Тёмный

WinCC v7.4 Step By Step #18: WinCC Tag Logging 📈  

WinCCGURU
Подписаться 3,2 тыс.
Просмотров 4,2 тыс.
50% 1

This is # 18 in our WinCC v7.4 tutorial Step By Step series, a WinCC SCADA Tutorial For Beginners. This video shows you how to log tag values to the SQL Server Database using SIMATIC WinCC version 7.4's tag Logging Editor. We will create a process value archive and add tags.
00:00 Introduction
00:25 Open Tag Logging Editor
00:44 Add a New Process value Archive
00:56 Add Tags to Archive
01:37 Set Acquisition & Archive Cycle
01:56 How do archiving cycles work?
#scada #scadaprogramming #scadasystem #wincc #siemens

Опубликовано:

 

5 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 11   
@WinCCGURU
@WinCCGURU 2 месяца назад
WinCC 7.4 Step By Step full Playlist: ru-vid.com/group/PLGP1qT2NhERx6zzbmqDBjZgV8N-YNY9vk
@davidweingartner5513
@davidweingartner5513 5 месяцев назад
Is it the same for a server client system?
@WinCCGURU
@WinCCGURU 5 месяцев назад
Yes it is. All tag logging configuration is done on the server. the clients all connect to the project through the server and can show trends, etc.
@vorapobautomation9760
@vorapobautomation9760 Год назад
Dear Sir, What is the meaning of Mesaage Text"failure feeding unit F(@1%d@)" and Xref D4.4 ?
@WinCCGURU
@WinCCGURU Год назад
Hi : The Alarm Logging Message Text above is pulling in a live process value from Process Value block number 1 as an integer (d). The @ signs at beginning and end are delimiters. If you look at the alarm message were this message text came from, there will be a tag assigned to Process value Block #1 which provides the integer data. So when the alarm occurs, the message text will look like: "failure feeding unit (3)" given that the defined tag value in process value block # 1 is value = 3 at the moment of the alarm. As for 'Xref D4.4' -- can you give me some context? is it part of the alarm message?
@vorapobautomation9760
@vorapobautomation9760 Год назад
@@WinCCGURU Yes Sir for WinCC V7.0 it has Xref column too.
@WinCCGURU
@WinCCGURU Год назад
@@vorapobautomation9760 its likely a text block (xRef) column and the D4.4 is a cross reference value or address put there to help determine the cause of the alarm; but without seeing the project I couldn't say.
@syamlyanatomy
@syamlyanatomy 8 дней назад
Will the alarm data will get stored in SQL?
@WinCCGURU
@WinCCGURU 8 дней назад
Yes. As well as tag logging data
@syamlyanatomy
@syamlyanatomy 7 дней назад
@@WinCCGURU any video available, how tag logging data gets stored in sql?
@WinCCGURU
@WinCCGURU 7 дней назад
Working on it 😀
Далее
WinCC 7.5 Insert Data into SQL
4:46
Просмотров 18 тыс.
На фейсконтроле 💂
09:41
Просмотров 457 тыс.
Это iPhone 16
00:52
Просмотров 522 тыс.
SCADA Tag Logging
10:25
Просмотров 2,4 тыс.
SCADA WINCC Tag Logging - The Basics
19:49
Просмотров 21 тыс.
Indirect tag winCC
14:09
Просмотров 12 тыс.
Lecture#9: Tag logging / Trend display in WINCC V7.5
37:57