Budarus GB142 error 6L 

Grey Lady Plumbing & Heating
Подписаться 17
Просмотров 4,4 тыс.
50% 1

This is the most common problem I find with these. The Venturi breaks down overtime in the fuel air mixture he comes to lean for the unit to operate

Опубликовано:

 

8 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 4   
@scottwillis5434
@scottwillis5434 3 месяца назад
Thank you for the video! Seeing a 6A without a choke (the venturi appears intact), then it will run a minute or two, then there's a little "chuff!", the flame goes out and I see a 6L. I cleaned it recently, including the condensate bottle. It remains to check the drain pipe. One wild thought is the supply flex-pipe may be undersized and its auto-shutoff might be partially triggering? Except I would expect one of those to be snap-action and latch on.
@scottwillis5434
@scottwillis5434 2 месяца назад
Sniffed around after smelling a bit of propane, used a flashlight to look into the gap between the blower motor and blower body and saw that the blower shaft seal had popped out! Leak and airflow disturbance explained. Hopefully I can push it back in, maybe add something to keep it in place so I won't have to replace the $600? blower because an under-$1-to-manufacture seal popped out. Still going to replace it with a heat pump, but now it's a less urgent situation.
@tobybryce-cb6fm
@tobybryce-cb6fm 4 месяца назад
The title says 6l error code you discussed a 6a error code!
@louishale4977
@louishale4977 Год назад
you should change the description from 6l to 6a
Далее
Working On A German Buderus Boiler
52:16
Просмотров 24 тыс.
Buderus GB142 Boiler Code 6A 227
3:06
Просмотров 71 тыс.
Сказала дочке НЕТ!
00:24
Просмотров 1,2 млн
Starman🫡
00:18
Просмотров 14 млн
GB142 Heat Exchanger Cleaning
8:19
Просмотров 25 тыс.
GB 142 service  Code 6A 227 part 3
2:00
Просмотров 16 тыс.
Сказала дочке НЕТ!
00:24
Просмотров 1,2 млн