Accumulator Facts & Tips 

HVAC School
Подписаться 344 тыс.
Просмотров 118 тыс.
50% 1

Bryan teaches a class about accumulator facts and tips. He explains what they accumulate inside an HVAC system, covers some common problems, and gives some tips on how to use them.
Accumulators are designed to accumulate liquid refrigerant before that liquid can reach the compressor. Liquid should never get inside the compressor. When liquid floods the compressor, it washes out the oil. Many compressors are also refrigerant-cooled, and that refrigerant has to be a cool vapor, not a liquid.
Accumulators are more common in Carrier heat pumps because those systems have fixed-orifice pistons that don't control the superheat. Therefore, the accumulator is an additional safety measure when there is no control over the superheat in a wide operating envelope; it interrupts the liquid before it can affect the compressor. Although the accumulator can become liquid-locked and feed back, it's unlikely. Accumulators also prevent slugging. However, modern compressors are unlikely to slug due to their refrigerant-cooled nature. Slugging happens when liquid gets into the compression chamber.
Overall, getting liquid into the compressor in any capacity is undesirable because it starts foaming the oil and ejecting it from the compressor. The oil lubricates the compressor bearings, which keeps the compressor working for its entire lifespan; premature failure may happen if there is too much mechanical wear without the oil. When oil is ejected from the compressor, it also goes to the rest of the system and can get stuck in the evaporator coil when it gets more viscous.
The accumulator has a U-shaped tube with a small pickup hole at the bottom, which picks up oil. (Oil is heavier than liquid refrigerant and will sink to the bottom of an accumulator.) If that bottom port gets blocked, oil won't be able to get through and will get stuck in the accumulator, so it can't lubricate the compressor. Copper shavings, dirt, and carbon flakes may block that port. There is also a port near the top that stops the accumulator from becoming liquid-locked.
In some cases, oil also may not return to the compressor due to long line sets. Long lines require the HVAC/R technician to add more refrigerant, and special considerations need to be taken to make sure that liquid refrigerant doesn't migrate (or vapor refrigerant doesn't condense to a liquid in the compressor). These strategies include liquid line solenoid valves, hard shutoff TXVs, and crankcase heaters.
When we replace a compressor, we want to pay attention to the accumulator. Replacing the accumulator is perhaps the best practice, especially in a burnout situation, but the old accumulator can be reused if it's flushed and completely cleaned out. It's a good idea to dump out the accumulator and analyze the oil; a lot of contaminated oil indicates a lot of oil loss and could be a burnout. The accumulator is a good place to test the oil, too.
Charging a system with an accumulator is different from charging a system without an accumulator. Liquid charging could result in refrigerant going into the accumulator and getting cold, which makes it hold liquid refrigerant and indicate undercharge because the subcooling won't go up (even though the system could be overcharged). So, using a charging scale and giving the system plenty of time to equalize will help prevent that from happening. With labor, refrigerant, and callbacks being as expensive as they are, the small details matter.
It's also worth noting that motors and electrical parts often fail due to mechanical conditions, not electrical ones. So, burnout isn't always caused by lightning strikes, start capacitors that aren't taken out of the circuit, or over-voltage conditions.
Read all the tech tips, take the quizzes, and find our handy calculators at www.hvacrschool.com/.

Опубликовано:

 

22 июн 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 113   
@Captain_Kdawg
@Captain_Kdawg Год назад
Good video. I knew the basic understand of the accumulator. But I can say I learned about the holes in the pick up tube today !!
@nu-nu-ramen3326
@nu-nu-ramen3326 3 месяца назад
😂😂😂e😮😅
@jasonjohnsonHVAC
@jasonjohnsonHVAC Год назад
Tech tip....accumulators can and do leak....usually from the bottom. Don't forget to check them on a leak search
@trevorjones559
@trevorjones559 Год назад
Yes. They have condensation nearly 100% of runtime, so if the paint is chipped on older equipment, chances are you're gonna find leaks. I've found them on the top also.
@seandowns8828
@seandowns8828 Год назад
Changed 2 out last week bottom leaks
@fre0nx675
@fre0nx675 Год назад
Almost always. Especially in heatpumps when they get full of dead leaves or muddy sand that holds water.
@OcRefrigeration
@OcRefrigeration Год назад
1) They leak up at where the factory connections are at copper to steel joint also. ( top of accumulator ) 2) also at Overtemperature Relief Plug in top area on Heatcraft units. ( see one of my videos if you don’t believe) 3) also at welds - top & bottom. Rust out. 4) bottom stud - as everyone is mentioning. 5) Factory paperwork says good life is 5-8 years on accumulator. After that all bets are off. 6) After welding in - I have started wire brushing & painting any burnt areas at top connections. Especially on marine applications.
@condor5635
@condor5635 Год назад
@@OcRefrigeration thanks for the wire brush paint it tip. My top area is rusty and needs that. It’s like 20 yrs old surprised it has not leaked already. I keep bottom of condenser clean of junk so that helps I guess. Thanks!
@davidryder3374
@davidryder3374 Год назад
As an HVAC instructor, I appreciated your pain when you asked a simple question and nobody answered.
@Boraxo
@Boraxo Год назад
Or an answer they just pulled from their behind.
@632Harrison
@632Harrison Год назад
I give you two thumbs up my friend I have been a HVAC / Refrigeration technician for over 42 years
@lynncomstock1255
@lynncomstock1255 7 дней назад
Good job. One correction at 11:06 Liquid will end up in the compressor oil regardless of temperature difference because oil has a very low vapor pressure, and the refrigerant vapor migrates into the compressor oil to increase the vapor pressure of the mixture. (Think of the low vapor pressure of the oil as like a very slight vacuum. It takes quite a while for this to happen. Manufacturers asked that the CC heaters be activated before startup because the bulk of the refrigerant shipped in the equipment will always be in the compressor oil. This is also a reason why compressors have twice the minimum operating oil ensure that they have enough oil under widely varying conditions.)
@enochian7133
@enochian7133 Год назад
Mr Brian,thank you for these videos .For some of us studying online these videos are sooooo valuable! Your students are lucky to have you as an instructor.
@jpstryker23
@jpstryker23 6 месяцев назад
just started this trade, thank you sir for putting this together in a concise explanation, im going to a school via our union in florida and these classes are helping fill some gaps where i dont fully understand at school. i love the animation, just seeing it helps tremendously.
@benkuxhouse787
@benkuxhouse787 Год назад
Nice video I’m a technician of 37 years and learned a few things. About the oil test I did a compressor replacement in freezer the compressor was $5000.00 alone Wholesale. Needless to say I came by a few times to do inspection of oil site glass and a few oil acid tests. as he said in this video which is correct commercial compressors can be very expensive
@adamcox1809
@adamcox1809 Год назад
I'm considering entering the trade and the amount of information I've learned from this channel for free is incredible. Thank you so much!
@TheBanaxel
@TheBanaxel Год назад
You sir are a honest contractor. Thank you.
@mathman0101
@mathman0101 Год назад
Love the chit chat with the techs you have now that’s an employer who teaches and strengthens their employee training kudos to you all and for sharing that knowledge.
@nathanhurst5155
@nathanhurst5155 Год назад
Thank you so much for these work meeting videos and all the others you do. They are all awesome 👏
@sparkyobrian6417
@sparkyobrian6417 Год назад
love these videos, hvac terms are so different than my field, very interesting !!!
@samutokakece731
@samutokakece731 Год назад
thank you for awesome and informative knowledge
@LheodaTechTv
@LheodaTechTv Год назад
Watching and sending support thanks for sharing
@gorrillaback11109
@gorrillaback11109 Год назад
This video came at a right time. I wanted more knowledge on accumulators and this video was recommended on the algorithm.
@VOTEREPUBLICANS594
@VOTEREPUBLICANS594 Год назад
Now i have understanding of the accumulater , thank you !
@larryproffitt4729
@larryproffitt4729 Год назад
Thank you for putting together this informative video.
@Bangkok-ik1fp
@Bangkok-ik1fp 10 месяцев назад
Such invaluable information presented so well. Thank you!
@Stuart68505
@Stuart68505 Год назад
Lots of helpful ideas. Thanks.
@POlin-qs1um
@POlin-qs1um Год назад
Great stuff. Coastal Nc area,Blackbeard Country. RustyTanks and Driers blow first,then Coils. A.c.r 30 Yrs. Sometimes I'll wrap a new Tank with black cork tar tape. It will never rust out. Ocean Salt galore. Life is a Beach! Great vids!
@mohammadalshaikhhasan5091
@mohammadalshaikhhasan5091 Год назад
Thanks Brian, a good topic to attention. Replacing the accumulator requirs attention about the size. If you describe little about what could happen when installing a bigger size accumulator in the system.? Thanks again
@dalvindersinghmanku8243
@dalvindersinghmanku8243 Год назад
Good information regarding accumulator....i heard this types of leakage in bottom of accumulator.
@Stuart68505
@Stuart68505 11 месяцев назад
Thanks lots of helpful ideas
@Cpt_bike_riders
@Cpt_bike_riders 7 месяцев назад
Struggling with a iced up accumulator. What can the problem be? This helps alot on clearing things about accumulators
@randyfalkosky8579
@randyfalkosky8579 Год назад
very well done!!
@MichaelSmith-pg6gi
@MichaelSmith-pg6gi Год назад
Excellent!
@etherealrose2139
@etherealrose2139 Год назад
Solid video.
@rafaarroyo5438
@rafaarroyo5438 Год назад
Thanks!!
@carldurham5879
@carldurham5879 Год назад
Accumulator sizing on variable speed compressor systems are critical and the same pipe sized accumulator must go in place if it is initially installed
@MrGarcon98
@MrGarcon98 Год назад
well done thank you
@duanecarroll4375
@duanecarroll4375 Год назад
I wish I could post a picture of 2 accumulators in an industrial setting. I had one that was for the cooler, and one for latent heat of fusion feeding a turbo ice maker. Had gravity fed vacuum tubes also. Some knarley rotary screw compressors let me tell you
@rachida3904
@rachida3904 Год назад
Good 👍
@vnesmuonnam
@vnesmuonnam Месяц назад
Thank you
@Pennconst101
@Pennconst101 Год назад
I would love feedback on this: probably five or six times in the last 15 years I’ve gone back on heat pumps and found them drastically overcharged however the overcharge is not immediately apparent. I’ve checked systems letting them run 30+ minutes only to go back a week later and find them off on high pressure And then proceed to recover sometimes more than 3 pounds. These are systems that are more than five years old and the question becomes how in the heck have they been running the whole time?! The only commonality is that they are all heat pumps so I presumed the accumulator has been acting as a receiver.
@Brokefootchuck
@Brokefootchuck Год назад
Did you remove all the refrigerant and weigh it back in? Or did you go by the manufacturers literature (pressure curves, subcool charts etc)?
@morisuesue5019
@morisuesue5019 Год назад
Should you replace the reversing valve when replacing the Compressor.
@mushtaqahmad7897
@mushtaqahmad7897 10 месяцев назад
Nice video
@davidpanyj
@davidpanyj Год назад
Amazing 😊
@JeremyChan
@JeremyChan Год назад
thanks for the great info!
@ELECTRICMOTOCROSSMACHINE
@ELECTRICMOTOCROSSMACHINE Год назад
Very cool.
@scott5654
@scott5654 Год назад
👍🏻👍🏻 Thanks, Excellent as usual ‼️ I never knew oil could be bad and yet not look bad, as in black, or smell bad, as in burnt. I learned something new.
@daveeckmann9568
@daveeckmann9568 Год назад
I took a compressor class by Copeland one time and they said the oil in a compressor should look new the same as it went in..."this is not an internal combustion engine...there is nothing inside the system to make it dirty" if its black it has been overheated/burnt.
@brianlittle717
@brianlittle717 Год назад
Great video. I learned a couple things. Should super Heat be measured on the suction line entering the accumulator, or should it be measured as it enters the compressor? And that’s a good point about crankcase heaters. Is there a reason the CCH is more common on a recip than it is a scroll?
@michaelwhitaker7764
@michaelwhitaker7764 Год назад
Reciprocating compressors have crankcase heaters more often because slugging can bend the valves in the compressor
@brianlittle717
@brianlittle717 Год назад
@@michaelwhitaker7764 I guess that makes sense. So you’re saying it’s harder to damage the scroll from cold oil?
@lynncomstock1255
@lynncomstock1255 7 дней назад
@@brianlittle717 Not cold oil. Liquid refrigerant slugging. Scrolls are designed so that the compression chamber between the scrolls opens up (enlarges) whenever non-condensable liquid refrigerant or oil completely fills the compression chamber.
@brianlittle717
@brianlittle717 7 дней назад
Is that the same thing as when it bypasses at 625psi? And how does the chamber get full of liquid? I know some liquid will go through it if it’s frozen up or when you’re charging it but that’s not a full chamber is it? It should be able to handle that. And if there’s a suction trap and it fills with oil then it might get a big gulp from that once in a while. But how does the crankcase heater prevent a full chamber of liquid if it’s not the oil we are worried about?
@mitbbs
@mitbbs Год назад
Is it normal to have a sweating accumulator in a hot humid day? I found a pond of condensation water under the outdoor unit. Thanks!
@emptech
@emptech Год назад
It's nice if we know the refrigerant capacity of a system, but we don't always. We tend to look at superheat on a cap system and subcool on a TXV system, but the manufacturer doesn't always give those numbers, so we use ball park numbers. I learned from others that while the system is running properly, the accumulator should be filled to about 2/3's of it's capacity. Like others, I've flashed it with a torch and then used a thermal camera to look at the liquid level, some will put their hands on the side and feel the liquid line. You didn't mention any of this, is it a wives tale? I'm rebuilding a wine celler control system, will have to charge it by the gage readings, but it does have an accumulator. A method I used one time, measured the volume of the accumulator, then calculated 2/3, got that number, then found the density of the refrigerant, and once charged by the numbers, then added enough refrigerant to fill the accumulator to 2/3, did I over-do it? Always appreciate the videos - Jim
@ooklathemok7322
@ooklathemok7322 Год назад
You do not charge a Refrigeration circuit by filling the accumulator. I believe you might be thinking of a receiver. These are 2 different components that do 2 different jobs. By design a well balanced system with an accumulator will not have any refrigerant in it. When a TXV is used it's job is to control superheat. A fixed orifice if charged correctly will rarely bring saturated refrigerant to the accumulator. But due to system operating parameters a heat pump or low temp refrigeration system could have saturated refrigerant returning to the accumulator. Mainly because of frost or ice on the evaporator. It is common to fill a receiver to 80-90% capacitor for condenser flooding, when teamed up with a head pressure control valve aka headmaster. Receivers are common on Refrigeration units. I hope this helps
@Nab-Asn2803
@Nab-Asn2803 Год назад
Thank you for domistraion, can I install acumelater in havc 6 ton that has recipating compressor inoder to protect my compressor in long run life of compressor
@condor5635
@condor5635 Год назад
This explains accumulator well. I had asked the question about what that cylinder was next to the compressor. Now I know. Mine is also a Carrier which I think you mention uses them a lot. The top junction looks like rusty and corrosion. I think I will wire brush and paint it. Thanks for the great video
@alaminmiah5291
@alaminmiah5291 Год назад
Good Sir
@wacoodude6567
@wacoodude6567 4 месяца назад
Does the accumulator always need to be have liquid refrigerant to return oil to the compressor? FYI when running in Heat Pump at really low temps, the density of liquid refrigerant can be more than the oil (depending on refrigerant and oil combination) causing oil return issues.
@gyrgrls
@gyrgrls Год назад
I've always chased my aspirations, but I never really accumulated much.
@Elisummit845
@Elisummit845 Год назад
🤣🤣🤣🤣 are you friends with TY Branaman? Lol
@michaelproust7891
@michaelproust7891 Год назад
Could you explain why a system fault could be exacerbated by the client running the interior ambient higher.
@WickedIllusion1
@WickedIllusion1 Год назад
Can someone expand on the 'hard start kit' part... If I have a presently well working system should I not add one? I was led to believe recently that even on a properly functioning system ( mine is a 9 year old Rheem, in SE Michigan) that a hard start kit is an "upgrade" and would likely extend the life of the compressor....
@hvacmisadventures
@hvacmisadventures Год назад
Yeah you can add one. It would be best if they all just came stock with them but that would be expensive and people don't wanna pay for that
@MdArshad-nn2do
@MdArshad-nn2do Год назад
😊 Nice 😊 video 😊 sir 😊
@John..556
@John..556 Год назад
I had a Rheem heat pump Freon leak and bad compressor. Figured leak was in indoor coil.. customer decided better solution to replace compressor. So I did, 1 month later I discover the new comp is dead. So i warranty it out. But I notice there’s 0 oil in the compressor. I thought wow no wonder it roasted. Then I put the other new one in pressure test is ok. But I know it’s leaking so I ignore it. Pull my vac and I’m seeing tons of vapor exhausting. So I start looking at my joints. All good. Then I lean on the accumulator and hear the hiss of death. That accumulator had cracked on the bottom and the oil and rust would semi seal it and it had leaked all the oil out underneath it but you couldn’t tell because it ran under the condensing unit… rheem is not my fav system lol. And I cut the accumulator out and straight pipes it works perfect now lol
@ryanmullins715
@ryanmullins715 Год назад
Just changed a compressor tonight,only to find a bad accumulator,I changed drier,contactor,dual cap,braised with nitrogen,had a feeling accumulator was bad knew I should have replaced it to,now have to recover and either flush or replace accumulator,thought it was mechanical but nope
@loveyoutoo7081
@loveyoutoo7081 Год назад
شكرا
@markbowker5936
@markbowker5936 6 месяцев назад
GREAT INFO! THANK YOU
@arealmaintenanceandrepairl1103
@arealmaintenanceandrepairl1103 10 месяцев назад
Do ac only have accumulators I had one with some sort of cartridges on the liquid line not filter dryer
@sjsz06
@sjsz06 Год назад
Are there any videos that don't act like a school asking questions as though you have already been given the info, but just relay the information? I like the info, but am way past going to school (I'm 74).
@wigginsryan0
@wigginsryan0 6 месяцев назад
I'm in Orlando. How can I find this course and take this course in person?
@pb5640
@pb5640 Год назад
Knowledgable guy but this is known in education circles as a talking head. I’m glad you added the pictures and illustrations which helps undo the boring talking head. I don’t think the students in the classroom had this advantage.
@jessehanecak2241
@jessehanecak2241 Год назад
I am not an experienced technician and I am far from what I see as an expert but I understand that electrical issues are almost never lightning strikes. I guess my question is, is this really a common thing? I wouldn't have expected it to be.
@lynncomstock1255
@lynncomstock1255 7 дней назад
Many years ago, compressor manufacturers claimed that a majority of compressors returned under warranty were not failed. I expect the same is true today because of incompetent technicians.
@UQRXD
@UQRXD Год назад
I am one to install a suction and liquid line filters. I heads off a lot of problems.
@Elisummit845
@Elisummit845 Год назад
They say not to install a suction dryer only after a burnout.
@Barracuda48082
@Barracuda48082 Год назад
Q. How to size an accumulator on a system that should have had one..?
@Mapdotgolf
@Mapdotgolf Год назад
So if we don’t want refrigerant in systems, does that mean pumping down a system is bad for it?
@indiantraveller194
@indiantraveller194 Год назад
Good
@AaronPowellvox
@AaronPowellvox 11 месяцев назад
Watching these videos with peanuts in the background and waiting for them to give you the right answer is sooooooo grueling. It’s why I never liked school. Just get to the point! Sheesh. I love the information and am grateful but I wish these videos were edited.
@zerwell47
@zerwell47 Год назад
The last I looked, refrigerant is heavier than oil...therefore oil floats on it. (7:33) not as stated. But, good video anyway.
@dhronpatel9158
@dhronpatel9158 4 месяца назад
Same thought here
@Mapdotgolf
@Mapdotgolf Год назад
So if we don’t want refriger
@Ihscout1069
@Ihscout1069 Год назад
Wish Lennox would use an accumulator and get rid of the outdoor txv
@nehorayneemani1039
@nehorayneemani1039 Год назад
Why did you mention accumulator with heat exchanger???
@irham9856
@irham9856 Год назад
👍👍👍
@cacangfishing9905
@cacangfishing9905 Год назад
Accumulator prak tips
@fre0nx675
@fre0nx675 Год назад
Someone told me those old TRANE orange compressors (Easter egg) had internal accumulators
@Zerofukstogive
@Zerofukstogive Год назад
The funny thing about skilled trades is that you can master one and be really good at it but you can't balance both. I've met plenty of people in my day that claim to do both but they are never masters of both. They chose one or the other but they will always say they know both. Stick with one trade and master it. I can pick up on a person that "pretends" to know it all. It's bullshit. I'm a card carrying plumber in ohio and I don't pretend to know hvac. I worked in hvac for a year and a half and I still don't pretend to know how to service hvac. It takes over 5 years to become a good tech in either trade. Stick to one and master one. It's easy to pretend to know both if you know how to talk but in reality you are just doing both and hoping those certified employees don't ever mess up.
@tomconner5067
@tomconner5067 Год назад
Liquids can't be compressed
@The-LongRoad-Home
@The-LongRoad-Home Год назад
I've never had a compressor and probably done hundreds I have come with a new wiring harness🧐
@hvaciqguy2655
@hvaciqguy2655 Год назад
BECAUSE A COMPRESSOR CANT COMPRESS LIQUID!!! Can’t someone just say that??? For F@CK sake… I would have to avoid these little get togethers… and YES WE DO talk JUST LIKE THAT in THIS-HOUSE…🤣😂 poor Brian…
@hvaciqguy2655
@hvaciqguy2655 Год назад
Then one day I’d be walking past, hearing Brian’s explanation n think to myself, wait, I didn’t know that…
@Mr.body1917
@Mr.body1917 9 месяцев назад
😂😂
@charlesfleming742
@charlesfleming742 Год назад
⁰p
@tomlewis632
@tomlewis632 Год назад
I always hated those damn steel accumulators that would rust out and leak. Especially Carrier and their shit brands.
@condor5635
@condor5635 Год назад
My carrier is over 20 yrs old. I am happy with it overall. Changed contactor and cap myself and also installed 5-2-1 recently. Copeland scroll compressor. Happy overall
@tomlewis632
@tomlewis632 Год назад
@@condor5635 Its funny because all of my training is from Carrier. In Florida, the A/C gets used for 10 to 12 months out of the year. Over the years for me, the average seemed like 7-10 years Max. Back in the day, before they got bought out by Trane, I saw General Electric ⚡️ units over 25 years old still running.
@condor5635
@condor5635 Год назад
@@tomlewis632 - I guess I’m extremely lucky then
@fwily2580
@fwily2580 Год назад
Asking questions as a method of teaching is not teaching. It’s just a bad conversation.Right?
@HVACS
@HVACS Год назад
Ask Socrates
Далее
Nitrogen Facts and Tips
15:54
Просмотров 58 тыс.
Locked Compressors
20:13
Просмотров 100 тыс.
МОЩЩЩНОСТЬ ZEEKR 001 FR
00:46
Просмотров 829 тыс.
МАЛОЙ ШАНТАЖИСТ
00:34
Просмотров 94 тыс.
HVAC  069 suction line accumulator
12:34
Просмотров 20 тыс.
Stop Sweaty Ducts, Vents and Systems
23:26
Просмотров 223 тыс.
Heat pump 04 Accumulator & Muffler
7:25
Просмотров 18 тыс.
Capacitor and Hard Start Myths Busted
28:41
Просмотров 204 тыс.
Class - What Superheat Signifies
17:07
Просмотров 220 тыс.
Diagnosing a Locked Compressor 3D
10:02
Просмотров 34 тыс.