Daikin McQuay WMC magnetic bearing chiller: start, loaded run, stop 

bnkwupt
Подписаться 1,5 тыс.
Просмотров 52 тыс.
50% 1

Here is a longer video of the McQuay (now Daikin Applied) WMC magnetic bearing water cooled centrifugal chiller. In this video we do a startup with a large cooling load, let it pull down to temperature, then slowly remove the load and let it shut down.
I edited out the middle of the video to avoid boring you to tears. ;)
In case you're curious, this was filled with my iPhone 6.

Наука

Опубликовано:

 

25 сен 2014

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 66   
@HuyNguyen-vl4nh
@HuyNguyen-vl4nh 6 лет назад
It is very impressive , it is cool to see all the operation on the monitor and it is very quiet . Thank for sharing your video . I will recommend it to my director when we are replacing the TRANE centrifugal compressor chiller . Have a good day .
@bnkwupt
@bnkwupt 5 лет назад
Thanks for the comment. We're seeing significant energy savings (greater than 40%), especially on moderate days where outside temperature and humidity are relatively low.
@subcooledheatpump
@subcooledheatpump 9 лет назад
Amazing how quiet those run, even at full load.
@jasonjohnsonHVAC
@jasonjohnsonHVAC Год назад
Love they can get the superheat way way down and not flood the compressors. They have very precise control over system operations. Not long ago we were punching tubes on a York YMC.....258 tubes....get boring punching tubes all day.
@agmc6767
@agmc6767 9 лет назад
Thank you for the video.I learned a lot.
@masterchef6694
@masterchef6694 8 лет назад
thanks man.....is helping me supervise the chiller commissioning
@RAVNEETBAL
@RAVNEETBAL 9 лет назад
This is the best video I ever seen, thanks lot for sharing
@NicolasLorenzo993
@NicolasLorenzo993 7 лет назад
muito bom parabéns a Daikin
@dangerousdan4184
@dangerousdan4184 7 лет назад
Very interesting, thanks!
@mchinchilla9791
@mchinchilla9791 Год назад
Greetings, I liked the video, I would like to know what parameters control the position of the expansion valve?
@davidperry4013
@davidperry4013 Год назад
I love chillers
@milsoncastro
@milsoncastro 4 года назад
Es un simple compresor , tornillos. Él importante es la alimentación eléctrica.. Los cables eléctricos son fundamentales y los terminales.... tengo más de 20000 horas.daking..hermoso.es el prosesos del gas.. consumo . mucha energía..es convertir.. Como esplicar un piloto elevarse un avión.! Es desde freon 11..
@skismile42
@skismile42 4 года назад
Nice video
@waseemsabir9405
@waseemsabir9405 6 лет назад
How we can check that how much gas filling is required? & how much gas present is in the system??
@brendankilgallon403
@brendankilgallon403 8 лет назад
Hi - really good video - just one question - a Spec. Item for TURBOCOR Chillers is that they have VSD Control with Variable Speed Drive between 10% and 100% which one would assume means that the Capacity Control is between these limits. Looking at the video. the Compressor speed was almost constant until the compressor stopped and also the IGV's appeared to be at 100% at the same time. The Power Input dropped, but how is the capacity control achieved - it appeared to be almost 2 stage control - Compressor 1 + 2 Operating in an On / Off Mode. Just Curious..? Brendan
@bnkwupt
@bnkwupt 5 лет назад
Hi Brendan, Capacity is controlled by a number of things - motor speed, vane position and the electronic expansion valve. To prevent stalling of the refrigerant flow, the compressor speed never drops below 80% except during startup. One compressor will run up to full load, then the system starts the second compressor to add capacity, at which point both compressors work together to maintain the leaving chilled water temperature. In this video, as building load is satisfied, both compressors ramp down to about 80%, then one compressor will turn off, leaving the remaining compressor to handle the load. As load decreases further, the one remaining compressor will slow itself down from 100% to about 80%, before finally shutting off. Note that motor speed and output capacity are related, but not at a 1:1 ratio. 80% speed is the lowest and 100% speed is maximum capacity (except during startup).
@abdulkhadermohin5978
@abdulkhadermohin5978 3 года назад
@@bnkwupt how about unloading capacity?
@bnkwupt
@bnkwupt Год назад
@@abdulkhadermohin5978 I’d estimate that it can unload down to about 15% of its cooling capacity.
@hmcgrath100
@hmcgrath100 8 лет назад
Nice chiller! Under low humidity & OA temp operating conditions, dramatically higher delta Ts are possible (16 - 20 degrees.) In order to achieve these efficiency improvements, the condenser and ChW pumps will need to be slowed down - but not less than minimum flow... The CUP sequence of operation should be configured to provide minimum energy use for the sum of the chilled and condenser water pumps & fans.
@bnkwupt
@bnkwupt 5 лет назад
This installation has fixed speed pumps for both chilled water and condenser water. We have another installation with variable speed pumps, but it doesn't actually seem to save any energy on these particular machines.
@gabrielfraga8335
@gabrielfraga8335 7 лет назад
Hi, thank you for the video, it was very enlightening! I am intending to develop a way to preddict the amount of power it is possible to save acording with the temperature set up in the evaporator or the condensador. Do you have any idea how to do that?
@bnkwupt
@bnkwupt 5 лет назад
Energy efficiency of the chiller depends on the design of the unit. For example, this centrifugal unit is most efficient when the condenser water temperature is at or below 72F. Screw chillers like higher condenser water. Some people will tell you that it's better to run a slower cooling tower fan speed and hotter condenser water temperature, but for this particular type of unit, the energy required to run the tower fan at a higher speed is far less than the energy required to run the compressors at a higher speed (to overcome the increased lift pressure from the higher condenser water temp). It's complicated, but most manufacturers will provide charts that explain the most efficient operating conditions.
@jmayer29
@jmayer29 8 месяцев назад
I've done dozens of plants, and there isn't any one answer to this. Plant efficiency depends on dozens of factors, and the most successful optimization efforts I've worked with have involved complex models of a particular plant and optimizing all the flows and temperatures through the system based on load, weather, chiller type, etc. And unfortunately, all of this will be for naught if the connected loads are operating efficiently. Efficiency is everything from the cooling tower fan to the damper on the VAV box.
@davida1hiwaaynet
@davida1hiwaaynet 7 лет назад
To quote a friend, those Turbocor compressors sound like 'pure sex' when they spools up. :) Very nice machine.
@craigmohyde4289
@craigmohyde4289 2 года назад
Did you make a yenta file on the compressors
@HuyNguyen-vl4nh
@HuyNguyen-vl4nh 6 лет назад
How many tons is your chiller ? What is the maximum RPM of the compressors when they are at fully loaded and the vanes fully opened ?
@bnkwupt
@bnkwupt 6 лет назад
It's rated at 180 tons nominal capacity. Max compressor RPM depends on condenser water temperature. Perhaps 35,000?
@mzunguwrites6085
@mzunguwrites6085 7 лет назад
Your flow rate remained 0. Did you have a sensor out you didn't mention? You mentioned banging the tubes, does this mean you are running straight water not glycol? If so why not? Also it would be really interesting to hear a discussion of what happens to the chiller during a power blinkage or outage?
@bnkwupt
@bnkwupt 7 лет назад
mzungu Writes this unit doesn't monitor flow rate other than yes/no.
@bnkwupt
@bnkwupt 4 года назад
Each compressor has a super-capacitor that will maintain the magnetic field long enough for the compressors to coast down to a safe and complete stop. This unit is running straight water with treatment chemicals - no glycol. Glycol has is less efficient at transferring heat and is unnecessary in this application because all of the chilled water plumbing is inside of the building. If the chiller was outside, glycol would be necessary.
@martylynchian8628
@martylynchian8628 9 лет назад
How much power does that thing take? Do you have to notify the power company before turning it on?
@bnkwupt
@bnkwupt 7 лет назад
Marty Lynchian at maximum output, it only consumes about 110,000 watts. On an average summer day, maybe 60,000. No need to notify the power company.
@davidtexidor747
@davidtexidor747 7 лет назад
how to turn on a chiller
@craigmohyde4289
@craigmohyde4289 2 года назад
The pump and fan unless controlled by the chiller does it’s own thing
@bnkwupt
@bnkwupt 2 года назад
In this application, the pumps and the tower fan are controlled by the chiller, as shown on the screen.
@mtremblay231
@mtremblay231 9 лет назад
What does an inlet guide vane position of greater than 100% indicate?
@bnkwupt
@bnkwupt 9 лет назад
It just indicates that they're wide open. I don't know why they chose to display a value greater than 100%.
@YSful
@YSful 9 лет назад
VeeDubTDI Refrigerant pre-rotation takes place after 100% IGV and it is done for compressor efficiency improvement purposes
@mtremblay231
@mtremblay231 9 лет назад
Thanks. I wasn't aware of that.
@douro20
@douro20 9 лет назад
I didn't think they used Turbocor compressors in these.
@bnkwupt
@bnkwupt 9 лет назад
They most certainly did use Danfoss Turbocor compressors on the WMC.
@craigmohyde4289
@craigmohyde4289 2 года назад
Do you work for Daikin?
@therandomchannel6103
@therandomchannel6103 Год назад
How can you set the screen to sleep, got some chillers that their screens never go to sleep on their own
@bnkwupt
@bnkwupt Год назад
You have to exit the machine’s software and return to the Windows screen. From there, you’d configure your screen saver settings just like you would on a desktop PC. I’ve moved on from this job so I can’t give you a step-by-step.
@therandomchannel6103
@therandomchannel6103 Год назад
@@bnkwupt oh that’s easy then, just how do you exit out of the program haha
@bnkwupt
@bnkwupt Год назад
@@therandomchannel6103 open the control box and press the small power switch on the computer inside near where you’d insert a USB drive. This will turn the display computer off. Then press again to turn it on. It should boot into Windows. There might be an easier way but I don’t remember what it is.
@therandomchannel6103
@therandomchannel6103 Год назад
@@bnkwupt awesome I’ll give that a try next time I’m over there. Thank you!
@kilemontana1257
@kilemontana1257 5 лет назад
hi, why the panel does not showme data
@huyenvuong9647
@huyenvuong9647 4 года назад
Me too, please!
@huyenvuong9647
@huyenvuong9647 4 года назад
How to reset?!
@craigmohyde4289
@craigmohyde4289 2 года назад
Don’t forget condenser relief
@henrymendez5934
@henrymendez5934 Год назад
Do you have the Technician password for this chiller?
@bnkwupt
@bnkwupt 10 месяцев назад
Sorry, I only have the operator password, not the technician password.
@ashusingh1478
@ashusingh1478 6 месяцев назад
Magnetic chiller plant ka full knowledge chahiye Hindi me
@alejandroelenes5397
@alejandroelenes5397 3 года назад
Excellent video!!! can you gimme the technician password??
@craigmohyde4289
@craigmohyde4289 2 года назад
Does not know a Daikin WMC or how it operates
@bnkwupt
@bnkwupt 2 года назад
Where are your chiller videos, Craig?
@jonapriyanto2967
@jonapriyanto2967 5 лет назад
Add subtittle in bahasa pls..
@deviratnasari2933
@deviratnasari2933 5 лет назад
add subtittle in video pls
@IrfanKhan-lg6px
@IrfanKhan-lg6px 6 лет назад
daiken chiller start sar speak hindi please
@ashusingh1478
@ashusingh1478 6 месяцев назад
Sir Hindi me banao video please
@craigmohyde4289
@craigmohyde4289 2 года назад
It is a Daikin WMC chiller. Not a MCquay
@bnkwupt
@bnkwupt 2 года назад
It was a McQuay when we bought it and it says both Daikin and McQuay on the unit. Daikin bought the McQuay factory in Staunton, VA where this unit was manufactured. Just because Daikin bought out McQuay doesn’t mean this unit isn’t a McQuay.
Далее
Daikin / McQuay Chiller Surging After Rebuild
10:18
Просмотров 2,1 тыс.
Magnetic Bearing Chiller Down
7:44
Просмотров 9 тыс.
York Magnetic Centrifugal Chiller
27:35
Просмотров 24 тыс.
Daikin VRV Troubleshooting Fun
22:19
Просмотров 23 тыс.
DAIKIN APPLIED AMERICANS CHILLERS  1080P
27:19
Просмотров 9 тыс.
How Air and Water Cooled Chillers Work
13:14
Просмотров 83 тыс.
Oil System YK York Chiller
16:54
Просмотров 15 тыс.
Prepping Chiller for Startup
19:01
Просмотров 13 тыс.
YK Overview Centrifugal Chiller York HVAC Training
27:47
#engineering #diy #amazing #electronic #fyp
0:59
Просмотров 2,4 млн