A Day Of Electrical Fault Finding - Father & Son Electrical Team In London Vlog #7 

Eastway Electrical
Подписаться 37 тыс.
Просмотров 38 тыс.
50% 1

This episode follows us as we attend two call out jobs around London.
The first job involves faulty hob in East London. We arrived to discover that the savy customer had isolated the fault, we were able to test the circuit and establish the cause of the fault.
The second job involved a loss of power in Kensington. The customer complained that they heard crackling throughout the property. We went in to investigate and the job took an unexpected turn.
Enjoy.
social media
/ eastwayelectrical
/ eastwayelectrical

Опубликовано:

 

30 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 131   
@anelectrician
@anelectrician 5 лет назад
Sparkie ! Get yourself a head torch and work hands free.
@stevebrindley
@stevebrindley 6 лет назад
That loose / disconnected neutral on the db ! Looks like a newish meter ! I bet the installer pulled on it !
@blakehorton8110
@blakehorton8110 5 лет назад
It's alot different here in the states , were 120 volt 1 phase for residential dwellings , and our panels are much larger , but the same principle I see process of elimination , start at begening work your way back and can't go wrong !!!!!
@fasalmahmood71
@fasalmahmood71 5 лет назад
If one has to run an insulation resistance test in a property in which it is difficult to remove all appliances or sensitive fittings will it be sufficient to do the test on 250v and not cause any damage? Thanks
@JwiseTheRealist
@JwiseTheRealist 5 лет назад
Yes
@getduppiedrs9364
@getduppiedrs9364 6 лет назад
Del is ur son just an apprentice camera man?
@dragonboy1533
@dragonboy1533 6 лет назад
Fault finding can be quite daunting to some people, you do make it seem easy and as you say it’s not rocket science, but it also comes with years experience, still enjoying these videos 👊 will give a follow on Instagram!
@eastwayelectrical
@eastwayelectrical 6 лет назад
Glad you are enjoying the content, thanks again for the encouraging comment
@democracyforall
@democracyforall 5 лет назад
Most likely the problem may have been that some water had gone down to the cooker somewhere. The good man should have just opened up the cooker to see if that was the case.
@donnierobertson3088
@donnierobertson3088 4 года назад
Second time watching 5/21/2020
@PlymouthSparky
@PlymouthSparky 6 лет назад
Good one Delroy, it was sure tight in that cupboard. I love a bit of fault finding, find it always rewarding once fixed.
@eastwayelectrical
@eastwayelectrical 6 лет назад
Completely relate to you on that PS, rewarding is the perfect way to sum it up.
@kenallen9163
@kenallen9163 4 года назад
thank goodness in Canada we required to have 3 ft space in front of breaker box
@ricardosmith3621
@ricardosmith3621 5 лет назад
learning to be a sparky as to speak, glad I came across this video 👌🏾 keep em coming 👍🏾👍🏾👍🏾
@pjgd8639
@pjgd8639 6 лет назад
First time I’ve watched a video from you Delroy, being a spark myself I appreciated some of the jobs. Will defo being watching further videos, keep them coming 😀
@illegalfreedom1055
@illegalfreedom1055 4 года назад
What a shit location for the consumer unit 😂😂😂
@MrDaveozau
@MrDaveozau 5 лет назад
Totally stupid location for a consumer panel Definitely not legal for Australia
@johndufton9686
@johndufton9686 5 лет назад
Your ob is fooked but I'm gonna waste time to tell you what you told me.
@jamesgreen8079
@jamesgreen8079 5 лет назад
Nothing worse than an interfering customer 🤣
@dennell
@dennell 5 лет назад
The second job has a consumer unit and meter with cables that could quite easily be pulled on by children, knocked when carrying something up those stairs behind them... whatever. To top it all off there's no isolation between incoming electric and meter (which should have been done when the smart meter was fitted)... This type of installation is surely against regulations and the whole CU and meter should be at least boxed in for safety... My guess would be that someone has come in through the front door drunk gone to hang their coat up and steadied themselves using that neutral cable LOL.... very dangerous as it could have been the live.
@5tevia
@5tevia 5 лет назад
Main isolation or DNO cut out could be located in another room. There is no regulation to say it needs to be by the meter.
@JwiseTheRealist
@JwiseTheRealist 5 лет назад
@@5tevia exactly
@michor10
@michor10 5 лет назад
I am binge watching all of your videos, sir. Great stuff!
@I_Damoooo
@I_Damoooo 6 лет назад
Good trick when removing sockets and switches is to run a Stanley blade around the edges to help stop damage to the paint and leaves a clean job when refitting , great content by the way
@saabuldin
@saabuldin 5 лет назад
I usually score it using a flat 4mm screwdriver.
@bitTorrenter
@bitTorrenter 4 года назад
@@saabuldin Doesn't do it as cleanly.
@lexprimo
@lexprimo 5 лет назад
You're a credit to your profession mate. Thanks for doing these videos.
@Slushplop
@Slushplop 5 лет назад
what does he say 6:47 that's the connection for your oven, that's your connection for your.... ob?
@MMKLYH
@MMKLYH 4 года назад
Hob, the 4 rings on top for cooking pans on
@anelectrician
@anelectrician 5 лет назад
Wow ! What a foolish place to site a fuseboard near the hot water cylinder. Also whenever I find a loose terminals in a fuseboard I find it a good practice to tighten all the terminals in that fuseboard.
@davidprivate5786
@davidprivate5786 5 лет назад
Agreed needs putting into the regs and clarifying in the building control notes. 1350 height isn't good enough...that said it's 150mm really so that's not compliant part p
@DerekHundik
@DerekHundik 5 лет назад
Foolish . its comletly out of whack. What an idiot agrred on this location ?
@DerekHundik
@DerekHundik 3 года назад
What i noticed recently that after changing CU to RCDs or RCBOs most of those old solid plate hobs failed.
@NoRetreatNoSurrender86
@NoRetreatNoSurrender86 6 лет назад
That's what happens when your out the door to early end up going back always hang about 😂 for a bit And as for those shit dual RCD boards fucking nightmare. Indidvual For each circuit is the way forward
@balladmad97
@balladmad97 3 года назад
Hi. Enjoying your videos. Just wondering why you didn't check the terminal on the actual hob.
@ef7480
@ef7480 Год назад
Great vids - even 4 years late!👍
@fishingnoddy7299
@fishingnoddy7299 6 лет назад
When I get things like your second job, I can't help but think it's a set up.....rarely do you not get sooting or burning. Nicely sorted though.
@eastwayelectrical
@eastwayelectrical 6 лет назад
Cheers Gary, oh mate there no shortage of surprises in this feild
@zXLuke4efcXz
@zXLuke4efcXz 3 года назад
I was expecting Matt Allwright from Rogue Traders to pop out!
@mansuralam2055
@mansuralam2055 4 года назад
Hello, I am indian Can u change your all video's in hindi translation. Its nice video's Awesome ur all video's
@arniewheeler4673
@arniewheeler4673 3 года назад
nice position for a consumer unit... was it there before the cylinder... hmmm
@DanielCastillo-cn3pp
@DanielCastillo-cn3pp 3 года назад
Its funny how panels are installed in cramped up locations. Here in the USA code says to allow three to five feet of open space in front of electric panels.
@kangtheconqueror
@kangtheconqueror 6 лет назад
Hey, hey Delroy! Just spotted your piccy in the June edition of Professional Electrician and Installer magazine. (Page 10-11) Fame at last, eh? Can I have your autograph? 😃😂 Ah... and a feature on Page 52.
@millsygolf1016
@millsygolf1016 6 лет назад
Come on del, sleeve the socket CPC at the end. Regulation 543.3.2
@eastwayelectrical
@eastwayelectrical 6 лет назад
Thanks for the suggestion, hope you enjoyed the video
@nitukumari-nh6ds
@nitukumari-nh6ds 5 лет назад
One of my neighbour has bypassed my main and inverter connection. I don't understand how is it possible when I have a new wiring and there is no touch with their wires then how come it is possible. Pls help me to find the fault.....
@defensegeneral9893
@defensegeneral9893 6 лет назад
It’s illegal in the US to block electrical control panel, like this house
@AGRElectrics
@AGRElectrics 6 лет назад
Probably an element in hob del. Pull back of hob off check each element the find part on espares.com next day delivery jobs a good one
@jonanders76
@jonanders76 6 лет назад
Lose the neutral and usually lose all the electronic stuff in the house. Neutral pulled out due to smart meter install and meter installer pulling on tails and not checking the main switch in the consumer unit after install. Common problem always check after meter fitters have been in the house. Enjoying your videos Delroy.
@malcolmcroll7556
@malcolmcroll7556 6 лет назад
if you use a surface mounting box -how do you deal with the knock-out hole because you cannot put in a grommet or stuffing gland -
@getduppiedrs9364
@getduppiedrs9364 6 лет назад
Del at 24:16 where’s the earth sleeving?
@anelectrician
@anelectrician 5 лет назад
Shush !
@DerekHundik
@DerekHundik 5 лет назад
Bare wire no earth sleeving and talking about the arc
@furrier69
@furrier69 5 лет назад
At 19.30 - Yeah suppose it's a good idea to disconnect the load side while wiggling around the tails... Good job the phase wasn't loose!!! Ha ha ha, nice one though Del
@johnkay7025
@johnkay7025 3 года назад
More likely some elements insulation broken down in hob or oven delroy
@johnschlesinger2009
@johnschlesinger2009 5 лет назад
That last c.u. with the loose neutral showed something I haven’t seen, and which is not good: the feed to the meter was going through the c.u. - weird.
@richmondoppong5585
@richmondoppong5585 4 года назад
Please what is the name of the machine on your neck using to the test the cables?
@danielfrazer7556
@danielfrazer7556 5 лет назад
I enjoy watching you troubleshoot. I too am an electrician with about 25 years experience in the US and it is interesting to see how different the electrical systems are in Europe compared to the systems we use here in the States. Great work and thanks for sharing!
@fieldsofomagh
@fieldsofomagh 5 лет назад
Good process of elimination. Customer happy!!
@jonathandugan7418
@jonathandugan7418 6 лет назад
There's nothing worse than a tight consumer unit
@eastwayelectrical
@eastwayelectrical 6 лет назад
Tell me about it, why on earth are the put in the most awkward places?
@desdiamond5700
@desdiamond5700 6 лет назад
Jonathan Dugan Mmmmm I would say WAR . FAMINE. DROUGHT. OPPRESSION AND IMPERIALISM is a shade worse!!
@kangtheconqueror
@kangtheconqueror 6 лет назад
Oh... I don't know Des. 🤔
@desdiamond5700
@desdiamond5700 6 лет назад
Kevin McNicholas 😂😂I take it he wasn't at Vietnam either!!
@kangtheconqueror
@kangtheconqueror 6 лет назад
Des Diamond And what about soggy biscuits?
@johngrannan
@johngrannan 5 лет назад
Sorry Delroy. I don’t understand your fault finding logic on the first job. It’s a cooker radial circuit with only two appliances on it, they are much more likely to fail than the MCB, wiring or switch. Disconnect the hob and cooker then IR test from there back to the CU, proves the switch and wiring - wouldn’t have shown a fault, hence it must be an appliance, re-connect cooker which would have been fine, same with hob, fault repeats. So it’s the hob, disconnect at the backplate so that a new hob can simply be wired in. Not being funny but am I missing something?
@TheDeathBonus
@TheDeathBonus 5 лет назад
Wouldnt the neon on the cooker switch affect the IR values?
@andywoods3467
@andywoods3467 6 лет назад
Would you not have sleeved that socket earth del, when you were at it?
@eastwayelectrical
@eastwayelectrical 6 лет назад
Thanks for the suggestion, I hope you are enjoying the content
@andywoods3467
@andywoods3467 6 лет назад
Delroy The Spark Always interested to see how other electricians work. keep it up 👌
@stevencorbin103
@stevencorbin103 6 лет назад
Nice work del.
@eastwayelectrical
@eastwayelectrical 6 лет назад
Cheers Steven
@linksone6287
@linksone6287 5 лет назад
Fantastic video gents. Well presented. However, can I just ask a question on 2391 inspection and testing. I’m about to sit my 2391 in a months time and wanted to install a rig testing board before the exam but not sure how many circuits i should include to make sure I’m well prepared for the exam. If you can possibly help me with a spec I would much appreciate your help!
@mzswaggalady
@mzswaggalady 5 лет назад
set up a ring. A good tip is to write out a manual of how to test. where to put the probs, what settings, expected readings for each test.
@markrainford1219
@markrainford1219 6 лет назад
Meter installer's fault, no question.
@5tevia
@5tevia 5 лет назад
Meter installer should have cleated tails before working on the meter, however I would say dodgy electrician was to blame, as looks like the neutral was never connected properly. Could definitely of caused afire that one.
@keithjackman1
@keithjackman1 6 лет назад
Great vid , keep them coming , What tool bag do you use , thanks.
@crigeorge9549
@crigeorge9549 6 лет назад
you didn't repair the cooker? Why? You should've looked at the switches, connections and the elements. It's not that much "electronics" stuff really.
@dennell
@dennell 5 лет назад
He's an electrician mate... not an appliance service engineer. If he messed with the cooker he could have voided a warranty or an insurance claim. He's not paid for that and if he was he could find a bill waiting for him instead of getting paid.
@carguillo1
@carguillo1 6 лет назад
Nice one del im still waiting to come and work with you all the best mate /kev
@eastwayelectrical
@eastwayelectrical 6 лет назад
Haha thanks Kev, all the best mate
@fasalmahmood71
@fasalmahmood71 5 лет назад
Hi, just a question, before doing the insulation resistance test wouldn't everything on the circuit be removed prior to testing? Thanks
@saabuldin
@saabuldin 5 лет назад
Usually the hob is on its own dedicated circuit. So there is nothing else to disconnect other than the hob.
@zippymo672
@zippymo672 5 лет назад
Its not easy when the fuse board is fitted into a cul de sac.
@JaydenLawson
@JaydenLawson 5 лет назад
When Luther is your electrician
@no_short_circuit
@no_short_circuit 6 лет назад
Thanks for the videos. I don't understand why when you did the phase to E IR test and you got 0.00 ohms that that indicated a fault. Can you explain that to me please?
@stevendoimo1674
@stevendoimo1674 5 лет назад
Means there is a short in the cable between phase to earth I.e no resistance between cables which indicates cables touching.
@ikeabuchi1
@ikeabuchi1 4 года назад
2nd job arching switch
@lessmith3718
@lessmith3718 3 года назад
Disconnect the hob.best thing😉
@ОляП-д4х
@ОляП-д4х 5 лет назад
This Electrik ! Super! Like this video.
@executechelectric
@executechelectric 5 лет назад
18:46 "if it was the live" there wouldn't be any power downstream..
@michaelboyes4948
@michaelboyes4948 6 лет назад
Where did you get them slim milwaukee screwdrivers i can only find the big ones
@andybell6641
@andybell6641 6 лет назад
think they are the bahco insulated drivers
@michaelboyes4948
@michaelboyes4948 6 лет назад
Andy Bell cheers i thought they were the slim milwaukee ones,one of the electricians i work with have them but his son bought them so don't know where to get them rather get the milwaukee ones than bahco tho
@tommul100
@tommul100 6 лет назад
It's a Wiha I think
@ek6868
@ek6868 6 лет назад
Excellent video plz keep uploading fault finding videos they are very informative for a newbie like me tanx.
@eastwayelectrical
@eastwayelectrical 6 лет назад
We might have another one that could be right up your street 😉
@aminkhan1292
@aminkhan1292 4 года назад
Delroy, my downstairs lights 2 lights work, and the other half doesnt, i noticed the mcb tripped, and flipped it back on, but half the lights downstairs are have no power, ive tested each switch with my tester and no voltage, do you thing there is a inline fuse thats blown?
@ImranKhan-cf8gs
@ImranKhan-cf8gs 4 года назад
Amin Khan could be a open circuit or broken neutral
@aminkhan1292
@aminkhan1292 4 года назад
@@ImranKhan-cf8gs i found out what the issue was, one of the live cables burnt out, i had to break into the walls to cut it out and extend it and all is working
@abooli2
@abooli2 5 лет назад
Nic job brother
@mij.londoner
@mij.londoner 6 лет назад
YES YES DEL Romford road The Pigeons Pub
@eastwayelectrical
@eastwayelectrical 6 лет назад
haha you have sharp eyes!
@waynegarbett958
@waynegarbett958 6 лет назад
Great video mate. Be interested to see more fault finding.
@nialloshea6630
@nialloshea6630 6 лет назад
Very good videos
@stanleykania7184
@stanleykania7184 5 лет назад
Working space law ??
@abooli2
@abooli2 5 лет назад
New subscriber here.
@leonardmilazi8288
@leonardmilazi8288 6 лет назад
How did you identified the actual neutral wire for the faulty circuit from a couple and bunch of wires on the neutral bar within the distribution board ?
@theinstallerguy786
@theinstallerguy786 6 лет назад
Leonard Milazi the cables should be connected to the numbered slots as per circuit number.
@leonardmilazi8288
@leonardmilazi8288 6 лет назад
thank you
@phillwildman
@phillwildman 6 лет назад
Excellent video Delroy.
@sparksparky9592
@sparksparky9592 6 лет назад
Excellent video please keep posting fault finding videos
@eastwayelectrical
@eastwayelectrical 6 лет назад
Thanks for the comment. As long as we keep getting fault finding jobs we'll keep posting them.
@ek6868
@ek6868 6 лет назад
👍👍👍
@eastwayelectrical
@eastwayelectrical 6 лет назад
Emojis say more than words in my opinion
@asef698
@asef698 6 лет назад
One of the Best spark channels on RU-vid. Informative stuff no sponsor reviewing crap just real work situations. Keep em coming del
@eastwayelectrical
@eastwayelectrical 6 лет назад
Cheers Ashley, very kind words indeed. Lots more to come.
@simonabbott7323
@simonabbott7323 6 лет назад
What's that geezer doing at 9:56??
@Elvis_TheKing
@Elvis_TheKing 4 года назад
Probably the latest youth dance! 🤣
@johndufton9686
@johndufton9686 5 лет назад
Another smart meter installation leaving a property dangerous. PEOPLE SAY NO TO SMART METERS.
@fishingnoddy7299
@fishingnoddy7299 6 лет назад
Why struggle testing in the tight space, test at the switch?
@eastwayelectrical
@eastwayelectrical 6 лет назад
Thanks for the suggestion, hope you enjoyed the video
@dav01kar
@dav01kar 4 года назад
I test both ends when IR testing, just something I have done (HABBIT)
@ek6868
@ek6868 6 лет назад
Definitely 😃
@Rosscoff2000
@Rosscoff2000 5 лет назад
You should definitely have isolated the load before working on that - apart from sparks as you put it back, bear in mind that the load side neutral would actually have been live while the neutral supply was disconnected.
@taianwar89
@taianwar89 5 лет назад
Great job Delroy but a few pointers mate, the second consumer Unit one has a multitude of issues/ No labeling, no RCD protection, old fusewire MCB's, meter tails need upgrading to 22mm, should have a 100a isolator between the meter leading to the DB and that's just what I can tell from looking at the DB who knows what the circuits are like in the rest of the property. I would have told the customer that the immediate fault has been resolved but she seriously needs to consider taking care of these other things here and would have given here a recommendation with an estimate to have this work done. Also, why not offer to replace the old double socket frontal while you were there? could have billed a bit more and have resolved another issue.
@alexhart4763
@alexhart4763 6 лет назад
I'm not an electrician and not involved in the trade at all but find your vlogs really interesting, keep up the good work!
@kevincuthbert3058
@kevincuthbert3058 6 лет назад
Nice job man, your a good sparky.
@eastwayelectrical
@eastwayelectrical 6 лет назад
Cheers Kevin,I appreciate the kind words
@tomala57
@tomala57 6 лет назад
It must suck to work on a consumer unit located in such location. Is there any requirement that dictates location of a consumer unit? US and Canada has a requirement for a working space in front of consumer unit/electrical panel that has to be free of any obstruction. I believe it is 3 feet of available space from unit cover. Other than that, good job guys.