Hello Dear Friends,
I'm currently working as control and instrumentation engineer. I have more than 3 years experience in power plant C&I maintenance.
Therefore I requests you to subscribe my channel for regular updates of power plant instrument maintenance and calibration of pH/conductivity/ORP Sensors, Silica analyser ( Hach 5500sc ), pressure guage/switch, level sensors etc.


Your feedbacks and requirement of C&I instrument maintenance are most welcome to improve my channel so please comment on video and if it helps you than don't forget to share with friends.
Комментарии
@lakhendrabaghmar7261
@lakhendrabaghmar7261 13 дней назад
Sir. Run 3 और run 5 क्या दिखाता है
@jitubabusay2826
@jitubabusay2826 Месяц назад
19 mA mai 100% open karna hai to kya kare please batayiye
@SonuKumar-ju2ok
@SonuKumar-ju2ok 2 месяца назад
Zero karne ke liye bhi +ve and -ve button ek sath press kar rahe h and 100 karne ke liye bhi same kar rahe h ?
@shantilaldhakar9967
@shantilaldhakar9967 2 месяца назад
Action fast karne k liye Aisa Kiya ha.
@shantilaldhakar9967
@shantilaldhakar9967 2 месяца назад
+ve button press & hold and then press -ve button In this way your action become fast.
@himanshushekharpandey7186
@himanshushekharpandey7186 7 месяцев назад
Thnx via
@shantilaldhakar9967
@shantilaldhakar9967 7 месяцев назад
Its my pleasure.
@vinaysane5435
@vinaysane5435 9 месяцев назад
Very Good &Knowledgeable Video.👍👍👍👍👍💐💐💐💐💐🙏🙏🙏🙏
@sunilrathod663
@sunilrathod663 11 месяцев назад
Thanks bhai
@sambalpurisongsulhabaysi.8343
har waqt kya dono + aur - button ko press kar k karna padega...agar nahi to dono ungli se kyon chek dete ho...
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
Har waqt nhi, Jab quick open ya close karna ho tabhi Aisa karn ha.
@Diwa94
@Diwa94 Год назад
up and down dono saath me push karte ho , ye to bolte nhi ho
@haidarquarrar8848
@haidarquarrar8848 Год назад
Sir auto calibration me run 2 me fans jaraha aur P 8.1 uske niche fault ka symbol and up 1 show kar raha Hai kaise setting karenge
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
Valve is either jam or may not open/close properly. There may be air leakage from seal/diaphragm in output side. Check for these issues
@vinaysane5435
@vinaysane5435 Год назад
Excellent Sir & Very Thanks for showing how to calibrate Siemens Sipart PS 2 Positioner. Very Thanks Sir. 💐💐💐💐💐💐💐🙏🙏🙏🙏🙏🙏🙏
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
Thanks for appreciation 👍
@sagarmali8393
@sagarmali8393 Год назад
What is meant by U- di error
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
means positioner feedback is inappropriate with respect to command signal.
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
futher you may adjust it by roller gear mounted just below display.
@Ajayyadav-nh3qb
@Ajayyadav-nh3qb Год назад
how to set her feedback deviation
@MdAli-vg2ko
@MdAli-vg2ko Год назад
Nice
@GauravKumar-xu9gh
@GauravKumar-xu9gh Год назад
I have confusion for parameter 7 and 38 could anyone can explain please.
@odishabirdlovers3827
@odishabirdlovers3827 Год назад
Mera position reverse may kam kar rahahey kya karu
@shantilaldhakar9967
@shantilaldhakar9967 Год назад
Check parameter no. 7 and select proper parameter i.e. “rise” or “fall”. Your problem will be resolved.
@odishabirdlovers3827
@odishabirdlovers3827 Год назад
@@shantilaldhakar9967 thanks
@RamSingh-nj8mr
@RamSingh-nj8mr 2 года назад
If positioner not operate in manual mode & not vary the opening percentage during manual command from positioner Plz help & how to contact you
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
My contact number 8003228484
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
May be air supply pressure is not sufficient or control valve/actuator is mechanically jammed.
@madhavrabari4756
@madhavrabari4756 2 года назад
🙏 Thanks 🙏
@instrumentpower6380
@instrumentpower6380 2 года назад
सर मैं जैसे ही End1 देकर hand press कर रहा हूं Range लिखा आ रहा है End 2नही आ रहा है क्या चेक करू
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
“Range”means your range selected in “End1” or “End2” is incorrect. Please set it inbetween 10% to 85% at zero and span respectively. 👍
@soumyaranjanjilu7816
@soumyaranjanjilu7816 2 года назад
Thanks for this video bt sipart ps2 all models calibration plz video make
@Marafeq344
@Marafeq344 2 года назад
Thank you for the video
@jamesmanuelcaetanobotelho6236
@jamesmanuelcaetanobotelho6236 2 года назад
Hello sir how to fix new sipart PS2 turn actuator and do setting on it
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Only Parameter no. 1 is to be selected as “turn” instead of “Lin” . Remaining procedure is exactly same. 👍
@jamesmanuelcaetanobotelho6236
@jamesmanuelcaetanobotelho6236 2 года назад
@@shantilaldhakar9967 sir if I had given the same supply 4-20mA coming from circuit anything will happen to sipart controller or need to give external source supply to simulate it.
@jamesmanuelcaetanobotelho6236
@jamesmanuelcaetanobotelho6236 2 года назад
@@shantilaldhakar9967 ok sir
@jamesmanuelcaetanobotelho6236
@jamesmanuelcaetanobotelho6236 2 года назад
Than answer my NXT question
@jamesmanuelcaetanobotelho6236
@jamesmanuelcaetanobotelho6236 2 года назад
Plz rply
@BhagwanSingh-sv3kh
@BhagwanSingh-sv3kh 2 года назад
Thank you helpful video
@thomaselsen1672
@thomaselsen1672 2 года назад
after a manual calibration, i am getting a negative number on the positioner display because the valve is seating which is desired but the negative number is not. How do i make the display read zero when going under the lower set point of the manual calibration?? Please Help!
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Your Positioner is mounted on which system i.e. Air to open/close actuator or power cylinder? Case 1: If ‘Air to Close’ type pneumatic actuator then check air pressure and ensure that it does not exceed specified limit. Case 2 : If power cylinder then you adjust through cushioning screw. And then repeat manual calibration procedure as explained in this video.
@thomaselsen1672
@thomaselsen1672 2 года назад
@@shantilaldhakar9967 it is a fail to close valve. On a diaphragm actuating control valve. The system set points requires the valve to jump up to 20% open as soon as any Ma signal is applied. So the valve was manually calibrated to set the lower limit to that 20% open so when Ma is applied it would automatically go to 20% open and achieve desired set points. Since the new 0% is manually calibrated to 20% open and the positioner closes the valve all the way to its seat once it gets the close signal. the display will read a negative number now because it thinks it is -20% to the seat. I was wondering if there is any way to zero that number out on the display or a better way to set up that valve to be able to achieve those set points. Thanks for the Help.
@mrinmoysahoo8626
@mrinmoysahoo8626 2 года назад
Agar run 1 ya run 4 ma error ageya to kya karna chahiye
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Error in RUN 1 means either actuator/power cylinder is jammed or air pressure is not sufficient. Please check air pressure, pressure seal condition and jamming of valve/actuator.
@mrinmoysahoo8626
@mrinmoysahoo8626 2 года назад
@@shantilaldhakar9967 thanks
@mrinmoysahoo8626
@mrinmoysahoo8626 2 года назад
Or run 4 kya matlab hai
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
@@mrinmoysahoo8626 It's my pleasure to help you 😊
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
@@mrinmoysahoo8626 RUN 4 : Positioner check and determine the minimum increment length so if error means there may be air leakage through actuator/power cylinder pressure seal parts. Please check and ensure that their is no any such leakages. 👍
@tariqueanwer9329
@tariqueanwer9329 2 года назад
Sir mera actuator 0mm tk close nahi ho raha hai please help
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Check your actuator specification and if it is air to close type actuator then set air pressure. Also, you may set pressure 5-10% higher than rated pressure. Secondly, if above things checked and ok but problem not resolved then ensure that actuator spring tension is ok or not. It may be due to high spring tension of actuator so adjust it properly. 👍
@vinaysane5435
@vinaysane5435 2 года назад
Very Thanks Shanti for sharing Valuable knowledge giving us about Auto Calibration of Siemens. Plzzzz tell us about how to go in parameter about air fail close or air fail open then control mode is digital or analogue,then how to perform manual calibration. Also if possible show ABB TZIDC calibration & ABB double acting Pisitioner calibration. Once again Very thanks. Best & Warm Regards, Vinay.
@8899122246
@8899122246 2 года назад
Feedback kaise set krenge
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Using rotary cluch , located just below display
@mdtausif6946
@mdtausif6946 2 года назад
Sar running abb control valve calibration out bata raha hai tu field mein kis equipment se calibration karenge sir please videos per banaaiye ham aapka subscriber hun
@surajkumarkhunte1181
@surajkumarkhunte1181 2 года назад
thank you
@aamirkh4064
@aamirkh4064 2 года назад
Thank you very much
@Hewagej
@Hewagej 2 года назад
Very good video Thank you so match
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Thanks for appreciation 😊
@bhagwansinghlodha939
@bhagwansinghlodha939 2 года назад
kavi kavi error aati h calibration nhi leta h wo
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Try manual calibration procedure.
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Check operation in manual mode.
@nikhilkapoor4561
@nikhilkapoor4561 2 года назад
Positioner display is not getting power on ....22 v DC ... What will be the solution
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
If power is healthy then it's interface card may be faulty. Solution: Contact to supplier/vendor for repairing/replacement.
@kunalpareta5908
@kunalpareta5908 2 года назад
Great job 👍
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Thanks
@janmuhammad2751
@janmuhammad2751 2 года назад
Good
@haidarquarrar8848
@haidarquarrar8848 2 года назад
Open karne keliye EK button ya do boton EK sath push karna zaruri Hai kya
@shantilaldhakar9967
@shantilaldhakar9967 2 года назад
Single button se slowly open hoga and Two buttons ek sath press karne se fast open hoga.
@haidarquarrar8848
@haidarquarrar8848 2 года назад
@@shantilaldhakar9967 thank you sir for reply
@haidarquarrar8848
@haidarquarrar8848 Год назад
Sir EK problem Araha Hai valve auto calibration karne ke baad bhi valve 20 % hai aur command bhi 20 % araha Hai auto mode me lekin dcs me 0%show kar raha Hai valve kya karun ki valve fully close hojayye valve hamara fail to close Hai
@AshokPrajapati-ec3qh
@AshokPrajapati-ec3qh 3 года назад
Good sir
@parmarnil4748
@parmarnil4748 3 года назад
0 jaga pe 100%dikhae और 100 % जगा 0 dekha to kya karne ka
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
केवल फीडबैक गलत आ रहा है या कंट्रोल रूम से कमाण्ड ही गलत आ रही है।
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
Check parameter No. 7 and 38. If position feedback is just reverse then change parameter no. 38 from rise to fall and vice versa. And if command signal is reverse then change parameter no. 7 as explained above. I hope you got solution, further feel free to contact if you have any query. Thanks
@jitubabusay2826
@jitubabusay2826 3 года назад
Hello brother I want to do reverse direction ,like When apply 4 ma That time should Full open & when apply 20 ma that time should Full close, plz explain
@sureshkumarverma5094
@sureshkumarverma5094 3 года назад
Thank you very much . Good information.
@abhijitpadhiary4349
@abhijitpadhiary4349 3 года назад
Thank you 🙏, Nicely explained.
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
Thanks
@hooshangalizadeh637
@hooshangalizadeh637 3 года назад
how to adjust the display contrast ?
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
please share details/model no. of your Siemens positioner. It will be like “ 6DR5051 or 6DR5052” .
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
I had gone through the positioner manual but did not find any information about contrast control. FYI 👍
@pradipkumaryadav252
@pradipkumaryadav252 3 года назад
If 41 blinking on screen then what will do
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
Check the Instrument air pressure, if it is not sufficient to open/close valve then this error occurred 👍
@sajidaziz2862
@sajidaziz2862 3 года назад
AoA sir my control valve ps2 positioner continue stuck on RUN 5 but not show finish option please giuide me
@sajidaziz2862
@sajidaziz2862 3 года назад
if stroke 20 mm then we select 90 or 30 but now i select 90 and selector switch on 90 same as follow in parameter 2 according to manual
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
@@sajidaziz2862 please select 33° angle and then lock that position at 33°.
@sajidaziz2862
@sajidaziz2862 3 года назад
ok i will try now
@sajidaziz2862
@sajidaziz2862 3 года назад
@@shantilaldhakar9967 sir but when we select 90??if stroke is more than 20??
@sajidaziz2862
@sajidaziz2862 3 года назад
@@shantilaldhakar9967 Thanks for guidelines my job is done.
@sreenubabu6488
@sreenubabu6488 3 года назад
Friend if possible English language
@sreenubabu6488
@sreenubabu6488 3 года назад
Thank you my friend..good job and very useful information
@manikr9465
@manikr9465 3 года назад
It was good informative video that who worked in instrumentation filed especially in fild side.if you possible plse put more different type of positioner configuration and caliberation. For instance azbil
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
Thanks brother for appreciation.
@SurenderSingh-sk3kn
@SurenderSingh-sk3kn 3 года назад
Bhai maan ge chorre
@parmarashvin3993
@parmarashvin3993 3 года назад
Sir ye 90°And 33 ° me kush samj nahi aa raha kush jyada jankari de sakte he please... Sir...
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
In case of linear actuators, if valve stroke is less than 20 mm then we select 33° transmission ratio else for valve stroke more than 20 mm we select 90°.
@parmarashvin3993
@parmarashvin3993 3 года назад
@@shantilaldhakar9967 ok thank you sir
@mayankparmar4850
@mayankparmar4850 3 года назад
Muje bi isme samaj nahi aaraha hy
@kirtandas1974
@kirtandas1974 3 года назад
Sir ek problem hai 100% command pe 66 % arha hai... Input Kya kare 12 no parameters me ja ke chenge kar ke dekh liya par ho nahi rha . Please iska kya problem hai btae
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
Factory reset your positioner and then re-calibrate in manual mode. If you got any issue then feel free to comment regarding problem.
@shantilaldhakar9967
@shantilaldhakar9967 3 года назад
RESET :: Go to parameter no. 50 and then press and hold “+” button for 5 seconds. This action will factory reset your positioner.👍
@Pawankavlog24
@Pawankavlog24 Год назад
@@shantilaldhakar9967 sir mere positioner me zero command dene pe 20% command aa rha h to kya problem hoga command zero nhi aa rha