Boiler Flame Failure, 50 Apartments with No Heat 

The Apprentice Survival Guide
Подписаться 17 тыс.
Просмотров 39 тыс.
50% 1

0:16 Gas Valve Replacement
4:30 Leaking Commercial Water Heater
5:30 Thermostat Schedule Set to 55
7:03 28 Series H.B.Smith 9 Section Boiler Flame Failure
Our day commences with the aftermath of bad weather-a boiler room flood. Join me as we replace a water heater and boiler gas valve affected by the flood. Delve into the intricacies of dealing with water damage and ensuring the swift restoration of essential components to maintain a functional heating system.
As the morning unfolds, we encounter a leaking water heater, presenting yet another hurdle. Explore the process of inspecting and addressing the leak, understanding the nuances of water heater diagnostics and the importance of prompt action to prevent further damage.
The narrative takes an unexpected turn with a "No Heat" call. Dive into the troubleshooting process, only to discover a simple yet crucial issue-the thermostat setting is set to low. Gain insights into the importance of thorough system checks, even for seemingly straightforward issues, to ensure optimal heating performance.
But the challenges continue as we conclude our day in an apartment building with 50 units, all facing a heating crisis due to a flame failure. Explore the complexities of diagnosing and addressing flame failure issues, specifically caused by a loose wiring connection for the blower motor. Witness the strategic troubleshooting and meticulous repair process required to restore heat to all 50 units.
Through this storytelling, my goal is to offer viewers a firsthand glimpse into the unpredictable and diverse challenges faced in the HVAC profession. Whether you're a seasoned professional seeking relatable experiences or an enthusiast eager to explore the intricacies of the field, this narrative promises an engaging and educational journey through the complexities of "Water Heater and Gas Valve Replacements, Leaking Water Heater Inspection, Thermostat Troubles, and 50-Unit Heating Crisis."
#hvac #boiler #apprentice

Развлечения

Опубликовано:

 

19 дек 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 54   
@edc1569
@edc1569 6 месяцев назад
US electrics and boilers are wild, though fair play I couldn't imagine fixing an euro equipment that had sat in 4 foot of water.
@caru3257
@caru3257 4 месяца назад
We don’t.
@brendanawrach8351
@brendanawrach8351 4 месяца назад
15:25 Hey I just got into commercial heating and gas. I love and need this Shhh. Keep it up brother!
@daddygc5814
@daddygc5814 7 месяцев назад
I'm impressed, damn good job on all your calls
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
that means a lot brother, thank you!
@john7017
@john7017 7 месяцев назад
Bring your straight edge 6" machinist rule, dial gauge with magnetic base and some assorted shim stock to align the pump to the motor so the new coupling inset does not self destruct.
@j26a24d
@j26a24d 6 месяцев назад
has many experiences in this type of pump
@StormUSA
@StormUSA 6 месяцев назад
No waste of time, Well done Bro!
@musicnerd72
@musicnerd72 6 месяцев назад
Not sick of watching your videos. I find them very entertaining!... And BTW, I personally LIKE the music in your vids! Keep up the great work! 👍
@ignacio8597
@ignacio8597 7 месяцев назад
You can change the water heater gas valve without opening the water. Theres a screw on the bottom and the face comes off, then theres a screw and the actual valve comes off.
@BartlettTFD
@BartlettTFD 7 месяцев назад
Your troubleshooting techniques are outstanding👍 Great video.
@MrButuz
@MrButuz 6 месяцев назад
Your multimeter sure earns it's keep with all the crazy electrics!
@ephraimsilberberg708
@ephraimsilberberg708 7 месяцев назад
Good stuff
@JerseyTom
@JerseyTom 7 месяцев назад
Good vids man. If you include a timestamp with 0:00 in the description (e.g. "0:00 Intro"), it will show the different chapters on the timeline of the video
@PawsumGaming
@PawsumGaming 7 месяцев назад
Man, you're like the boiler doctor.. Good job with that gas valve swap. Still can't get over that amount of water..
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
Thanks you always brother! Yea it was a fun day, I’m surprised more didn’t get damaged down there
@loramurray7954
@loramurray7954 7 месяцев назад
Always bring your meter to every call!! That’s union 101!
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
couldn't agree more, especially a good meter!
@jaredreynolds4935
@jaredreynolds4935 7 месяцев назад
U need a 3/8 and 7/16 combo wrench for thermocouples
@nicholashartzler2205
@nicholashartzler2205 7 месяцев назад
Are big boilers still preferred over 2 or 3 redundant tankless boilers in series. I used to fix boilers at my last job and they were well due for replacement. I can’t imagine the are more then 75% efficient.
7 месяцев назад
I'm watching this from Europe. Is this the usual state of electrics in the USA ? 😲
@boby115
@boby115 7 месяцев назад
In old cities like New York , Philadelphia , Chicago , St. Louis , Boston, Baltimore, Detroit and I could list another two dozen older cities. Landlords will get the last dime out of a piece of equipment & wiring before modernizing and then it’s on a triage basis . Europe didn’t really start wiring homes until the late 1920 to 1930s far behind the United States at that time. The 1904 worlds fair in St. Louis was completely electrified (the electrical contractor that wired the world’s fair “Guarantee Electric “is still in business today). So your statement would be like me looking at a 1954 MG /TD & saying “you wire your cars that way? “ 😂.
@CommieCat
@CommieCat 6 месяцев назад
11:18 - so the wire worked itself out of the nut? All on its own? The 70v would be ghost voltage that would be invisible to a LowZ meter.
@timcat1004
@timcat1004 7 месяцев назад
How did you get my Kline 10 in 1 ?
@caru3257
@caru3257 4 месяца назад
I did attempt one bleeder replacement with the water on. The radiator had air. I got hot water all over me.
@SilverandCigars
@SilverandCigars 7 месяцев назад
couple more service calls after all that? Man I love where I work. Changing out that gas valve would of been my 8 hours
@alexbecker9588
@alexbecker9588 7 месяцев назад
Lol I have the same problem there is to much work not enough good techs
@TheShortStory
@TheShortStory 6 месяцев назад
The music was fine. Just mixed a bit loud
@axelwilner
@axelwilner 6 месяцев назад
Need a cranberry vodka to accompany the soundtrack.
@tyregalaxy28
@tyregalaxy28 7 месяцев назад
Nice i see you in jersey
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
hell yea!
@CommercialGasEngineerVideos
@CommercialGasEngineerVideos Месяц назад
50 apartments 😮. Oh noooo, what we gonna do.
@TheRAMBO9191
@TheRAMBO9191 7 месяцев назад
Not sick at all watching! I'm sad it was only 15 min I could watch an hour Unedited sir🍻
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
ill do my best for you brother!
@ITman496
@ITman496 6 месяцев назад
I thought all this looked familiar... Ah, Newark..
@rickchapman9232
@rickchapman9232 7 месяцев назад
Did that hot water heater fall over or was it laid down by hand? Was it glass lined?
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
I believe it was “laid” down by hand lol, I’m pretty sure I remember it being like that the last time I was in the boiler room
@berderk2796
@berderk2796 7 месяцев назад
Hey bro i just discovered your channel and thanks for showing the stuff you do, also what kind of books do you recommend for beginners? I'm an apprentice plumber but wanna expand my skill set and learn about the more technical stuff you do, any advice is appreciated
@elijah3807
@elijah3807 6 месяцев назад
Manufacturer literature and code books.
@donnellbaxter8050
@donnellbaxter8050 7 месяцев назад
What was the blue piece you put on te boiler.
@harryschrysan3183
@harryschrysan3183 7 месяцев назад
It's a diagnostic control
@mikev.1034
@mikev.1034 7 месяцев назад
👍👍
@ed6837
@ed6837 7 месяцев назад
Maybe the pump coupling destructed because they ran the pump with the valves shut
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
totally possible, not sure why the disconnect was on if the valve was closed but thats above my pay grade lol 🤦🏼‍♀️
@joeyf504327
@joeyf504327 7 месяцев назад
music is a bit loud at time and hard to hear what you're saying
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
thank you for the feedback brother! i will work on it
@walkingfreak
@walkingfreak 7 месяцев назад
Water heater elements is a fun one up until you get the element that wants to be a dick head and get stuck in the tank then you're scrambling around while water is dumping out.
@user-or1lu3ku3m
@user-or1lu3ku3m 6 месяцев назад
The editing is wild 😅 wtf is even going on
@kc0eks
@kc0eks 7 месяцев назад
Could not handle nyc traffic and chaos
@IvanBogdanovych
@IvanBogdanovych 7 месяцев назад
Hello, I'm a new subscriber. Do you have a video about your work, what is your specialization, where do you work, why do you work with metal, do you work with copper? It would be interesting to hear that about you. Of all the USA RU-vidrs, you are the best, you speak very well and politely. I like you very much. Thank you.
@paulparadiso941
@paulparadiso941 7 месяцев назад
You should use the proper tools
@theapprenticesurvivalguide
@theapprenticesurvivalguide 7 месяцев назад
like what?
@briansmyla8696
@briansmyla8696 7 месяцев назад
If you do any more of these, don't use music anymore.
@TheJmich2001
@TheJmich2001 7 месяцев назад
Stuntman calls those rubber bits "pizza toppings"
Далее
Amazing 100 Year Old Mansion Steam Heating System
24:14
THEY SAID PLEASE HURRY THE AC'S ARE NOT WORKING
45:53
Просмотров 264 тыс.
EVOLUTION OF ICE CREAM 😱 #shorts
00:11
Просмотров 4,8 млн
Finger Heart - Fancy Refill (Inside Out Animation)
00:30
Наше обычное утро 💕
00:42
Просмотров 914 тыс.
HVAC Nightmare: Units Crash Before Winter Storm
19:50
R290 Refrigerant Service Training | Leer Inc.
9:01
Просмотров 35 тыс.
Boiler Room Disaster Escalates to Apartment Flood!
27:07
This Circulator Pump Install BROKE Me
19:21
Просмотров 13 тыс.
Common Boiler Problems - SteamWorks
6:19
Просмотров 111 тыс.
Monster Steam Boiler is an Understatement
20:45
Просмотров 24 тыс.
Thermostat Wiring Explained!
10:35
Просмотров 962 тыс.
This Was a TERRIBLE Install….Until Now
16:29
Просмотров 32 тыс.
19 июля 2024 г.
0:20
Просмотров 9 млн
НРАВИТСЯ ЭТОТ ФОРМАТ??
0:37
Просмотров 7 млн