Wiring ICF Walls!!! 

Cutting Edge Homes !
Подписаться 19 тыс.
Просмотров 40 тыс.
50% 1

In this video I address a common question regarding ICF construction, how do you run wires in the foam walls with no stud spaces? My very first ICF related video touched on this same topic but ultimately is a bit dated and the audio is bad so I'm redoing that video and adding a lot of detail I wish had been in the original!

Хобби

Опубликовано:

 

3 дек 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 69   
@dericktharp5796
@dericktharp5796 Год назад
Your the Absolutely best Hand talker I’ve ever witnessed!! I’m envious!
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
😊 thank you!
@shakejones
@shakejones Месяц назад
Great video+explanation! Thank you for sharing your knowledge! Well done mate 🙏🏻
@JoseLopez-dy7iz
@JoseLopez-dy7iz Год назад
Aaron thank you for the details for the DIY's. I was nervous in thinking of building my retirement home in ICF but this has opened my eyes and blow my mind with how easy it is. Looking forward to the next videos and to your Angel Fire build!
@BlackmerStudios
@BlackmerStudios Год назад
Thank you for sharing these “simpler” steps to working with ICF. These are exactly what I’m looking for to build and finish my own cabin. Looking forward to the siding video. Thanks again Aaron!
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Thanks!
@drewmorrison2303
@drewmorrison2303 Год назад
So awesome! This is gold. I plan on building in 2024 so I am soaking all this in
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Thanks!
@mattgirgenti3595
@mattgirgenti3595 Год назад
I was literally just researching the 'how not to hit a wire' when this video came out. perfect timing and the video showed the process perfectly. Than you. next on my list is the same question with not hitting the pex pipe with screws ... :)
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Same answer regarding pex although it would be a little bit more possible…. Generally though pex will deflect screws only pulling through drywall, meaning they usually need to be pulling through wood or plastic to have enough pull to grab the pex and pierce! But if you managed to hit one dead center I suppose it could occur albeit unlikely, you can also take not of where the pex is and consciously avoid the area, there’s usually only a few pex lines running in the icf walls themselves
@truthtalker4711
@truthtalker4711 Год назад
Siding will be cool, love these videos.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Thanks!
@8thlineenterprises343
@8thlineenterprises343 5 месяцев назад
Some great tips here. Thanks.
@cuttingedgehomes9251
@cuttingedgehomes9251 5 месяцев назад
You’re welcome!
@jeffquine8883
@jeffquine8883 3 месяца назад
The electrician that wired my home had different bars with holes he drilled in them for different thickness Styrofoam for the ICFs. He mounted a roller skate wheel with a bolt to the chainsaw bar. He zipped out the cuts for the wire in no time.
@JRP3
@JRP3 Год назад
Do you ever use conduit in the foam for extra wire protection?
@T.I.N.D
@T.I.N.D Год назад
Metal conduit IS allowed and it would be great for extra protection. But anyone out there doing the labor isn’t going to readily want to run conduit through ICF primarily because of cost and effort. So yes, you can and may see it done, it’s convenient later on but it’s tough to get rough in for ICF
@wrfarms9741
@wrfarms9741 Год назад
Please be sure you include the core drilling of the hole for the electric service to your circuit breaker box in the follow up to this video. I definitely want to see how that works. I like the idea of using the chainsaw to cut a channel for the wiring. Do you think it would be better and more cost effective to cut a much larger channel and include plumbing in the same area where it makes sense, or is this against code? Really looking foward to the next video of installing exterior panels. I am considering using steel panels for longevity and fire resistance.
@Iuliancik
@Iuliancik Год назад
I am guessing all the pvc pipes were done before concrete pour, so no coring would be needed
@butopiatoo
@butopiatoo Год назад
Thx for the fir out the wall in a mechanical room tip. I've got that situation and wondered. Amazed you can get the cans in that deck, guess it's just a matter of how much foam is available to cut out. Confused why you didn't screw the outlet boxes into the concrete. Do you level/rough sand the wall before you sheetrock? just looks like a lot of "stuff" protruding.
@InquiryTeaching
@InquiryTeaching 4 месяца назад
provided you shimmed up level a quick squirt of foam is solid and quick, plus satisfies securing the wire within 6 inches from the box. Loctite 3xl also works.
@darrenure2323
@darrenure2323 Год назад
Does removing foam, significantly affect the R value? Thanks, loving these videos. I am in the early stages of planning an extension to my house in Scotland and would like to use ICF. good to see these hints and tips.
@EvermontKing
@EvermontKing 11 месяцев назад
No
@antonkachulkin6980
@antonkachulkin6980 Год назад
Hi there and Thank you for all of your video!) How do you protect electric and plumbing from accident nails etc?! Very important topic but no one talks about it.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
So if plumbing is close to the surface for some reason mail plates are generally used, electrical it’s rarely necessary because we typically embed the wires 2” deep, which is the same as the center of a stud, with the beautiful added detail that once we cut through the web there’s no meat for a mail or screw to bite into to pul it into the wire like it can in a wood stud, if u inadvertently put a drywall screw on top of the wire channel(won’t reach typically) but it will simply strip out the drywall because there’s no longer a web their to but!
@T___Brown
@T___Brown Год назад
Id suggest creating a melter by using nichrome wire and a 12/24v DC power supply. No mess. Little fumes but mask and open air is fine.
@InquiryTeaching
@InquiryTeaching 4 месяца назад
hot knife... amazon or ebay. No need to reinvent
@jhippl
@jhippl Год назад
your local inspector must be nice, mine made me staple the romex with in 12 inches of every box including into the concrete. (NEC 336-18) He also mentioned that the boxes I used were wrong because I was using them in a way that the manufacture didn't specify in their install instructions. (370-23(a) through (h)) he wanted me to use metal surface mount boxes and screw them into the concrete. Not that I agreed with him but I had to do what they wanted.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
That’s just silly…. Inspectors can be the best friend or worst enemy of innovation…. Our inspectors, especially the one known to be the toughest and most anal, love icf and are generally enthusiastic to see what we are doing! They’ve been helpful regarding great areas such as pool bonding too
@christopherbeddoe406
@christopherbeddoe406 Год назад
Mounting metal boxes to concrete is less than Ideal. Forcing you to staple wiring into concrete is nuts. If you lock the wiring in with spray foam it is 100% secured along the entire run. Can't get better than that.
@ToddBizCoach
@ToddBizCoach Год назад
@@cuttingedgehomes9251 there is a need for building inspectors to view inspector educational videos ( that are building inspector approved)showing approved procedures involving ICF for Home construction: electrical, HVAC, plumbing and framing.
@clarkharms
@clarkharms Год назад
I am glad someone brought up the need to secure wires near boxes. This is technically correct for traditional builds and unfortunately building inspectors can be ignorant of anything they are unfamiliar with. I have pushed back on building inspectors and appealed to the state, I am a homeowner not a contractor, so I have less to lose since I don’t need to have an ongoing relationship with the inspectors. The last building inspector I dealt with was a complete a-hole and was eventually fired. He certainly did not understand the law and tried to prevent me from installing my own solar thinking he had absolute authority over everything, his ego got the better of him. Anyway before building I would definitely sit down with the building inspector and explain exactly what you plan to do and make sure he/she/they/them approves of how you intend to install everything then get that in writing on your permits. Even if you have ten pages of attachments explaining the details it is well worth it when they forget what they approved several months earlier.
@Dead_Aim556
@Dead_Aim556 Год назад
Correction fox block foam thickness is 2-5/8”
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Thank you for straightening that out for me;)
@icfsystem7514
@icfsystem7514 Год назад
I would like to introduce a new ICF WALLS Equipment that will change your life on ICF construction
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Email me support@icfguru.com
@billmccance7762
@billmccance7762 Год назад
AMVIC ICF it easiest to make horizontal chainsaw cuts for wire at the seem between two blocks because there is no web there
@aldenpines
@aldenpines Год назад
Why not build a simple plywood chase over the panel for the wires?
@stuartoates424
@stuartoates424 Год назад
By far the best way to run wireing ICF is to run smurf tubing in the cavity with Plastilock boxes. Easy to pull any wiring or replace it. Total protection and so much cleaner and quicker
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
For sure not quicker…. Are you saying to place them before the pour???
@stuartoates424
@stuartoates424 Год назад
Yes,run the smurf in the cavity,either 1/2 " or 3/4" tie to web either side of a join. Done it 100s of times and never had a failure.
@danthurman9076
@danthurman9076 5 месяцев назад
Much simpler to just run a piece of 2 inch pvc to drop the wires into the top of panel.
@cuttingedgehomes9251
@cuttingedgehomes9251 5 месяцев назад
No it’s not…
@danthurman9076
@danthurman9076 5 месяцев назад
@@cuttingedgehomes9251 😂 😂 for sure you can just break out all of the knock outs for wire, put in romax connectors, strip the wire, connect to the neutral and ground terminal, and connect to the breaker.
@ericsyre9418
@ericsyre9418 Год назад
Wouldn't using a hot knife a lot less messy? These foam beads stick to everything.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Way slower and not great in the webs, but yes, less messy
@clarkharms
@clarkharms Год назад
Vacuum at the end of your chainsaw bar may help with the mess but your method is better than hot knife when trying to cut through webs it would take too long with hot knife.
@jackgibbons6013
@jackgibbons6013 Год назад
Are you not concerned about the foam sucking the plasticiser out of the cable sheathing, making it super brittle, and then having short risks if the cable ever moves (around the box or something)? I thought you were supposed to have conduit or something to protect the cables from this.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
No, you actually aren’t suppose to run romex in conduit…
@mintheman7
@mintheman7 Год назад
Why not just fur out the ceiling and install thin profile LED lights, should be much easier and you only lose 1-2 inches of height.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
Huh?
@mintheman7
@mintheman7 Год назад
@@cuttingedgehomes9251 Modern LED's don't need a huge ceiling box like the ones in the video. 1.5" deep boxes are sufficient. Just use 2" furring strips on the ceiling to run the wires and the boxes, that way you don't have to dig into the ICF at all.
@yavor19121
@yavor19121 5 месяцев назад
Just get a propane torch instead to cut the styrofoam.
@cuttingedgehomes9251
@cuttingedgehomes9251 5 месяцев назад
Lol how bout the webs???
@Bonserak23
@Bonserak23 8 месяцев назад
Crack kills
@cuttingedgehomes9251
@cuttingedgehomes9251 8 месяцев назад
Thanks for watching
@AnthonyAlvarado78
@AnthonyAlvarado78 9 месяцев назад
Seems like it would have been easier to run wire before filling it
@cuttingedgehomes9251
@cuttingedgehomes9251 9 месяцев назад
Not remotely
@RS-lt2ue
@RS-lt2ue Год назад
Aaron, take a look at the email I sent you several days ago, if you would, please.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
What’s your address? I can only see your initials here
@RS-lt2ue
@RS-lt2ue Год назад
@@cuttingedgehomes9251 Just reply to your email address.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
@@RS-lt2ue what email are you sending to? Support@icfguru.com or aaron.cuttingedgehomes@gmail.com? I don’t see a new message but perhaps it hasn’t come through, if it was days ago try resending, sorry I get a lot of emails and it may be buried
@NYa-mo7se
@NYa-mo7se 2 месяца назад
Please don’t take this short cut. Run conduit.
@cuttingedgehomes9251
@cuttingedgehomes9251 Месяц назад
You have no idea what you are talking about…
@abigailslichter6706
@abigailslichter6706 Месяц назад
This is one of the reasons you use ICF’s. Looks Great keep up the good work!
@joelaplaca293
@joelaplaca293 7 месяцев назад
butcher
@cuttingedgehomes9251
@cuttingedgehomes9251 7 месяцев назад
?
@Krazie-Ivan
@Krazie-Ivan Год назад
Heh, found you via the og version of this vid way back. Hope to make it out to AF next summer, learn more, & talk about some wild ideas I've got for nearly PassivHaus on the slimmest budget.
@cuttingedgehomes9251
@cuttingedgehomes9251 Год назад
That’s awesome! Ya angel fire is going to be legit, hopefully putting the finishing touches on numbers at world of concrete…. Assuming interest rates don’t do anything more than what’s expected and materials stay stable I’m pretty fired up about it!
Далее
ICF Review!  Fox Blocks vs Nudura?
17:41
Просмотров 158 тыс.
FARUX RAIMOV AVJIGA CHIQDI - JAVOHIR🔥
01:01
Просмотров 634 тыс.
ICF True Cost Spring 2023
14:22
Просмотров 42 тыс.
How to install electrical wiring into ICF walls
8:03
Waterproofing Benefits of ICF
1:18
Просмотров 265
ICF Foundation with Insulating GRAVEL?
9:03
Просмотров 161 тыс.
How to frame a curved wall
15:42
Просмотров 36 тыс.
ICF True Cost!!! Summer 2023 Update
15:01
Просмотров 19 тыс.
How to bend and install electrical conduit
20:14
Просмотров 1,3 млн
Married Couple Saves 20K DIY-ing ICF!!!
16:53
Просмотров 19 тыс.
Застрявшее Кольцо 🤯
0:26
Просмотров 5 млн
Умеют рыбки половить 🤣
0:27
Просмотров 3,1 млн
Recycled Car Tyres Get a Second Life! ♻️
0:58
Просмотров 23 млн
#shoot
1:00
Просмотров 6 млн