Roger looks at a problem with a concrete lintel.
Here's the message from Ryan:
Hi, so about 6 months ago, I had this arch open extended.
For the last three months, the lintel below the wall has been cracking.
The wall on the left has not cracked at all.
The wall that is cracking is on the side of the house against a main road.
I wondered if this is a problem, if this lintel must be replaced or if it can be repaired with something like a helical bar or studs through the lintel into the wall above it.
Thanks,
Ryan
==========================================
#HomeImprovement #lintel #homerenovation
🔗 Skill Builder Link Tree: linktr.ee/skillbuilder
👍 Tell us what you like: skill-builder.uk/vote
📪 Ask Skill Builder: skill-builder.uk/send
🎥 TikTok: / skillbuilder
📣 Facebook: / skillbuilderchannel
📷 Instagram: / skill_builder
🛒 As an Amazon Associate, we earn from qualifying purchases
🎬 All videos: ru-vid.com...
💧 We Support Charity Water: www.charitywater.org
◾ Out of respect to our channel sponsors and the wide variety of people who watch our videos, we'll remove comments that do not follow common standards of politeness and decency.

Опубликовано:

 

7 мар 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 227   
@slyteen2197
@slyteen2197 Год назад
I'm an engineer and we have a saying at work "if it looks right then it probably is". That lintel doesn't look right. It's the wrong product for the job.
@derekloudon8731
@derekloudon8731 Год назад
I am not a builder just a basic DIYer but I am really enjoying these short videos on problem investigations. Keep them coming please.
@whitefields5595
@whitefields5595 Год назад
For a non-Engineer you explained it very well. When doing stress calculations on a beam like this the inherent 'strength' of the beam determines the load it can carry. By straining the metal bar and letting concrete set around it, the inherent strength of the beam is increased, It is pre-loaded (= pre-stressed). It contains energy, strain energy. This can be compared to your van. Its static weight that pre-load the spring with twisting energy in the spring. When you go over a pothole the wheel is pushed downwards by this release of strain energy stored in the spring. Without this the van would lurch into the pot hole. Same thing with continuous railway lines. These are stretched and welded at the same time. When the sun heats them up the stored tensile strain energy absorbs the energy of thermal expansion and so they don't buckle. Strain energy stored in toughened glass makes it shatter into small pieces. The upwards curve of the lintel is encouraged because concrete is very strong in compression. For the beam to sag it has to go through the mid-position which is resisted by the compressive strength of the concrete on the upper surface. Building the lintel into 'wet' brickwork adds to the compressive resistance on the upper surface. With the upward bend the additional bricks would all have to compress for the beam to pass the mid-point. Built in 'dry' then there is a built-in fault line above the lintel that can move a bit more than if it were all done wet and set at the same time. There is however an ultimate load in all of this. The weight of bricks above will ultimately exceeds the benefit of their compressive strength, its going to sag.
@lenb9037
@lenb9037 Год назад
The wet brickwork does not add to the compressive resistance of the concrete it increases the compression in the concrete. Wet brickwork does not act as a beam. Built in 'dry' the lintel would be nominally arched upwards. Crack should not appear above lintel if properly installed.
@whitefields5595
@whitefields5595 Год назад
@@lenb9037 Len, you are correct. My (and Roger's) use of the term 'wet' refers to the laying up of courses of brickwork using wet mortar on top of the pre-cast (dry) lintel. If something like SBR is used there would be a good bond to the lintel and once dried out, the effective depth and strength on the cast lintel would be increased due to the homogenuity of the now dried out mortar. For the lintel to go through it's 'arched up' posture would require this new brickwork above the lintel to compress. It will do so eventually, but only after it has provided addition load-bearing capacity to the lintel. I agree with your last sentence, but we all agree that this is what this post was all about, the lintel was not installed correctly. I'm not as convinced as you that a 'dry' installation would ever me good in this instance, but I'm an engineer, not a builder!
@lenb9037
@lenb9037 Год назад
@@whitefields5595 Design for 'dry' brickwork would be normal for this application in an existing wall and the packing above the lintel and below the 'dry' brickwork would be installed as tight as possible to restrict any gap perhaps with an expanding grout admixture. I personally would not consider SBR in structural calculations although there may be some nominal/minimal assistance. Just to clarify I am a structural engineer (retired) not a builder! It would be interesting to find out whether the lintel may have been installed upside down and if so whether re-installation took place to correct it.
@janoginski5557
@janoginski5557 Год назад
Well said “you never stop learning”, unfortunately some individuals never start. 😂
@honestabe2845
@honestabe2845 Год назад
Hi Roger, love the video. I have some experience with this type of situation. One thing that's often overlooked when designing or choosing a beam is how it will deflect (bend) when underload (installed). When doing a job like this its not just a case of assessing the beams capacity to take the load (dead and imposed loads) but also how much it will bend and sag over time as the load is applied. There are British standards that are used to assess beam deflection and if it will cause cracking to plaster or any final surface finishes. An added complication in this case is when lintels are installed in this scenario there is likely to be a small gap above the lintel and the brickwork above it. Meaning over time the brickwork will sag and start to fully bear on the lintel and cause it to deflect. If the beam deflection hasn't been taken into account when selecting lintel size then you will see a crack. This link gives a guide for steel, principles are very similar: ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-brC9JEKqV7M.html
@janoginski5557
@janoginski5557 Год назад
Bang on Roger, “Wrong Lintel, wrong guys”, succinct & straight to the heart of the matter. Should have been steels, no argument.
@SteveAndAlexBuild
@SteveAndAlexBuild Год назад
In 35 years I’ve never heard of a plank lintel 😳. The fact that there is a full pike/ gable above that room means that wall is load bearing. My guess is that the left hand one is in correctly and the right hand side is maybe upside down? Meaning the pre stressed camber is pushing down instead of up . On openings that big steels every time 🧱🤙🏽💪🏽
@SkillBuilder
@SkillBuilder Год назад
Steve They call them plank lintels in the South of England but we are as thick as two short............planks down here
@SteveAndAlexBuild
@SteveAndAlexBuild Год назад
@@SkillBuilder 😆😆🧱👍🏽
@lksf9820
@lksf9820 Год назад
Not all gable walls are load bearing, only older ones with purlin roofs. Modern ones with trusses aren't.
@SteveAndAlexBuild
@SteveAndAlexBuild Год назад
@@lksf9820 surely the gable is a load in itself , that’s a lot of heavy bricks above as in a “ load “
@lksf9820
@lksf9820 Год назад
@@SteveAndAlexBuild Then It's just a wall. 'Load bearing' means it's carrying something other than itself.
@davidcobb5816
@davidcobb5816 Год назад
The change of loading onto the central pier to support the gable wall may mean the foundation are not sufficient for the increased loading. When it was a full length wall the loadings would have been spread evenly along the foundations now they are concentrated onto the lintel bearing points and then through the piers to the foundations, point loading.
@TomasRamoska
@TomasRamoska Год назад
I used 150mm for a much shorter opening non-load-bearing wall. 75mm doesn't look reliable enough for me 😅
@mesudkeskic7531
@mesudkeskic7531 Год назад
Spot on Roger, as soon as I saw that, I could see that the incorrect lintle was used.. Steel would be the way to go..
@chrismonks2095
@chrismonks2095 Год назад
Did he have a structural engineer's calculation? Were building control involved at all?
@alistairmacfadyen9365
@alistairmacfadyen9365 Год назад
Excellent roger..
@jacko791
@jacko791 Год назад
Didn't even realise you could get those lintels in that length. It won't even support its own weight over that span. I wouldn't be surprised if the bricks above are supporting themselves and the cracks have occurred where the lintel has sagged away from them under its own weight
@habsom1406
@habsom1406 Год назад
That scarf is certainly 'entertaining' Roger! 👍😎
@paul756uk2
@paul756uk2 Год назад
He's wearing it to cover his concrete wrinkles.
@eliotmansfield
@eliotmansfield Год назад
cant afford to run his heat pump 😅
@SkillBuilder
@SkillBuilder Год назад
Hab Som It is called a snood and it is from Keyfix.
@catabaticanabatic3800
@catabaticanabatic3800 Год назад
Never seen a "beam " like that before. Only time I've seen a flat lintel is above a short apan like a window opening. There's no strength in that. That added wih probable inverted installation could account for the drop or sag. Get the builders back in. Give them cups of tea and plenty water for their horses.
@gdfggggg
@gdfggggg Год назад
I think when you build it as one the cement and brickwork above will set as one solid object to the lintel. When you try to introduce a new lintel under neath old brickwork it just won’t form as one solid object. I reckon they might have the Lintel upside down. Having followed many structural drawings I’ve never installed a lintel of 65mm (assuming it’s uk) with that span. It would normally be a a UB or a double UB bolted together.
@SkillBuilder
@SkillBuilder Год назад
I think you are right (again),
@gdfggggg
@gdfggggg Год назад
@@SkillBuilder wish my missis thought the same 🙄😆
@Pistol_Knight
@Pistol_Knight Год назад
1st thing I said in my head was the lintel is upside down, I would only use a lintel like that above a patio door with no more than 3 courses of brick on top otherwise its a steel all the way even a box section would be better pre stressed concrete lintels have their uses but i don't think that is one of them
@johnf3326
@johnf3326 Год назад
Yes the thin beam and brickwork effectively form a compound beam from new. But replace the beam and use a beam designed as if the whole lot above constitutes the load, plus using acros during the process, of course!
@gdfggggg
@gdfggggg Год назад
@@johnf3326 so effectively the new beam would be calculated as a separate entity.
@interabang
@interabang Год назад
You're right about the compression of concrete lintel. They have to be built in wet so the weight of the bricks pushes down against the upward force of the rods. The opposite effect is with those thin metal lintels you have to support them with timber until they go off.
@jaytea3299
@jaytea3299 Год назад
Roger your channel is one of the best. I don’t comment on these types of platforms often, but I want to offer that this may be an interior wall, (ie not likey but possible for sure, we cannot see the layout but I may be wrong and it is indeed under a gable- the drawing is not a shop drawing nor blueprint) and I’m wondering if it’s a combination of poorly installed finishes in conjunction with the issues that you already mentioned in the video. We have that problem with drywall stress cracks at corner bead when it’s not installed correctly and when there’s movement in the walls. If this is the case, the cracking would’ve been caused after the finishes (ie in my country, drywall/plaster, trims, paint) installation by any additional work done above the are or by dynamic loads above the lintels. In addition to poor design, the execution of finish installation can contribute (though not “cause”) these types of issues. Thanks for all you do! Kudos!
@amazing451
@amazing451 Год назад
If there is gable end brickwork above that would be classed as a load bearing wall, even it wasn't supporting joists or purlins, it is supporting the weight of the masonry above!
@jimjam1934
@jimjam1934 Год назад
Those 65mm lintels should have 2 courses of Engineering bricks above with ex-met reinforcement in the bed joints, built in one go as you said Rog so in effect it becomes a 225mm deep solid unit
@tmwoodhams
@tmwoodhams Год назад
You can see there is one acrow prop supporting the middle of the lintel before it's plastered in. That would suggest to me that maybe instead of fitting the lintel and installing brick work above, or dry packing with mortar they may have tried to wind the beam up to the underside of the existing brickwork. If I were installing a lintel or a steel beam I would form a pocket or shoulder using a padstone (are there any padstones?) and sit the ends of the beam/lintel on that. Sometimes you can't do it that first and might need to build the padstone up to the bottom of lintel/beam, in which case there should be a prop at one or both ends while the mortar is setting.
@MrJFoster1984
@MrJFoster1984 Год назад
You are correct Roger about the courses of brickwork above the lintel being required in order to form an arching effect. The manufacture normally stipulates the minimum number of courses required for the sectional size of lintel, this could be something like 3,5 or 7 courses. Your are meant to lay the lintels with the rough side up and just like rendering you should give your brickwork and lintel a wet down first with something like a garden pump up pesticide sprayer to control the suction much like in rendering with a scratch coat or priming. Also best to pack in structural non shrink grout between the existing brickwork and lintels. Think of the brickwork and lintel combination being like the section size of timber, the deeper the beam of the brickwork and lintel the greater it can span. It acts much like a floor joists versus a ceiling joist or a common rafter vs a hip rafter. Also the brickwork either side of the lintel matters, en castre is the engineering term if I am not mistaken, this resists the deflection/bending moment of the beam.
@stanieman
@stanieman Год назад
it was nice to hear you on BBC radio 2 yesterday!
@SkillBuilder
@SkillBuilder Год назад
Thank you,, it was difficult because I was on site and had to ask everyone to stop working to keep the noise down, it puit me under a bit of pressure.
@bayerpaul
@bayerpaul Год назад
Nice JINGLE😂
@handsfree1000
@handsfree1000 Год назад
I’ve recently removed a load bearing wall to form a open kitchen diner, used a RSJ and no cracking at all.
@marklaing8145
@marklaing8145 Год назад
Even if the beam is correct for the span it should never have an acrow jacking it up in the centre. If this needs to be done to squeeze the mortar between the lintel and bricks above it should be done at each end. This takes out any bowing which may take place once the mortar is set and the props removed. It looks in the pics that the lintel has settled in the middle causing the cracking and can probably be packed and repointed assuming the lintel is correct for the span and there’s no underlying structural issues.
@rjp666
@rjp666 Год назад
If its a fair face or fire spec lintel they have a top and bottom and are usually marked, but rule of thumb is to position the reinforced steel rods towards the bottom away from load thus eliminating sag.
@johnf3326
@johnf3326 Год назад
Usually in a prestressed lintel the top of the beam is the rough bit. Also the stressed rebar would be in the bottom of the concrete with about 50mm of cover. Concrete is strong in compression and weak in tension. Hence the bottom of the beam would be in tension if the load was great and the rebar here was not prestressed. In this way you can get away with a smaller beam. But at 75mm you could only have rebar right down the middle so prestressing would not have as significant effect
@thechrissyb
@thechrissyb Год назад
The bearings on those lintels look rubbish, it honestly looks terrible. Normally building control want a minimum of 150mm bearing if a lintel is retro fitted. Also on some sort of Padstone. That looked like a load of cement just parged in. Also like Roger said, it would have been steels not a shite concrete lintel.
@HW55
@HW55 Год назад
I’m surprised that got past the Building Control inspector. It wouldn’t have got passed by my local Council.
@geoffhaylock6848
@geoffhaylock6848 Год назад
Bringing new build quality to old build property.
@markc7955
@markc7955 Год назад
I put in a concrete lintel just like that. About same length. But mine was 150mm tall and only held up 5-6 course of brick which the rafters didn't sit on anyway. I'm not sure if I set it in correctly but hopefully over did it on inherent strength side.
@dennisphoenix1
@dennisphoenix1 Год назад
Looking at the picture it looks like it was a garage that's been converted. Hence the roof above. Either Way you can only remove two thirds of a supporting wall . This looks like more has been removed. The cracking has occurred because the builder has pushed the lintel up in the middle with an acro prop when bedding it in . Hence it's dropped back to its neutral state . Just cut out and repoint with a finger trowel.
@basmoo3987
@basmoo3987 Год назад
I believe the interlocking of the bricks above the linetel is called the cordobelling effect(bricks lock together preventing collapse.
@howardosborne8647
@howardosborne8647 Год назад
It is exactly as you describe and that is what you are seeing here in the images. The lintel has sagged and isn't having any contact with the 'self supporting' brickwork above it. They need to strip the lot back and make certain the lintel isn't fitted upside down then at the very least install wedging packers between the lintel and brickwork and point the whole joint full with sand/cement mix. The size of the seating nibs at either end may also be too small as it stands.
@970357ers
@970357ers Год назад
Marginal depth pads atop that pillar as well.
@cybershot123
@cybershot123 Год назад
It would be nice to see the brick work above to see if there is any cracks
@Pete.Ty1
@Pete.Ty1 Год назад
👍👍👍 Thanks.
@eastcoastuk1120
@eastcoastuk1120 Год назад
Where is the building inspector. They have to be involved on structural work. They would not have allowed a prestressed lintol in that situation surely.
@kingofthetrowel1725
@kingofthetrowel1725 Год назад
My thoughts exactly, needs an SE and a building control application, that needs sorting ASAP
@mitchmix999
@mitchmix999 Год назад
Composite Vs non-composite are the 2 types. One needs bricks above it, the other can take direct load.
@mikesmith1485
@mikesmith1485 Год назад
Roger, what's going on with the desk and multi-screens?...you look like you're presenting Sky news! Kidding, mate. Love every bit of your content.
@SkillBuilder
@SkillBuilder Год назад
We have something planned which is going to be coming as soon as we sort out a couple of technical issues with the studio.
@karl5395
@karl5395 Год назад
Shows how important it is to now protect unsuspecting customers and regulate the industry to prevent any upstart calling themselves a builder imo.
@phil2544
@phil2544 Год назад
A 9" x 6" concrete lintel for that span is a must, a single course lintel is bound to sag
@lenb9037
@lenb9037 Год назад
The wall below the eaves/ceiling level should definitely be described as load bearing if there is a brick wall above. All lintels of this type with brickwork above must be designed for the weight of a triangular brickwork area directly above in accordance with the relevant standards (which assumes the brickwork above the triangle will arch and support itself). In this case the depth of brickwork above the lintels at either end may not be sufficient to conform with the relevant standard (i.e. insufficient to arch properly above the nominal triangle) due to the gable shape and a more liberal loading should be adopted for the lintel design.
@glennpowell3444
@glennpowell3444 Год назад
On my extension( single story) I used a steel that accomodated the block and brick over the door and window.Very little load on it but under building notice it should and would be capable in the future of supporting a second storey above if that was ever done not that I will but in the future someone may.Much like the footings I built it on.Able to support another storey easily.To be fair UK building regs are as good if not better than any in the world structually.I prefer to over engineer any job than under engineer.
@kevinoak7558
@kevinoak7558 Год назад
Like someone said its not the UK? It would be steels with UK regs and that pillar looks ropey too, would probably be a steel too in UK. As it stands it probably won't crack more so just fill it if its definitely got no loading but I'd want a structural engineer to have a look.
@nonoyorbusness
@nonoyorbusness Год назад
Ugh get rsj's in there ASAP!
@C4sp3r123
@C4sp3r123 Год назад
0:43 you can see the electrical panel - that looks like a USA panel, that might explain some of the points and issues and techniques used.
@SkillBuilder
@SkillBuilder Год назад
Could be S.A
@peterthebricky
@peterthebricky Год назад
As you said Roger prestressed lintels are supposed to have 6 courses over and anything over a metre is supposed to have a 150mm bearing that looks like 100mm also there's often a way up to them too I took one out of the garage door opening on a townhouse Ashford that had a crack in the middle when we got it out there was an arrow on the front pointing down, it had been layed upside down 9" deep with one rebar in at the bottom
@SkillBuilder
@SkillBuilder Год назад
Isn't the rebar supposed to be at the bottom?
@peterthebricky
@peterthebricky Год назад
@@SkillBuilder yes I didn’t make it clear, the lintel had one piece of steel at the bottom with an arrow pointing upwards but it was layed upside down with the arrow pointing down
@ianscottuk
@ianscottuk Год назад
So if it has a set of bricks on the top, presumably as they are rigidly connected, they become part of the beam and are in compression? Hence why you can get away with the plank sizing.
@andyalder7910
@andyalder7910 Год назад
Easier to install upside-down since any bow won't hit the bricks above it!
@jameswiggins4236
@jameswiggins4236 Год назад
There’s not a lot of bearing by the looks of it either roger, can’t believe that was knocked out without a strong boy in sight 😬😬
@tinytonymaloney7832
@tinytonymaloney7832 Год назад
You look like a Radio 2 presenter sitting there all wired up 😂
@SkillBuilder
@SkillBuilder Год назад
Are there any left?
@stevehallam6495
@stevehallam6495 Год назад
I think pretty much everything is covered in the comments. Brickwork really needs to be built over them as you go and fully propped until it has cured. There is plenty of room to use 150mm lintels or steels. I certainly wouldn't consider using such a lintel on this span retrospectively.
@sonnythatcher
@sonnythatcher Год назад
Issues like this is why we use structural engineers. Above our pay grade to understand why it's not enough to take the load 😅
@enjek5654
@enjek5654 Год назад
The span is way too long for any notable load for a prestressed concrete lintel of that depth to provide structural support. I’d never design one for a span over about 1.6/1.8m. Roger, did you ask the guy to send the structural calculations? Does he have any?
@MrDunosan
@MrDunosan Год назад
Don’t stress out too much as it is that tiny pilar in the middle that failed 😅
@Sandysand701
@Sandysand701 Год назад
looks like the lintel is not sitting on enough brick! Not a reason for it to crack though. Can only see cracking in the plaster work! Could the lintel be Ok behind the plaster?
@ReedikTuuling
@ReedikTuuling Год назад
The point of building the brickwork on top of the concrete lintel is that the bricks "hold the end of the lintels down" and also the mortar ties lintel and the bricks together. If you just squeeze the lintel under the existing brickwork you support the ends of the lintel on the bricks at the ends and the lintel doesn't really support anything (the bricks will "float" above it, even if there is no gap) - sooner or later you get this "triangle" above it because those are the bricks it was supposed to support. In this case I assume the lintel was soo long (and maybe upside down) and sagged on its own weight even without the bricks pushing down on it. Assuming the lintel could have supported the bricks above - if you laid the bricks on top of the lintel, they would have bent the lintel a little, but because everything would have "sagged together" you don't get a crack anywhere.
@peterknight2176
@peterknight2176 10 месяцев назад
Lintel not strong enough or packed properly under brickwork above ?
@JuxZeil
@JuxZeil Год назад
I'm not sure why they didn't use steel box lintels...you can get them made to just about any dimensions and you can offer them to the upper coarse because you're allowed to pad the ends. 🤷‍♂
@petemarshall7784
@petemarshall7784 Год назад
from what I can tell from the pics i would say it is load bearing, but would need to see more to say for sure. but either way you need to get somebody to look at it properly and im guessing rip it all out an put steels in.
@johnf3326
@johnf3326 Год назад
Simple rule in sizing: If it looks right it is right and vice versa
@scottnever8732
@scottnever8732 Год назад
continuous wall ? how is that not load bearing?
@stephengreen6338
@stephengreen6338 Год назад
You could maybe educate me Roger, but thats a hell of a span for a 75MM lintel init?, just asking
@SkillBuilder
@SkillBuilder Год назад
They sell that lintel so it must work under the right conditions
@davesheffield3620
@davesheffield3620 Год назад
I’m not a builder but I would want a structural engineer to see that before any works done , I would hazard a guess this was done let’s say on the cheap.
@jharris7407
@jharris7407 Год назад
How’s that been passed by building control ?
@Johnny5Toy
@Johnny5Toy Год назад
What did you mean by "equalised"?
@scottnever8732
@scottnever8732 Год назад
? how did building control pass this? Bearing is too short and as stated should be a steel or load bearing lintel.
@paulmcdonald8055
@paulmcdonald8055 Год назад
Imagine that the pre stressed lintel was installed upside down? The bow pointing downward???
@mickg770
@mickg770 Год назад
Should have put a steel in on pad stones job done
@SA-vz7qi
@SA-vz7qi Год назад
It seems a very odd choice, I would assume the length would make a steel the optimum choice. I tend to assume when space isn't a premium you don't want it to feel marginal.
@8bitsim
@8bitsim Год назад
First thing is this sort of structural work needs building reg's approval and if you do that you'll need structural calculations for the lintels. A structural engineer would specify a steel for this job, single course pre-stressed concrete lintels are generally just for small spans and standard/light loads. It really is worth the extra expense of doing it with BR approval as not only will you sleep easier and have no problems but when you come to sell the house you can run into big legal issues with the solicitor costing you much more than the few hundred it would have cost you to do it properly.
@SilverTrowel631
@SilverTrowel631 Год назад
Did they go through building control? Did they use an engineers design? Or was this the builders idea? I suspect the latter. Which may cause an issue when they try to sell the place. Any search by a surveyor will show the work was never signed off and it'll need retro inspection. If they went through building control and an engineer, the install must be wrong. Maybe it wasn't packed well. But my feeling is that they should have used RSJ's. I cant see how it's a non load bearing wall with that gable above. And that supporting pier don't look sufficient, it should maybe have been a steel post bolted to the RSJ's.
@thewoodmuncher8140
@thewoodmuncher8140 Год назад
A non load bearing wall would terminate within the floor/ceiling joist
@philipwhiteman6134
@philipwhiteman6134 Год назад
thats not in the uk looks like south africa
@davideyres955
@davideyres955 Год назад
South Africa’s tends to have better building standards.
@jannenreuben7398
@jannenreuben7398 Год назад
Not surprised that has cracked. All the loading from the gable end brickwork is now transferred through that tiny central column into the foundation. The two side walls will be under increased stress too. I'll bet they didn't check that whatever was underneath was capable of dealing with the increased load. In fact I'd wager that whichever shaven monkeys did the work didn't check anything much.
@domfranks85
@domfranks85 Год назад
The beam is upside down 💯 the force is wanting to push down centrally
@ADF-js9vi
@ADF-js9vi Год назад
Do the concrete lintels not have a top and bottom? How can the manufacturers determine in which direction they will bow? Is it by placing the rods offset within the concrete? 🤔
@SkillBuilder
@SkillBuilder Год назад
some do some don't. In a plank lintel the rods are in the middle and you look at the bow.
@ADF-js9vi
@ADF-js9vi Год назад
@@SkillBuilder Thanks. Just can't understand how, if the rods are in the middle the direction of bow can be controlled? Surely each rod could be working against the others? 🙂
@robertstainforth6890
@robertstainforth6890 Год назад
Surely a gable end wall is a load? Too much flex on a lintel that thickness with the span. When built in from the beginning the cement bonds to the lintel making it far stronger …
@Johnjoe321
@Johnjoe321 Год назад
That’s horrific that they used 75mm concrete lintel instead of RSG, that was to cut cost corners.🤠
@timothykeech7394
@timothykeech7394 Год назад
The reason prestressed lintels tend to arch upwards should be because stressed reinforcement is placed below centre and the off-set results in an upward bending tendency. Could it be possible that they have installed this lintel upside down? That would greatly reduce the strength of the lintel, not necessarily catastrophically if it is not heavily loaded, but it could account for the cracking. As an ex- structural engineer, albeit with limited experience, that was my first thought.
@howardosborne8647
@howardosborne8647 Год назад
Your description of tensioned wire reinforcement placement is absolutely correct. I spent some years working for a concrete fabrication company who made all types of concrete lintels and this as you describe is exactly how the moulds and reinforcement were set up before pouring.
@timothykeech7394
@timothykeech7394 Год назад
@@howardosborne8647 When I was working as a structural engineer my job was to do the design calculations for reinforced and pre-stressed concrete beams, columns and slabs. I did not do this for long - hence my stating I'd had little experience - but the principle I described I know is correct. I guess I had enough experience to know that the basic principles haven't changed but, just to date my knowledge, I did my calculations on a slide rule.
@robertapreston4200
@robertapreston4200 Год назад
This is a mystery Roger, there is an inside on this side of the wall and an outside of the wall. So, basically, there is no brick work in the middle of this home. Is there? Curious, because you are awesome, but maybe the pictures are just misleading.
@stevenolivero5207
@stevenolivero5207 Год назад
when I did building work with concrete lintels or even steels in this way I would tress the lintels by hammering wedges between the centre brick and lintel or beams so it took the load, basically taking the slack out of the lintel or beam
@lksf9820
@lksf9820 Год назад
What were your wedges made from?
@ricos1497
@ricos1497 Год назад
​@@lksf9820cheese I believe. Bloody expensive these days though.
@lksf9820
@lksf9820 Год назад
@@ricos1497 Wenslydale then, Dairylea would be no good here.
@stevenolivero5207
@stevenolivero5207 Год назад
@@lksf9820 chisels or a bit of steel, it doesn't matter of the material at it can be removed after pointing up, there are many ways to put a lintel under a bit of stress,
@jeffmaxwell8821
@jeffmaxwell8821 Год назад
Obviously does not have Building Control consent either ! If it collapses someone will be up in front of the judge for manslaughter charges. I can’t emphasise the need to get professional help with building alterations
@philipbennett2183
@philipbennett2183 Год назад
Just a question (driffting somewhat) What became of Roger and Rob Clevett ??, thought they were big pals.
@SkillBuilder
@SkillBuilder Год назад
Robin is focusing on building the 'Robin Clevett' brand.
@isctony
@isctony Год назад
I can't see how that is not load bearing, looks like they need to prop asap and get some steels in there
@TABRO284
@TABRO284 Год назад
I do not like the look of any of that, it does not look safe. Have they plastered directly onto the concrete lintel? the same coving is visible in the before and after. At 1:18 The original plaster on the brick seems to be flush with the side of the lintel.
@colrunswild4adventure781
@colrunswild4adventure781 Год назад
I would have got a structural engineer to look at the job to calculate the opening for the correct lintel of steel.
@marie-anncapps9733
@marie-anncapps9733 3 месяца назад
Hi… we have a cracked lintel in an old Victorian house. I can send you pictures. We have insurance coming to look at it but thought would we would as your advice.
@SkillBuilder
@SkillBuilder 3 месяца назад
yes please www.skill-builder.uk/send
@accobra456
@accobra456 Год назад
they put the pre stressed side arc facing down
@MarkUKInsects
@MarkUKInsects Год назад
that was my thought too. I have used dozens of these, and there is always an arc. Not sure of what they are bedded on either, from the photos looks like excessive mortar, but I could be wrong?
@peternunn7104
@peternunn7104 Год назад
This hasn't been seen by building control or a structural engineer, it is not safe, you need to get some props under this soon as possible, is the concrete floor beneath the central peer capable of holding the weight.
@paulthompson5416
@paulthompson5416 Год назад
😂 gable end is not load bearing? I’d love to see him lift it down and pop it back up if there’s no weight in it 😂 Not like brick:block have any weight to them or the roof tied in would add any additional pressure. I’m with Rodger a steel would have been a better job, plus as we all know the fire retardant paint makes the steel 10 times stronger again 👌🏼👌🏼
@bluevanmani
@bluevanmani Год назад
Those 75mm precast lintels are non load bearing!!!!
@MrMattoneill
@MrMattoneill Год назад
I think he needs to get a structural engineer in for a look in case it is load bearing. Not convinced he's clear enough about that. Would have thought best practice would be two steels, and depending on the load possibly a column.
@FugitiveRazor
@FugitiveRazor Год назад
I'm no builder but that sht don't look safe I'd go and get some acros supports sharpish as that sht looks like it could drop any time soon.
@michaelfraser5723
@michaelfraser5723 Год назад
Roof no load , haha
@davenoble7350
@davenoble7350 Год назад
Just a guess. Could have been installed upside down, Then the acro has forced the lintel straight and now removed is bowing down again.
@TheWatchman1893
@TheWatchman1893 Год назад
Should of had the pillar removed all together and had a massive steel end to end
@michaelfraser5723
@michaelfraser5723 Год назад
Old brickwork is always loose, so it was going to fail,
@ChrisinHove
@ChrisinHove Год назад
One rule of thumb for rc is beam depth in inches = beam span in feet. That beam may have been installed on its side….
@EverydayLife621
@EverydayLife621 Год назад
Exactly 👍🏼 - and maybe a bit more given the load that it’s supporting above. It’s only a matter of time before the whole house comes down.
@johncrannastructuralengine8177
these concrete lintels are OK for a single door opening but the span of that opening is far too much for the capacity of the lintel and it has just over deflected. The builder has not consulted a structural engineer and just taken a guess at using that lintel. I suspect that he has not made a building regulation submission. The lintel is carrying load - the masonry above - so it IS load bearing. I am wondering if he thinks it is not load bearing that he doesn't need to make a build regs submission. As you rightly suggest Roger there should be steel beams going in for that span.
Далее
Roger Is Stumped by This Tricky Problem. Can You Help?
19:56
Why Has Your Wall Cracked? and What Can You Do?
11:53
Просмотров 856 тыс.
Stray Kids "Chk Chk Boom" M/V Teaser 1
00:40
Просмотров 740 тыс.
Why Retaining Walls Collapse
12:51
Просмотров 3 млн
Why Haven't We Warmed to Porotherm in the UK?
8:34
Просмотров 318 тыс.
What's the Difference Between Paint and Coatings?
14:23
MORE LINTEL PROBLEMS!!
36:14
Просмотров 43 тыс.
The Reluctant Builder and Why He Became One
16:09
Просмотров 47 тыс.
What Are Cavity Trays & Where Are They Used?
12:11
Просмотров 187 тыс.
Testing The Burn Ability Of Insulation In Wall
19:45
Просмотров 2,6 млн