@AllenHart999 5 лет назад
Darren Elaouad Viessmann rep. Thanks
@rolandsmith2141
@rolandsmith2141 5 лет назад
Disconnecting the condensate pipe from bottom of heat exchanger when flushing out the debris (put a vessel under it obviously) would be a good trick .......ah Allan.
@AllenHart999
@AllenHart999 5 лет назад
You could do it that way but i would rather do it with hose connected. then clean trap out at the end if needed.
@jasonporteous9722
@jasonporteous9722 11 месяцев назад
Hi Allen What is the name of the chemicals you use to de-scale
@AllenHart999
@AllenHart999 11 месяцев назад
i normally use one shot but its not really advised anymore.
@paulmcgeoch2603
@paulmcgeoch2603 5 лет назад
Is this your own boiler Allen or is it a customers? Good video 👍🏼
@AllenHart999
@AllenHart999 5 лет назад
Paul Mcgeoch It’s my boiler now. Thanks
@olek735
@olek735 3 года назад
After this service Allen was to buy this boiler. Lol.
@fraserholmes2442
@fraserholmes2442 4 года назад
Hi Allen- ive got a Viessmann V100 WB1C 35kw that needs the pump replacing. Does the whole system have to be drained down to replace a pump, or are there isolating valves? Cheers
@themadhatter4761
@themadhatter4761 5 лет назад
Great thanks for sharing 👍👍👍👍👍
@AllenHart999
@AllenHart999 5 лет назад
Thanks for watching👍
@mikebarron4929
@mikebarron4929 5 лет назад
You must be real cosy in that mancave
@AllenHart999
@AllenHart999 5 лет назад
Michael Barron Love my man cave now 😂😂😂
@philipross7909
@philipross7909 3 года назад
Hello Alan I have just had a 111w fitted The boiler works all ok However when the burner turns off the boiler temperature display rises by up to 10c above the set point After a while it reduces The ch is set to 70c and water to 60c Any ideas ?
@johnward5006
@johnward5006 3 года назад
Normal operation.
@johndickson8992
@johndickson8992 3 года назад
It that the same for a wiessmann 050 boiler
@jeffmoore2351
@jeffmoore2351 5 лет назад
Thank you very much for your video. I have bought a second hand boiler system made in the UK its big its cast iron it has a gas blower. Plan to get a licensed professional in for pressure and gas workings. But I am curious if you would know if the company in question is still in business. Thank you again you earned your pint of Ale on that one. Aussie Jeff
@AllenHart999
@AllenHart999 5 лет назад
Where are you?
@jeffmoore2351
@jeffmoore2351 5 лет назад
Victoria Australia. The old boiler system is a cast iron Potteron about 450 by 450 by 900 approx high would have been installed late 70,s originally run on heating oil converted to a natural gas burner which is a Nuway unit approx estimate on size of unit somewhere between 30 and 50 k/ no idea about flow rate could send pictures if you are curious or willing to help. Aussie Jeff
@AllenHart999
@AllenHart999 5 лет назад
Jeff Moore I would be happy to help but unfortunately I wouldn’t have a clue. Thanks
@jeffmoore2351
@jeffmoore2351 5 лет назад
@@AllenHart999 would it help if I was to send you pictures to a mobile phone number as I don't do emails on my phone.
@AllenHart999
@AllenHart999 5 лет назад
Jeff Moore Pictures wouldn’t help really. I wouldn’t know what I was looking at 😂Thanks
@gimbalair
@gimbalair 3 года назад
I have this boiler, this video has been a real eye opener. I had issues with my plate heater fouling up, the installer blamed the rubber pipes, a known issue by all accounts, he cleaned it out and performance was much better. I have since had the boiler serviced regularly by a different company and they do not carry it out as thoroughly as this. I’ll be showing them this video. I came here as I wanted to learn how to wire a Nest thermostat, which until I get the boiler serviced is pointless installing. I’m not gas safe so won’t be undertaking any of this myself, even though it looked straight forward.
@AllenHart999
@AllenHart999 3 года назад
If the system is clean then they do not normally sludged up. 👍
@phasedout6769
@phasedout6769 5 лет назад
great video, very informative. I'd like to see more along this format. Fault finding, diagnosis and service. 👍
@AllenHart999
@AllenHart999 5 лет назад
Apprenticeonfire Thanks
@felix807
@felix807 Год назад
Older versions without condensation were very good products, needs only maintenance, a low procent of repairs. The new versions are crap!
@AllenHart999
@AllenHart999 11 месяцев назад
Thank You
@gasways986
@gasways986 4 года назад
Hi Allen very informative video, what chemical do you use to clean the plate FX2?
@jason23419
@jason23419 10 месяцев назад
For the novices how do they know which way up for the plate heat exchanger?
@AllenHart999
@AllenHart999 10 месяцев назад
I would always advise to go on a manufacture training course. Thanks.
@1ramus1
@1ramus1 25 дней назад
Thank You Allen. Very useful information for future. I have been using the same boiler for four months and have had no problems yet.
@scottreger4266
@scottreger4266 Год назад
Thanks Allen for sharing your professional experiences in this video, managed to pluck up the courage to tackle the plate heat exchanger on my vitodens 100, got to say being a competent person you made this job basic enough for me, saved me money and got my boiler back up and running!! Showing you channel support and thanks very much well put together video...
@sirazsaleh5942
@sirazsaleh5942 5 лет назад
Hi Alan, Which cleaner chemical did you use to clean the hot water plate heat exchanger . I have a similar symptoms on my potterton Promax 28He I do get hot water, but sometimes for about 10 seconds water gets cooler and then it gets hot again, this happens now and again, not always. I would say intermittent not always. I suspected heat exchanger may be partial blocked or the boiler may be operating like this from new. The boilers is 3 years old.
@AllenHart999
@AllenHart999 5 лет назад
A lot of people use one shot.
@MohammedAli-rh5ii
@MohammedAli-rh5ii 3 года назад
@@AllenHart999 hi Alan ur video are amazing just i just bought a new property my heating work ok but my hot water warm for a bit and then goes to cold can u pls tall me what problem that might be. .thank you very much
@rayc1503
@rayc1503 3 года назад
@@MohammedAli-rh5ii NTC sensor, pcb, flame sensing electrodes. Blocked plate to plate. It's best to call in a gas safe engineer. It's hard to diagnose without being there.
@54321kola
@54321kola 3 года назад
👍👍👍
@James-m8b5d
@James-m8b5d 9 месяцев назад
Had loads of these year mostly with 050. Some I've managed to clean others I have just straight up replaced just to save a return visit. 050 has very small fins so much hard I have found to clean. Good video l, and great pro
@rayc1503
@rayc1503 5 лет назад
Hi Allen could you put up a link to the cake slice holder you cleaned the primary he-ex with? 😊
@AllenHart999
@AllenHart999 5 лет назад
ghostmanromeo uk I got it from my Viessmann rep. Not sure who sells them. Sorry
@slickydee5507
@slickydee5507 5 лет назад
@@AllenHart999 Viessmann sells them. I'm a US wholesaler we buy the exact same ones from Viessmann
@gjmheating8857
@gjmheating8857 2 года назад
Nice Allen I do same thing with heat exchanger but use white vinegar whilst having chin wag. If the boiler is on ground floor can you still drain through filling loop? Also I recommision vessels in situ helps with draining etc. I had one last week refilled it to 1 bar shot up so quickly and when heating was on it was so High but there wasn't actually any water inside boiler when I drained it I checked usual hose on expansion vessel but couldn't find blockage etc.
@dcreaven1
@dcreaven1 2 года назад
Thanks Alan , I’m a newly qualified gas engineer and your videos have got me out of trouble many times
@MikeAnderson-si2xe
@MikeAnderson-si2xe 5 месяцев назад
my dad worked for viessmann for 8 years and had the tools but where is the screwdriver from
@jamesdc1993
@jamesdc1993 5 лет назад
Very interesting to see how it all works (and how it breaks). I wish that I was gas safe so that I could have a tinker!
@olek735
@olek735 3 года назад
What's is a "tinker"?
@jamesdc1993
@jamesdc1993 3 года назад
@@olek735 Sorry, I should have been clearer and avoided the colloquialism. To "tinker" to me means to work with or on some device or machinery. Here in the UK you need to be qualified to work on boilers, and I am not!
@boygeninho
@boygeninho 3 года назад
I can't put my boiler in eco cystem, I don't have the taps in my screen, I try I try put but always I don't be successful My boiler is the same of the movie
@wackadakka3134
@wackadakka3134 2 года назад
I have the veissman 050 , the hot water flow is very slow , but its constant temperature , . no one can seem to figure out whats happening ! ..any ideas ?
@stewben1169
@stewben1169 5 лет назад
Excellent video very in-depth and very informative. Thank You
@AllenHart999
@AllenHart999 5 лет назад
Stewart Bentham Thanks 👍
@davidgorrie7606
@davidgorrie7606 3 года назад
foegot to add your instals are great to, a major factor is eying up prior to taking job on every detail hidden work and a lot of the time say on phone for a breakdown customer they tell youthe faults and on your drive to job u can save time by going to check main obvious faults right away althoughof course there has to be a full inspect repair and recommission of system , look forward to seeing more , i can subscribe if you send me details allen , thank you for making a great start to my day again mate ,
@alisonmcrory
@alisonmcrory 7 месяцев назад
Viesmann bar us at 1 when I switch it on it goes up to 3 bar how do I de pressurise it
@krystianjakubiak1508
@krystianjakubiak1508 8 месяцев назад
everything is fine, but there is no instructions on how to bleed the hot water system.
@ML-lg4ky
@ML-lg4ky 5 лет назад
I wish viessmann had a dealer network here in Upstate NY
@AllenHart999
@AllenHart999 5 лет назад
What boilers do you have over the pond?
@ML-lg4ky
@ML-lg4ky 5 лет назад
Allen Hart Weil Mclain, peerless, lochinvar, HTP, Utica, mostly cast Iron units still in use. I installed a Buderus G115 with a riello burner last year and absolutely love it. Most homes have forced Air here but some have hot water baseboard with requires 180f degree water. Many people here that install High efficiency boilers are very unhappy because the do not see any gas savings because they don’t have the proper heat emitters. Am going to install an radiant slab in my new garage so I’m looking for the proper boiler for that. Keep up the good work Allen.
@madmaycon2531
@madmaycon2531 5 месяцев назад
Thanks a lot Allen, Perfect video !!!!
@Nick_G7IZR
@Nick_G7IZR 3 года назад
So just wanted to thank you for helping me fix our variable hot water upstairs. Downstairs was fine, but upstairs was variable. I cleaned the heat exchanger plate but also topped up the expansion vessel and all is fine now. After her initial doubt (when I flooded the kitchen because I hadn't fully drained it) I now have a happy wife! :)
@AllenHart999
@AllenHart999 3 года назад
Glad I could help!
@aksentyalagoz6061
@aksentyalagoz6061 2 года назад
thank you for the very informative video where in alberta canada can a oerson get parts
@kayleighbeuzelin
@kayleighbeuzelin 3 года назад
Very good and educational. Thanks for your time
@456Brian
@456Brian 5 лет назад
Hi Alan what boiler would you recommend . I have 9 rads the one I have is a ideal classic we've had it 20 years .it is a conventional boiler thanks
@AllenHart999
@AllenHart999 5 лет назад
brian jones Baxi Platinum is a great choice or the Viessmann 100, Thanks
@456Brian
@456Brian 5 лет назад
Thanks Alan all the best
@SalimKhan-gk1fh
@SalimKhan-gk1fh 5 лет назад
brian jones , get the Viessmann vitodens 100 it’s a great boiler, I recommended one to my neighbour last year & he was really impressed with how quiet it was ,& how quick it warms up all the rads, but best off all its extremely gas efficient !
@456Brian
@456Brian 5 лет назад
@@SalimKhan-gk1fh thanks you for your advice
@SalimKhan-gk1fh
@SalimKhan-gk1fh 5 лет назад
brian jones , your welcome Brian, just ensure u use somebody who is familiar with whatever brand of boiler you choose and also any subsequent servicing is carried out to Allen harts thoroughly high standard! I must be on my 20th viessmann boiler fitted so far I only had to call them out once & the engineer was brilliant and found the issue very quickly, which was an installer issue! This boiler Allen is working on has been mistakenly written off and replaced due to it only needing a thoroughly good clean! I see this situation quite often now
@jasonnewportcounty9897
@jasonnewportcounty9897 2 года назад
Hi Alan what cleaner did you put in the heat exchange unit Cheers
@anthonyclinton1355
@anthonyclinton1355 3 года назад
Hiya Alan, does this boiler have a drain off point if you don't have a magnetic filter to drain from, I'm gas safe registered but never worked on this boiler b4?? Thanks bud 👍
@AllenHart999
@AllenHart999 3 года назад
Yes you use the filling loop. Thanks.
@brahim21261
@brahim21261 2 года назад
Thank you friend😹👋👋👋
@owsi2297
@owsi2297 5 лет назад
Cheers mate that was a really interesting video 👍
@AllenHart999
@AllenHart999 5 лет назад
Thank You
@mariom383
@mariom383 4 года назад
What should I check? My unit gets the house up to temperature and it doesn’t come back on. So I turn it off and put it back on and it does the same thing again. Any idea please let me know thank you
@marie_helenebelanger3340
@marie_helenebelanger3340 10 месяцев назад
Qu'est ca veut dire FC merci beaucoup
@markcliff9923
@markcliff9923 4 года назад
Great video Allen, got to do a plate heat ex on the 100-w 25kw combi, is it the same? Don't usually do much on the viesmanns, parts really expensive, I am gas safe by the way👍
@AllenHart999
@AllenHart999 4 года назад
Very easy to do, yes.
@keitho77
@keitho77 5 лет назад
Thanks for the video Alan. Very interesting to see how it all works. How would you go about fixing a boiler that the flow of water in is too fast, causing a no hot water issue in a shower?
@AllenHart999
@AllenHart999 5 лет назад
Set the boiler up correctly. Reduce the flow to match the boiler. Thanks
@Randommusingsvideos
@Randommusingsvideos 5 лет назад
Interesting video; if that boiler was removed for the hot water fault then it goes to show the value in getting a heating engineer to take a look at it (And get the boiler serviced annually too!) Viesmann boilers a really good as they have a stainless steel inox heat exchanger, so should last a while longer than boilers with the cheaper aluminium heat exchangers. Once again Alan, a great informative video!
@AllenHart999
@AllenHart999 5 лет назад
Thank you
@SalimKhan-gk1fh
@SalimKhan-gk1fh 5 лет назад
Random musings , An interesting video to watch, but the thought in the back your mind is was this boiler removed just because of the hot water fault? so whole new boiler installation for such a small fault ?? unbelievable!
@AllenHart999
@AllenHart999 5 лет назад
Salim Khan I am guessing that would be the case but not sure
@sodig876
@sodig876 5 лет назад
Very informative video Allen 👍 keep up the good work.
@AllenHart999
@AllenHart999 5 лет назад
Thank you
@ArifPolicewala
@ArifPolicewala 7 месяцев назад
Thank you Allen. That was a straight forward precise video❤
@AllenHart999
@AllenHart999 7 месяцев назад
Thanks very much for your comment, please consider subscribing to support the channel 🙂
@brucecarter6541
@brucecarter6541 3 года назад
Thanks Allen love your vids,you have found my problem with boiler, 👍👍👍
@AllenHart999
@AllenHart999 3 года назад
Good to hear
@mangojassal
@mangojassal 3 года назад
I have one of these so a big 👍 up
@rocketman246
@rocketman246 5 лет назад
Excellent video mate. I did the same with a Worcester but only lasted temporary so had to change ultimately with a new Hex
@AllenHart999
@AllenHart999 5 лет назад
I had one on a viessmann a while back that lasted 5 mins, i had to take heat exchanger out and flush it all. Thanks.
@JagtarSingh-gw2yq
@JagtarSingh-gw2yq Год назад
Thank you!
@Nick_G7IZR
@Nick_G7IZR 5 лет назад
I have the same problem with mine, getting to 88'c then cutting out. I understood the heat exchanger and cleaning the combustion chamber etc, but what on earth was that thing you pressurised and would I need to do that and if so, with what adapter? Thanks!
@robertdonaghy7260
@robertdonaghy7260 5 лет назад
Cheers Allan, i enjoyed that. Decent of you to take the time to make these Videos.
@AllenHart999
@AllenHart999 5 лет назад
Thanks.
@jackhoskins722
@jackhoskins722 5 лет назад
Could you put details of that heat exchanger tool in the description please mate !
@AllenHart999
@AllenHart999 5 лет назад
I got it from my rep.
@Moocow9991703
@Moocow9991703 4 года назад
@@AllenHart999 Thanks Allen I've been a worcester installer for about 10 years but recently I've found out that they are a large share holder of boxt so my loyalty as completely gone and I'm not keen on the idea of promoting worcester anymore....i was thinking of switching over to viessmann instead, do you think that would be a good move for my business? Many thanks Dan.
@scottvincent1810
@scottvincent1810 5 лет назад
I have this boiler. I have a leak from condensing trap. Can you do a video on condensing trap removal please?
@WEYHARRY1
@WEYHARRY1 5 лет назад
Good video Allan
@AllenHart999
@AllenHart999 5 лет назад
Thank you.
@kostaskostakis6651
@kostaskostakis6651 4 года назад
Hello How must be is bar?
@AllenHart999
@AllenHart999 4 года назад
Thank you so much for the comment. Happy new year
@abdulh63
@abdulh63 5 лет назад
Love the video! Very well explained and easy to understand
@AllenHart999
@AllenHart999 5 лет назад
abdul hafiz Thanks
@Ro55stw
@Ro55stw 5 лет назад
Good video mate
@AllenHart999
@AllenHart999 5 лет назад
thank you
@olek735
@olek735 3 года назад
What is the main reason for second exchanger being so "dirty"?
@albert5538
@albert5538 Год назад
Hello Allen, I am in a similar situation. When I turn on the hot water, it doesn't come out very hot. When the boiler reaches 60 degrees, it stops and does not turn on again until it reaches 25 degrees. The dial is at number 6. I have cleaned the exchanger, I have also cleaned the coil and finally checked and set the expansion vessel to 1 bar. Do you have any idea what it could be? I suspect that the sensor that measures the temperature is measuring more temperature than the real one.
@richardwallinger1683
@richardwallinger1683 4 года назад
super advice and diagnostics ..
@AllenHart999
@AllenHart999 4 года назад
Thank you for taking the time to watch my video.
@konradbidwell8363
@konradbidwell8363 5 лет назад
Alan top draw mate I had a customer call me today with exact boiler describing same issues so did a little google and happy to see this come up. Obviously I shall diagnose properly when I go tomorrow but I’m sure this vlog will be of use👍🏻👍🏻
@hugebartlett1884
@hugebartlett1884 Год назад
That was well worth watching. Always been fascinated by these systems,look forward to the engineer giving the boiler its annual service.
@ebru9830
@ebru9830 4 года назад
When I use the kitchen tap while the hot and cold water is running, the water would turn freezing cold. When I shut the cold water and only the hot water is open it would still be freezing cold for like a minute or so then it would go back to normal but the same thing would happen over and over again. Can you tell me why this is happening and what I could do about it please?
@paulrossiter9567
@paulrossiter9567 4 года назад
Very useful video ....this along with most of your others has gone straight into my saved vids ⭐️⭐️⭐️⭐️⭐️ You are the guru 🧙‍♂️
@josephclark48
@josephclark48 5 лет назад
Hi Alan. What is the problem if pressure guage drops down when boiler is running and does not increase above the standing pressure? Great videos.
@richardbutler6985
@richardbutler6985 2 года назад
Question sir should the boiler temperature drop when hot water or heating isn't being used? Or should the boiler keep reheating to the set temperature e.g. 65c if set there ?
@davidgorrie7606
@davidgorrie7606 3 года назад
great work allen , your mind must be on ob all the time , your knowledge on practical theory maintenance service worl and breakdown are 2nd to none , brilliant to watch , what do you do in your spare time allen ? ha ha ha i was an lpg fitter engineer , for calor gas covered whole of scotland . great job , doing commercial work industrial domestic and caravan sites covered everything , watching your self takes me back to my days when you just got on with job , in a hundred life time i couldnt have had a more satisfying job and experience over years no one can replace it , brilliant to watch your vids allen keep up great work 1st thing i do when i have a cuppa and shower in morning is put your vids on , im a dedicated fan brilliant mate ,
@charliewillis8527
@charliewillis8527 4 года назад
Does the door seal need to be replaced every time it comes apart and does it need to come apart ever year as the Worcester boilers only come apart when they fail the pressure test but a change the red burner seal every 4 years i only work mainly on the Worcester boilers as thats what i install and repair which keeps me more than busy with all my other jobs
@MrVictorvolvo
@MrVictorvolvo 2 года назад
Would anyone know what size hose is being used, which is attached to the bleed valve to clean the heat exchanger?
@rajeshbangera6149
@rajeshbangera6149 Год назад
Thank you Allen. As always great video and explained well. Cheers
@markfung6418
@markfung6418 5 лет назад
Hi Allen, thanks for putting up informative videos! I had a Vitodens 100 WB1A installed 10 years ago. Overall I'm happy with it. The first heating company didn't install low loss header. This reduces efficiency I was told by current authorized rep. It is cleaned and maintained yearly. However, the boiler locked out reporting F3 code a number of times. Technician determined that spark generator needed replacement. Boiler worked well for two years afterwards. Now the boiler puts out F3 code again. After last maintenance visit, the fan (or something) made loud humming noise during startup. The noise reduced once the boiler was full on. Everything was working fine otherwise. Had the technician back. He heard it too but couldn't determine the cause. I didn't want him to just replace whatever (motor or fan) making that noise. Allen you know these boilers well. I would like to get your feedback on some items. 1/. How durable are these boilers? 2/. How often spark generator needs replacement? 3/. Love to have a hot water combi version but I'm worried about having issues without hot water and heat. How reliable is the combi type? 3/. My boiler is 10 years old. Should I continue to have it serviced or have it replaced? Would greatly appreciate your opinion. Thanks. Mark.
@newsbiz
@newsbiz 4 года назад
Hello, I had F4 fault (condensate), Wiessman manual says refractory must be dried out with a hair dryer - how do you do that?
@philgreen3376
@philgreen3376 3 года назад
Just found your videos, great information Thanks👍
@danielwilliams3978
@danielwilliams3978 2 года назад
Informative Video Allan, thank you for making it.
Далее
Viessmann Vitodens 100 Combi Boiler Strip Down WB1C
24:24
Vitodens 100 range overview
4:45
Просмотров 19 тыс.